ABB Installation Products K655LR-K0330 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786628902
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetrical momentary rating
- Accommodates conductor sizes: 500 kcmil compressed/stranded to 600 kcmil compact/solid, or 250/300 mm² compact
- Cable insulation diameter range: 1.090 inch to 1.310 inch
- Meets ANSI/IEEE Standard 386 with 8.3kV max phase-to-ground and 14.4kV max phase-to-phase at 15kV
- Fully shielded, molded rubber housing with 100% peroxide-cured insulation and conductive EPDM materials
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series Deadbreak |
Series | 600 Series |
Size | 1.090-1.310 inch (cable insulation diameter) |
Size | 1.090 inch to 1.310 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.5500 L |
Package Weight (Metric) | 2.9710 kg |

K655LR-J0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
K655LR-K033020MAKS
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Adapter Metal Tape Shield.
K655LR-K0320-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 450 or Compact/Solid 500/550. Cold-Shrinkable Jacket Seal Included.
K655LR-K0300-SG3
15-25kv 600 Amp Dead Break Elbow With Sealing Kit, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K655LR-K0280
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 250 or Compact/Solid 300.
K655LR-K0320
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 450 or Compact/Solid 500/550.
K655LR-K0290
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.Frequently Asked Questions
What is the cable insulation diameter range?
The cable insulation diameter range is 1.090 inch to 1.310 inch.
What voltage ratings does this elbow connector support?
The K655LR-K0330 supports 15kV and 25kV voltage ratings for medium-voltage applications.
What material is the compression lug made of?
The compression lug is made of aluminum.
What conductor sizes are compatible with this connector?
The connector accommodates 500 or 600 kcmil compressed/stranded conductors, or 250/300 mm² compact conductors.
Is this a deadbreak or loadbreak connector?
This is a deadbreak connector, allowing safe connection and disconnection under load.
What series does this elbow connector belong to?
This connector is part of the ABB 600 Series deadbreak elbow connectors.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of K655/K675LR Deadbreak Elbow Connectors, designed for fully shielded, submersible high-voltage cable connections. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 2h
Tools needed:
Wire strippers, Wire brush, Crimping tool, Torque wrench, Hotstick, Capacitive voltage sensing device
Supplies needed:
K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant (silicone), Threaded Stud (if mating part lacks one), Grounding wire (min. No. 14 AWG Copper), Suitable grounding connector, Tape marker, HV insulated cap(s) or connector(s)
- Perform Initial Safety Checks and Part Inspection
DANGER: All apparatus must be de-energized during installation or removal of parts. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, rating, and compatibility. Check package contents for completeness. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Have all required tools at hand and maintain cleanliness.
- Assemble Cable and Cut to Length
Assemble the cable in its final position, ensuring enough slack for adequate clearance to remove elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the center line of the mating product.
- Clean Cable Surface and Prepare Cable
Clean the outer surface of the cable a distance of 24 inches (610mm) or up to the bent back concentric neutral wires. Follow the specific cable preparation steps (A, B, or C) that apply to your cable type, including removing the outer jacket (if applicable) and preparing the cable according to the provided diagrams and dimensions for cable insulation, semi-con shield, and tape marker.
- Bevel Cable Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Protruding Conductor Insulation
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution not to cut or nick the cable adapter or the conductor. Verify that the length of the exposed conductor is between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly from the beginning.
- Crimp Compression Lug onto Conductor
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 6-3/8 inches. Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-3/8 inches to 7-1/8 inches (162mm-181mm); otherwise, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Ensure the cable adapter remains flush with the tape marker; if not, reposition the cable adapter. Once confirmed, remove the tape marker.
- Prepare and Lubricate Mating Apparatus
Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean. DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected.
- Connect Elbow to Mating Apparatus Stud
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. Ensure a secure and proper connection.
- Connect Opposite Mating Part to Elbow
Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part to ensure proper connection and sealing.
- Install Insulating Plug and Cap (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps securely into place. This step prepares for subsequent voltage testing.
- Ground the Cable Shield
Insert one end of a grounding wire, with an ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist it to form a small loop. Do not damage the grounding eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Capacitive Voltage Test
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per instructions. To test for voltage, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device made for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means, as contamination or wrong equipment can give false readings. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.