Contact for Pricing
Overview
- 600 Amp, 25kV rating for medium-voltage applications
- Aluminum compression lug for superior conductivity
- Insulated cap included for enhanced safety
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Compatible with AWG/kcmil 500 stranded, 600 kcmil compacted solid, and mmSquared compact 250/300 conductors
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | 1.515 inch to 1.780 inch |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656RLR-L0330
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
656LRTP-L5380
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
775LRTP-K5240-DRG
900 Amp, 35kV, Deadbreak, Stick-Op Connector Kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. With Insulated Cap. 900 Amps - Copper Conductor only.
656LRTP-H2330-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit, Insulated Cap. Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
656LRTP-L2380-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit, Insulated Cap. Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655LRTP-H0270
600 Amp, 25kV, Stick-Op Connector Kit. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
655LRTP-J0260-DRG
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.How to Install the 273/375DRG(3) Insulated Cap with Ground Lead
This guide details the safe installation of the ELASTIMOLD 273/375DRG(3) Insulated Cap with Ground Lead, designed for insulating, shielding, and watersealing 25kV and 35kV class loadbreak bushing interfaces.
Estimated time: 15m
Tools needed:
Hotstick, Live-line tool
Supplies needed:
273/375DRG(3) Insulated Cap with Ground Lead, ELASTIMOLD approved lubricant
- Prepare for Installation and Ensure Safety
Before beginning, ensure all apparatus is de-energized. Inspect all parts for damage, correct rating, and compatibility with mating parts. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Read all instructions thoroughly and have all required tools at hand. Do not touch or move energized products. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Connect the Electrostatic Grounding Wire
Connect the free end of the electrostatic grounding wire to the system ground. Leave enough slack in the wire to allow for hot-stick operation of the insulated cap. CAUTION: Ensure the electrostatic grounding wire is trained so it does not contact the bushing interface during operation. WARNING: If the ground lead disconnects during operation, do not attempt to reattach it without first pulling the insulated cap off the bushing with the hotstick.
- Lubricate the Insulated Cap
Remove the protective cover from the insulated cap. Lubricate the cap's internal mating surface using only the supplied lubricant or other ELASTIMOLD approved lubricants. Do not substitute, as other lubricants may be harmful to this product and its mating parts. Keep the internal mating surface free from dirt and grime. Always replace the protective cover when the cap is not in use.
- Install the Insulated Cap onto the Bushing
Firmly attach a hotstick (minimum 8 ft. recommended) to the insulated cap's pulling eye. Insert the male contact of the insulated cap into the loadbreak bushing. Push the cap home with a fast, firm, and straight motion. Verify that it is fully mated and the locking ring is properly seated. Once fully installed, detach the hotstick from the insulated cap.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.