ABB Installation Products K655LR-J0320 15/25kV 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter)
UPC: 783786412778
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating with 600A continuous current capacity
- Deadbreak design enables safe connection/disconnection on de-energized systems
- Fully shielded, submersible molded rubber housing for wet/corrosive environments
- Includes insulated plug, cap, stud, lug, and cable adapter in one SKU
- Meets ANSI/IEEE Standard 386 for 15kV and 25kV classes
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15/25 kV |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.4000 L |
Package Weight (Metric) | 2.9030 kg |

K656LR-H0320-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 450 or Compact/Solid 500. Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K655LR-J0280
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 250 or Compact/Solid 300.
K655LR-J0230-SG3
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG Compressed/Stranded #1 or Compacted/Solid 1/0 or mm2 Compact 50. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K655LR-H0260
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed/Stranded 3/0 or Compact/Solid 4/0 or mm2 Compact 95.
K655LR-K0300-SG1
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. 200ECS-G1 Jacket Seal and Grounding Kit Included.
K655LR-L0350
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 600 or Compact/Solid 700.
K655LR-L0390
15/25kV 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Conductor Size kcmil Compressed/Stranded 800.
K655LR-H0290
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.Frequently Asked Questions
What is the maximum operating voltage for this elbow connector?
The elbow connector is rated for 15/25kV. For the 15kV class, the max phase-to-ground operating voltage is 8.3kV, and for the 28kV class, it is 16.2kV.
What conductor sizes can this elbow connector accommodate?
It can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the acceptable range for cable insulation diameter?
The cable insulation diameter can range from 0.640 inches to 1.935 inches.
What is the continuous current rating of the connector?
The connector has a continuous current rating of 600 Amps.
What is the momentary current withstand rating?
It can withstand a momentary current of 25kA symmetrical for 10 cycles.
What is the impulse withstand rating (BIL)?
For the 15kV class, the BIL is 95kV. For the 28kV class, the BIL is 140kV.
What is the AC one-minute withstand voltage?
For the 15kV class, the AC one-minute withstand is 34kV. For the 28kV class, it is 45kV.
What is the DC fifteen-minute withstand voltage?
For the 15kV class, the DC fifteen-minute withstand is 53kV. For the 28kV class, it is 84kV.
What is the corona extinction rating?
For the 15kV class, the corona extinction is 11kV AC at 3pC sensitivity. For the 28kV class, it is 21.5kV AC at 3pC sensitivity.
Can this connector be used in submersible applications?
Yes, it features a fully shielded, fully submersible molded rubber housing.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 655/675LR and K655/K675LR deadbreak elbow connectors. These connectors establish fully shielded, submersible cable connections for 15kV and 25kV class high voltage systems.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Cable stripping tool, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable voltage sensing device
Supplies needed:
655/675LR or K655/K675LR Deadbreak Elbow Connector kit, Cable (appropriate type), Tape marker, No. 14 AWG Copper wire (or equivalent ampacity), Suitable grounding connector, Grounding device (if applicable), HV insulated cap(s) or connector(s), Lubricant, Silicone lubricant
- Prepare the Cable for Assembly
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean the Cable Outer Surface
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable Insulation and Shield
Prepare the cable according to its type (e.g., non-jacketed, jacketed, Unishield, lead sheath) by removing the outer jacket (if applicable) and exposing the cable insulation, semi-con shield, and neutral/shield wires as per the provided diagrams. If using a 20MA/21MA grounding device, 600ECS Jacket Cable Seal, or 10TL cable shield adapter, refer to their specific installation instructions.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean, then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-1/4” and 4-9/16” (108mm-116mm); otherwise, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping (this dimension should be less than 6-3/8”). Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8” to 7-1/8” (162mm-181mm) after crimping; otherwise, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products for Connection
DANGER: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place. Proceed to voltage test directions.
- Ground the Cable Shield
Insert one end of a wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop. Do not damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no grounding device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Final Torque Check (for L-Kits)
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per the instructions provided.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device and is NOT directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a hotstick to remove the test point cap, peeling it off at an angle rather than pulling directly. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, following its manufacturer’s directions, to determine if the cable is energized. Contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.