ABB Installation Products K655LR-K0320-S 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786324644
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating
- 15/25kV voltage class
- Fully shielded, dead-front, submersible design
- Accommodates cable insulation diameters from 1.090" to 1.310"
- Includes aluminum compression lug, insulated plug, cap, stud, cable adapter, and cold-shrinkable jacket seal
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection Type | Deadbreak Elbow |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum, Rubber, EPDM |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 600 Series |
Series | 600 Series Deadbreak |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Size | 1.090-1.310 inch (cable insulation diameter) |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 7.3000 L |
Package Weight (Metric) | 3.3110 kg |

K655YSR-K2320
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
K655LR-K0300-SG3
15-25kv 600 Amp Dead Break Elbow With Sealing Kit, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K655LR-K0280
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 250 or Compact/Solid 300.
K655LR-K0320
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 450 or Compact/Solid 500/550.
K655LR-K0290
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.
K655LR-H-2270
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Copper Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125.
K655LR-K0240
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
K655LR-G5270-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Bi-Metal Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG Compressed/Stranded 4/0 or kcmil Compact/Solid 250 or mm2 Compact 125. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the maximum operating voltage for the K655LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.
What conductor sizes can the K655LR handle?
It can be used with conductor ranges from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for this elbow connector?
The insulation diameter range is from 0.640 inches to 1.935 inches.
What is the continuous current rating for the K655LR?
The continuous current rating for the K655LR is 600 Amps.
What is the momentary current rating for the K655LR?
The momentary current rating is 25kA Sym for 10 Cycles.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand for the 15kV voltage class?
The AC one-minute withstand for the 15kV voltage class is 34kV.
What is the AC one-minute withstand for the 28kV voltage class?
The AC one-minute withstand for the 28kV voltage class is 45kV.
What is the corona extinction rating for the 15kV voltage class?
The corona extinction rating for the 15kV voltage class is 11kV AC at 3pC sensitivity.
What is the corona extinction rating for the 28kV voltage class?
The corona extinction rating for the 28kV voltage class is 21.5kV AC at 3pC sensitivity.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere K655/K675LR Deadbreak Elbow Connectors on 15kV and 25kV class systems.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Wire brush (for aluminum conductors), Crimping tool (per lug instructions), Hotstick, Suitable voltage sensing device/meter (for capacitive test points), Torque wrench (per mating part instructions)
Supplies needed:
K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant (silicone type), Threaded Stud (if mating part not equipped), No. 14 AWG Copper wire (or equivalent for grounding), Suitable grounding connector, Grounding device (if used), Waterproofing material (for cable jacket), HV insulated cap(s) or connector(s) (to replace shipping covers), Tape marker
- Ensure Safety and Prepare Components
DANGER: De-energize all apparatus before beginning installation. This product must be installed only by competent personnel trained in high voltage safety practices. Inspect all package contents and components for completeness, damage, proper rating, and compatibility with mating parts. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Prepare the Cable for Connection
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for 24 inches (610mm) or up to the bent-back concentric neutral wires. Follow the specific cable preparation instructions (e.g., jacket removal, shield preparation) as detailed in the document for your cable type (non-jacketed, jacketed, Unishield, lead sheath, etc.).
- Install Cable Adapter and Prepare Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to nick the cable adapter or conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm); if not, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the lug. Measure the 'Check Dimension' before crimping; it must be less than 6-3/8 inches. Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-3/8 inches to 7-1/8 inches (162mm-181mm); if not, redo the assembly.
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter is still flush with the tape marker; if not, reposition it. Remove the tape marker.
- Connect to Mating Apparatus
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove any protective shipping caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End and Torque
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to the specified torque per instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield and Waterproof
Insert one end of a piece of wire (at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with a grounding device if used, or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
The ELASTIMOLD deadbreak elbow connector has an integral capacitance test point. To use it: 1. Remove the test point cap with a hotstick, peeling it off at an angle. 2. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device made for capacitive test points, following its manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can give false readings. 3. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.