ABB Installation Products K655L2-L0330-0MA 15/25kV 600 Series Deadbreak 2-Way L-Kit, Cable Insulation Diameter 1.180 inch to 1.465…
UPC: 783786957842
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating
- 600 Series Deadbreak 2-Way L-Kit
- Cable insulation diameter: 1.180" to 1.465"
- Aluminum compression lug included
- Conductor size support: 500 kcmil (stranded), 600 kcmil (solid), 250/300 mm² (compact)
Specifications
Amperage Rating | 600 A |
Application | Used to connect two cable ends and using the two insulating plugs as test points allows for capacitive voltage testing |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 10.87 in |
Length | 276.098 mm |
Material | Housing - EPDM-Rubber |
Special Features | No Seal. Metallic Tape Shield Adapter |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak 2-Way L Kit |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-J0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
161A4-B-5240
15kv, 200 Amp Elbow and Bushing Insert Kit, Loadbreak, Cable Insulation Diameter .635-.905 Inches, Bi-Metal Lug, Conductor Size 1/0-2/0. The use of a Sealing Kit is Recommended.
K655L3-H5270-S
15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
161A4-C5240
15kv, 200 Amps, Elbow-Bushing Insert Kit. Cable Insulation Diameter .805-1.060 inches. Bi-Metal Compression Lug. Conductor Sizse 240 - 1/0 Stranded/Compressed or 2/0 Solid/Compact or 53.49 mmsq.
655CETP-N0380-S
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.515 inch to 1.780 inch. With Shrink-Fit Jacket Seal Kit. Aluminum Compression Lug, 700/750 kcmil Stranded/Compressed or 900 kcmil Solid/Compact.
K656I-H0240
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size Compressed/Stranded 1/0 or Compacted/Solid 2/0.
756LR-L0300-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K151SR-B0220-SG3
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62. 200ECS-G3 Jacket Seal and Grounding Kit Included. Comes with Straight Receptacle Housing, Receptacle Pin Connector, Lubricant, Installation Instructions and Crimp ChartFrequently Asked Questions
How do I order the K655L2 2 Way L-Kit?
To order the 15/25kV, 600A 2 Way L-Kit, specify the ordering number K655L2.
What is the K655L2 kit's primary application?
The K655L2 elbow kit connects two cable ends. Its insulating plugs allow for capacitive voltage testing.
What are the 15kV operating voltage limits?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What is the continuous current rating for 15kV?
The continuous current rating for the 15kV voltage class is 600 Amps.
What is the impulse withstand rating for 15kV?
For the 15kV voltage class, the Basic Impulse Level (BIL) is 95kV.
What are the 28kV operating voltage limits?
For the 28kV class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
What is the continuous current rating for 28kV?
The continuous current rating for the 28kV voltage class is 600 Amps.
What is the impulse withstand rating for 28kV?
For the 28kV voltage class, the Basic Impulse Level (BIL) is 140kV.
What are the key features of the K655L2 kit?
The K655L2 is a 15/25kV, 600 Amp Deadbreak 2 Way L-Kit with a fully shielded, submersible molded rubber housing. It uses 100% peroxide-cured EPDM materials.
How is the K655L2 kit connected or disconnected?
The K655L2 kit can be connected or disconnected using standard hand tools and equipment. This operation must be performed in a de-energized state.
How to Install a 600/900 Series Deadbreak Connecting Plug
This guide provides step-by-step instructions for the safe installation and connection of a 600/900 series deadbreak connecting plug with its mating part. Ensure all apparatus is de-energized before beginning installation.
Estimated time: 45m
Tools needed:
Torque wrench, 3/8” hex bit socket (or 600ATM), Wire strippers
Supplies needed:
600/900 Series Deadbreak Connecting Plug, Lubricant (supplied with plug), No. 14 AWG (2.5mm) copper wire, Stud (if not pre-installed in mating device)
- Prepare the Mating Plug Device (If Applicable)
If the mating plug device (such as an elbow, bushing extender, vault stretcher, or elbow end module) is not equipped with a stud, hand tighten the supplied stud into the mating plug device. Ensure the stud is threaded in until the start of the flats are below the contact surface.
- Clean and Lubricate Components
Thoroughly clean both the connecting plug and its mating part. Apply the supplied lubricant to both surfaces as indicated in the product diagrams. It is critical to use only the provided lubricant; do not substitute, as other lubricants may damage the products. Maintain cleanliness throughout this process.
- Connect and Torque the Connecting Plug
Carefully push the connecting plug into the mating part (elbow, bushing extender, vault stretcher, or elbow end module) until the threads engage. Ensure the contact surface of the connecting plug is firmly held against the contact surface of the mating part. Using a torque wrench with a 3/8” hex bit socket (or 600ATM), tighten the connection to 50 to 60 foot-pounds (68 to 81 newton-meters) of torque.
- Ground the Connecting Plug (If Applicable)
If grounding is required, insert one end of a No. 14 AWG (2.5mm) copper wire or equivalent through the grounding eye on the connecting plug. Twist the wire tightly around the eye, being careful not to damage it. Connect the other end of the wire securely to an appropriate ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.