ABB Installation Products K655LR-H0260 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786426256
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp current rating
- 15/25kV voltage class
- 600 Series Deadbreak Elbow design
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for 3/0 AWG to 95 mm2 conductors
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.4000 L |
Package Weight (Metric) | 2.9030 kg |

K656CY-H0260-S
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. Cold-Shrinkable Jacket Seal Included.
K655LR-K0300-SG1
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. 200ECS-G1 Jacket Seal and Grounding Kit Included.
K655LR-L0350
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 600 or Compact/Solid 700.
K655LR-L0390
15/25kV 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Conductor Size kcmil Compressed/Stranded 800.
K655LR-H0290
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.
K655LR-K0300-S
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. 200ECS Jacket Seal Included.
K656LR-L0320-S
Elbow Connector with Test Point, 600 Amp, Dead Break, 15/25 KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 450 or Solid 500/550. 200ECS Jacket Seal Included.Frequently Asked Questions
What is the maximum voltage rating for this deadbreak elbow?
The ABB K655LR-H0260 deadbreak elbow has a voltage rating of 15/25kV.
What conductor sizes can this elbow accommodate?
This elbow accommodates compressed/stranded conductors of 3/0 AWG, compact/solid conductors of 4/0 AWG, or compact mm2 conductors of 95 mm2.
What is the insulation diameter range for this cable adapter?
The cable adapter is designed for cable insulation diameters ranging from 0.850 inches to 1.050 inches.
What components are included with the K655LR-H0260?
The K655LR-H0260 includes an insulated plug, cap, stud, lug, and cable adapter.
What type of lug is used for conductor connection?
An aluminum compression lug is included for conductor connection.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation of K655/K675LR Deadbreak Elbow Connectors, designed for fully shielded, submersible high-voltage cable connections.
Estimated time: 2h
Tools needed:
Cable cutters, Utility knife, Beveling tool, Cleaning solvent, Rags, Wire brush (for aluminum conductors), Crimping tool (specific to lug), Torque wrench, Hotstick, Voltage sensing device (for capacitive test points)
Supplies needed:
K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if applicable), Silicone Lubricant, Threaded Stud, No. 14 AWG Copper wire (or equivalent ampacity), Grounding connector, HV insulated caps (if replacing shipping covers), Tape marker, Waterproofing material
- De-energize Apparatus and Inspect Components
Before beginning, ensure all apparatus is de-energized. Verify the package contents are complete and undamaged. Inspect all components for proper fit with the cable and/or mating products. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors if the circuit will be submerged or energized later. Failure to de-energize can result in serious or fatal injury.
- Prepare Cable for Connection
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires. Follow specific cable preparation steps (A, B, or C) based on cable type (e.g., remove outer jacket, prepare shield as shown in diagrams).
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Lug
Remove protruding cable insulation flush with the cable adapter, ensuring not to nick the adapter or conductor. Exposed conductor length must be 4-1/4” to 4-9/16” (108mm-116mm). Insert conductor fully into the compression lug (wire brush aluminum conductors first). Before crimping, verify 'Check Dimension' is less than 6-3/8”. Crimp the lug per its instructions. Wipe excess inhibitor. After crimping, the distance from lug end to cable adapter must be 6-3/8” to 7-1/8” (162mm-181mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to Mating Product
Remove protective caps from the elbow and mating part. If needed, hand tighten the supplied threaded stud into the mating part. Clean and lubricate both the elbow and mating part. Push the elbow onto the mating part, aligning the compression lug hole with the stud. Insert the mating part for the opposite end, engage threads, and hand tighten. Torque the mating part per its instructions. DANGER: DO NOT CONNECT/DISCONNECT OR ENERGIZE MATING PRODUCTS WHILE ENERGIZED or DISCONNECTED.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place. Proceed to voltage test directions.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper ampacity) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for any grounding device used, or an alternate method if none is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Do not use conventional voltage meters. Use a suitable sensing device for capacitive test points to check for energization. Contamination or incorrect equipment can cause false readings. Treat the elbow as energized until 'no voltage' is confirmed by other means to prevent injury. After testing, clean, lubricate the cap with silicone, and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.