- 15/25kV voltage rating for medium-voltage applications.
- 200 Amp continuous current capacity.
- Accommodates cable insulation diameters from 0.805" to 1.060".
- Aluminum compression lug for 1/0 AWG stranded or 2/0 AWG solid conductors (53.49 mm²).
- Deadbreak locking splice design for secure and safe connections.
Specifications
Amperage Rating | 200 A |
Application | Used where a new installation is required or to make repairs on existing cable installations |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Permanent Locking Apparatus, Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide Cured Construction includes Insulation and Conductive EPDM Materials |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Locking Splice |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.0000 L |
Package Weight (Metric) | 0.9070 kg |

756ETP-J0240-DRG-S
600 Amp, 35kV, Deadbreak, Window Op With Test Point, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG, Compressed Stranded 1/0 Compacted Solid 2/0. With Insulated Cap and Cold-Shrinkable Jacket Seal.
K676LR-K2330
900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K151LS-B1220
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62. Includes an aluminum compression lug.
K151LY-B1240
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151LY-C1240
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151LY-A1220
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
K151LY-C1230
200 Amp, 15/25kV, DeadBreak elbow, Locking Y Splice, Bails are not required for Locking Splices, Cable Insulation Diameter 0.805 inch to 1.060 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Includes an aluminum compression lug.Frequently Asked Questions
What connector materials are available for K151LS?
Customers can choose between universal aluminum (code 0) or all copper lug (code 2) for the connector material.
What is the continuous current rating for K151LS?
The K151LS has a continuous current rating of 200 Amps for both the 15kV and 25kV voltage classes.
What is the 25kV class maximum operating voltage?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV, and the maximum phase-to-phase is 26.3kV.
What is the 15kV class maximum operating voltage?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
What cable insulation diameters does the K151LS accept?
The K151LS is designed to accept cable insulation diameters ranging from 0.575 inches to 1.220 inches.
What is the K151LS locking splice used for?
The K151LS provides a permanent, fully shielded, and fully submersible splice. It is used for new installations or repairs on existing cable installations up to 25kV.
What is the 25kV class maximum operating voltage?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV, and the maximum phase-to-phase is 26.3kV.
What is the 15kV class maximum operating voltage?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
What is the 25kV class maximum operating voltage?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV, and the maximum phase-to-phase is 26.3kV.
What is the K151LS locking splice used for?
The K151LS provides a permanent, fully shielded, and fully submersible splice. It is used for new installations or repairs on existing cable installations up to 25kV.
How to Install the K151LSP Non-Separable Straight Plug
This guide provides step-by-step instructions for the safe and proper installation of the K151LSP Non-Separable Straight Plug, designed to permanently connect solid dielectric type cables by mating with the K151LSR receptacle on 15kV or 25kV class systems.
Estimated time: 1h
Tools needed:
Cable cutting tool, Wire strippers, Wire brush, Crimp tool, Rag, Measuring device (ruler), Approved solvent
Supplies needed:
Conductor Contact (female), Nylon Venting Rod, Lubricant (supplied with product), Plastic Pin (part of contact, removed during installation), Silicone grease, #14AWG or equivalent copper wire (customer supplied), Sealing material (for grounding connections)
- Ensure Safety and Prepare for Installation
Before beginning, ensure all apparatus are de-energized. This product must only be installed by competent personnel trained in high voltage electrical equipment safety practices. Check the package contents for completeness and damage, and verify all components fit the cable and mating products. Have all required tools ready and maintain cleanliness throughout the procedure.
- Prepare Cable Jacket and Neutral/Shield
For Jacketed Concentric Neutral cable, cut and remove the cable jacket 8 inches from the cable end, allowing sufficient concentric neutral wires for grounding. For Copper Tape Shield cable, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the end of the cable. If using an ECS or MA grounding device, follow its specific instructions for outer jacket cut back.
- Remove Insulation and Conductive Shield
Remove 1-1/8 inches of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid or larger aluminum cable, remove 1-7/8 inches. Cut squarely; do not pencil the cut. Wire brush bare aluminum conductors immediately before inserting them into the crimp barrel.
- Crimp Socket Terminal
Insert the bared conductor fully into the crimp barrel, ensuring it remains seated. Crimp the socket terminal, starting at the crimp line imprinted on the barrel and rotating each successive crimp or indent at least 90 degrees. If using aluminum cable, carefully wipe excess inhibitor from the contact and cable insulation.
- Prepare Semi-Conductive Shield and Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield to a point 7-3/4 to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut, taking care not to cut or nick the insulation. Pencil the insulation 1/8 inch. Replace the plastic pin. Clean the outer jacket and thoroughly clean the insulation with an approved solvent to remove all traces of semi-conducting residue, wiping from the cable end toward the outer jacket. If using an ECS or MA grounding device, install it following its instructions.
- Lubricate Cable and Housing
Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as shown in the product documentation and to the inside of the housing. Do not substitute other lubricants, as they may be harmful to this product or its mating product.
- Install Plug on Cable
Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Once the cable is fully inserted, remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), taking care to ensure the rod is not cut while mating parts. Insert the plug assembly into the receptacle as far as possible until the contact assembly 'clicks' and locks into its final position.
- Verify Connection and Remove Nylon Rod
Verify the locking contact by pulling on the cables; do not pull the housing. If the parts separate, repeat steps 8B and 8C. Once the connection is verified as secure, pull out and remove the nylon rod.
- Connect Grounding
If an ELASTIMOLD grounding device is not being used, connect a length of #14AWG or equivalent copper wire (customer supplied) through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.