ABB Installation Products K655LR-K0320 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786660391
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 15/25kV voltage rating
- 600 Series Deadbreak Elbow design
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for secure connection
- Accommodates cable insulation diameters from 1.090" to 1.310"
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.4000 L |
Package Weight (Metric) | 2.9030 kg |

K655YSR-K2320
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
K655LR-K0290
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.
K655LR-H-2270
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Copper Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125.
K655LR-K0240
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
K655LR-G5270-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Bi-Metal Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125. Cold-Shrinkable Jacket Seal Included.
K655LR-K0270
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125.
K655LR-K0300
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K655LR-J2300
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.Frequently Asked Questions
What is the maximum operating voltage for this elbow connector?
The elbow connector is rated for 15kV voltage class with a maximum phase-to-ground operating voltage of 8.3kV, and for 28kV voltage class with a maximum phase-to-ground operating voltage of 16.2kV.
What conductor sizes can this connector accommodate?
It can be used with conductor ranges from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for compatible cables?
The connector is compatible with insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the continuous current rating of the connector?
The connector has a continuous current rating of 600 Amps.
What is the momentary current rating?
The connector has a momentary current rating of 25kA symmetrical for 10 cycles.
What is the impulse withstand rating for the 28kV class?
For the 28kV voltage class, the impulse withstand rating is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage for the 15kV class?
For the 15kV voltage class, the AC one-minute withstand voltage is 34kV.
What is the corona extinction rating for the 28kV class?
The corona extinction rating for the 28kV voltage class is 21.5kV AC at 3pC sensitivity.
What standards does this deadbreak elbow meet?
This deadbreak elbow meets ANSI/IEEE Standard 386, Latest Revision.
What materials are used in the construction of the housing?
The housing is made of 100% peroxide-cured molded rubber, including insulation and conductive EPDM materials.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K655/K675LR Deadbreak Elbow Connectors, including cable preparation, lug crimping, and connection to mating apparatus for 15kV and 25kV class systems.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Cutting tool, Wire brush, Crimping tool, Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
Lubricant, Compression Lug, Threaded Stud (if mating part not equipped), Wire (at least No. 14 AWG Copper), Suitable connector (for grounding), Tape marker, Protective caps, Silicone lubricant, Insulating Plug (if applicable)
- Ensure Safety and Prepare Workspace
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Gather all required tools and supplies, ensuring cleanliness throughout the procedure. Inspect all components for damage, proper rating, and compatibility with mating parts.
- Prepare the Cable for Connection
Assemble the cable in its final position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent-back concentric neutral wires. Remove the outer jacket (where applicable) and prepare the cable insulation and semi-con shield according to the specific cable type and provided diagrams, ensuring proper tape marker placement.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-1/4” and 4-9/16” (108mm-116mm); if not, re-do the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” before crimping; this dimension should be less than 6-3/8”. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-3/8” to 7-1/8” (162mm-181mm); if not, re-do the assembly.
- Install the Elbow onto the Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Make sure the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part with the lubricant supplied, keeping surfaces clean.
- Secure the Elbow to the Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect the Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground according to the instructions supplied with the grounding device, or through an alternate method if no grounding device is used. It is also recommended that the jacket of the cable be waterproofed at this point to prevent moisture from entering the cable.
- Torque Components for 600amp L-Kits (Caution)
CAUTION: When constructing 600amp L-Kits, be sure to tighten each component to the specified torque per the instructions provided with those components.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or using the wrong measuring equipment can provide a false “no voltage” indication. To prevent serious or fatal injury, treat the elbow as energized until the “no voltage” test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.