
Contact for Pricing
Overview
- 200 Amp, 15/25kV DeadBreak elbow locking splice
- No bails required for locking splice function
- 4 inches of cable replacement length for repair applications
- Accommodates cable insulation diameters 0.635" to 0.905"
- Includes aluminum compression lug for direct termination
Specifications
Amperage Rating | 200 A |
Application | Used where a new installation is required or to make repairs on existing cable installations |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Permanent Locking Apparatus, Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide Cured Construction includes Insulation and Conductive EPDM Materials |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Locking Splice |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.0000 L |
Package Weight (Metric) | 0.9070 kg |

376LR-J-5260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
K151LS-C1240
15/25kV 200 Amp, Deadbreak Locking Splice / Repair Splice, Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K676LR-K2330
900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K151LS-B1220
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62. Includes an aluminum compression lug.
K151LY-B1240
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151LY-C1240
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
K151LY-A1220
15/25kV 200 Amp, Deadbreak Locking Y Splice, Cable Insulation Diameter 0.575 inch to 0.740 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.Frequently Asked Questions
What connector materials are available for the K151LS?
The K151LS is available with universal aluminum (code 0) or all copper lug (code 2) connector materials.
What standard does the K151LS meet?
The K151LS meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating for 25kV class?
For the 25kV voltage class, the impulse withstand (BIL) is 125kV.
What is the impulse withstand rating for 15kV class?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV.
What is the maximum phase-to-ground voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV.
What is the maximum phase-to-ground voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.
What is the continuous current rating for the splice?
The K151LS has a continuous current rating of 200 Amps for both 15kV and 25kV voltage classes.
What pull strength can the K151LS withstand?
The pin and socket interlock of the K151LS can withstand pulls of up to 500 lbs.
What is the maximum voltage rating for the K151LS?
The K151LS is designed for use up to 25kV.
What is the K151LS product type?
The K151LS is a permanent, fully shielded, fully submersible deadbreak locking splice.
How to Install the K151LSP Non-Separable Straight Plug
This guide provides detailed instructions for the safe and proper installation of the K151LSP Non-Separable Straight Plug, designed to connect solid dielectric type cables by mating with the K151LSR receptacle on 15kV or 25kV class systems.
Tools needed:
Wire brush, Crimping tool, Approved solvent, Rag
Supplies needed:
K151LSP Non-Separable Straight Plug, Conductor Contact (female), Nylon Venting Rod, Lubricant (supplied), Crimp Chart, Solid dielectric type cable, K151LSR mating receptacle, Silicone grease, #14AWG copper grounding wire (customer supplied, if needed)
- Prepare for Installation and Ensure Safety
DANGER: De-energize all apparatus before installation or removal. Do not touch or move energized products. Inspect all parts for damage, rating, and compatibility. Ensure installation is performed by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions can result in serious injury or product damage. Check package contents for completeness and ensure proper fit with cable and mating products. Read all instructions before starting and have all required tools ready, maintaining cleanliness throughout.
- Prepare the Cable Jacket
For Jacketed Concentric Neutral cable: Cut and remove the cable jacket 8 inches from the cable end. Ensure sufficient concentric neutral wires are available for connection to the ground point. For Copper Tape Shield cable: Cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the end of the cable. If using an ECS or MA grounding device, follow its specific jacket cut-back instructions.
- Prepare Cable Insulation and Conductive Shield
Remove 1-1/8 inches of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid or larger aluminum cable, remove 1-7/8 inches. Cut squarely; do not pencil. Immediately wire brush bare aluminum conductors before inserting into the crimp barrel.
- Crimp the Socket Terminal
Insert the bared conductor fully into the crimp barrel. Crimp the socket terminal, starting at the crimp line imprinted on the barrel and rotating each successive crimp or indent at least 90 degrees. If using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare the Semi-Conductive Shield and Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield to a point 7-3/4 inches to 7-13/16 inches back from the end of the socket using a straight, smooth, 'squared' cut. DO NOT CUT OR NICK THE INSULATION. Pencil the insulation 1/8 inch. Replace the plastic pin. Thoroughly clean the outer jacket and insulation with an approved solvent, wiping from the end of the cable toward the outer jacket to remove all traces of semi-conducting residue. If using an ECS or MA grounding device, install it now following its instructions.
- Lubricate and Install Plug onto Cable
Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as shown in the diagram and to the inside of the housing. DO NOT SUBSTITUTE other lubricants, as they may harm the product. Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Remove and discard the plastic pin from the socket.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), taking care not to cut the rod. Insert the plug assembly into the receptacle as far as possible until you feel the contact assembly 'CLICK' and lock into its final position.
- Verify Connection and Finalize Grounding
Verify the locking contact by pulling on the cables (DO NOT PULL THE HOUSING). If the parts separate, repeat steps 7B and 7C. Pull out the nylon rod. If an ELASTIMOLD grounding device is not being used, connect a customer-supplied length of #14AWG or equivalent copper wire through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.
