ABB Installation Products K655SELR 600 Amp, 15/25kV, 600 Series Spiking Elbow wih Spiking Contact, Insulating Plug, Cap…
UPC: 783786376599
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetrical momentary withstand
- Supports 15/25kV voltage classes (up to 28kV phase-to-phase, 16.2kV phase-to-ground)
- Fully shielded, fully submersible molded rubber housing with 100% peroxide-cured EPDM construction
- Spiking Aid "T" body enables cable contact cutting without splicing
- Compatible with standard 600A class equipment and Elastimold Regular "LR" series elbows
Specifications
Amperage Rating | 600 A |
Connection | Compression |
Connection Type | Spiking Elbow |
Current Rating | 600 A |
Insulation | EPDM Rubber |
Material | EPDM-Rubber |
Material | Composite (Insulating Materials) |
Series | 600 Series |
Type | Spiking Elbow |
Voltage Rating | 15/25 kV |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
VAG-022-00
Solenoid Valve Connectors, Field Wireable, 3 Pole, Form A 18mm, 24V, 10A, LED w/MOV, .5-NPT opening
T1505063000-000
Rectangular hoods and bases portfolio features base housing, cover, hood, or hood and base housing assembly with inserts connector product types. Products are designed for bottom, side, top, or top and side cable entry. Rectangular hoods and bases offer solutions with a variety of hood and base locking device types as well as connector mounting types.
K655LINKCLR-L0330SWG
RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.180-1.465 inches, Conductor Size 500 Stranded/Compressed, SwitchGear
K655LINKCLR-K0300SWG
RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.090-1.310 inches, Conductor Size 350 Stranded/Compressed, SwitchGear
K655DSR-L0330
25kv, 600 Amp, Direct Test Straight Receptacle Elbow, Deadbreak, Cable Insulation Diameter 1.180-1.465. Aluminum Lug, Conductor Size 500 Stranded/Compressed or 600 Compact/Solid. 17 inches long. Mates with K650SRA.Frequently Asked Questions
What is the Corona Extinction voltage for 28kV class?
For the 25/28kV voltage class, the Corona Extinction voltage is 21.5kV AC at 3pC sensitivity.
What is the K655SELR connector used for?
The K655SELR provides fully shielded, submersible deadfront cable connections to high voltage apparatus and allows splicing/tapping 600 A systems.
What voltage classes is the K655SELR rated for?
The K655SELR connector is rated for use on systems up to 28kV class. It has specific ratings for 15kV and 25/28kV voltage classes.
What is the continuous current rating for this connector?
The K655SELR connector has a continuous current rating of 600 Amps for both 15kV and 25/28kV voltage classes.
What is the momentary current rating?
The momentary current rating for the K655SELR connector is 25kA Symmetrical for 10 Cycles. This applies to both 15kV and 25/28kV classes.
Is the K655SELR connector submersible?
Yes, the K655SELR connector features a fully shielded, fully submersible molded rubber housing.
How much additional distance does the extended elbow span?
This longer elbow uses an extension connector to span an additional 8-5/16 inches (211mm) distance.
What items are included in the K655SELR kit?
Each kit contains an elbow connector housing, copper compression lug, stud, insulated plug with cap, lubricant tubes, cable adapter, installation instructions, and a crimp chart.
How do I select the correct catalog number?
To select the catalog number, determine the cable's insulation diameter for the W code, choose the connector material type, and select the compression lug code based on conductor size.
What is the maximum phase-to-ground operating voltage for 28kV class?
For the 25/28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.
How to Install the K655/K656/K675/K676ELR Extended Deadbreak Elbow Connector
This guide provides detailed instructions for installing the K655/K656/K675/K676ELR Extended Deadbreak Elbow Connector, designed for fully shielded, submersible cable connections to high voltage apparatus and for splicing/tapping 600-ampere or 900-ampere systems up to 28kV class. All apparatus must be de-energized during installation or removal of parts. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Measuring tape or ruler, Beveling tool or sharp knife, Cleaning supplies, Wire brush (for aluminum conductors), Crimping tool, Torque wrench, Wire strippers/cutters, Hotstick, Capacitance sensing device
Supplies needed:
Tape marker, Silicone grease (lubricant), Cable Adapter, Compression Lug, Extension Contact, Flat Washer, Disc Spring, Bolt (for extension contact), Extended Elbow Housing, Threaded Stud (if needed), Insulating Plug (if applicable), Voltage Detection Cap (if insulating plug used), Grounding wire (minimum No. 14 AWG Copper), Suitable ground connector, Waterproofing material
- Prepare the Cable for Installation
DANGER: Ensure all apparatus is de-energized. Position the cable in its final assembled position with enough slack. For concentric neutral cable, unwind the neutral wires. Cut the cable 10 inches (254mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm). Remove the outer jacket (where applicable) and semi-con shield, then install a tape marker to the specified dimension for your cable type (e.g., 9-3/4 inches, 10-3/4 inches, or 12-3/4 inches). Do not cut or nick the cable insulation.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean the cable insulation, then lubricate it with silicone grease, working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the cable adapter or conductor. The exposed conductor length MUST BE 4 3/8 to 4 11/16 inches (111mm to 119mm). For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping (it MUST BE less than 6 1/2 inches / 165mm). Crimp the compression lug according to its supplied instructions. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping MUST BE 6 1/2 to 7 1/4 inches (165mm to 184mm).
- Attach the Extension Contact
Attach the extension contact to the compression lug using the flat washer, disc spring, and bolt supplied. Maintain a straight line between the lug and contact, then tighten the bolt to 50-60 foot-pounds torque.
- Install the Extended Elbow Housing
Lubricate the cable adapter and the inside of the elbow cable entrance with silicone grease. Install the extended elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Connect to Mating Product
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with silicone grease, ensuring surfaces remain clean. Push the elbow onto the mating part, aligning the hole in the extension contact with the stud on the mating part.
- Secure the Mating Connection
Clean and lubricate both the elbow and the mating part with silicone grease. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap with silicone grease. Place the cap on the elbow and push down hard until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage; follow voltage test directions.
- Ground the Cable Shield and Waterproof
Insert one end of a piece of grounding wire (with ampacity at least equivalent to No. 14 AWG Copper) through each grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (K656ELR/K676ELR Models)
For K656ELR/K676ELR models, perform a voltage test. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable capacitance sensing device, following its manufacturer’s directions, to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.