ABB Installation Products 776LR-J5270-S 900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and…
UPC: 075114126236
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 900 amp current rating for 35 kV class systems
- Deadbreak design allows connection/disconnection under load
- Integrated test point for safe voltage verification without de-energization
- Cold-shrinkable jacket seal for moisture-resistant installation on 0.980-1.180 in cable insulation
- Bi-metal compression lug compatible with 4/0 AWG, 250 kcmil, or 125 mm² compact conductors
Specifications
Amperage Rating | 900 A |
Application | 35 kV, 900 Amps |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold Shrinkable Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 10.4000 L |
Package Weight (Metric) | 4.7170 kg |

375LR-L-2270
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
274RLR-G-230
25kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
K465LR-G-0250
15/25kV, 630 Amps, Deadbreak Elbow without Test Point. Cable Insulation Diameter 0.760-0.950 inches (19.304-24.130mm). Aluminum Compression Lug, Conductor Size 2/0 Stranded/Compressed or 3/0 Solid/Compact or 70 mm2. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Tube Lubricant, Cable Adapter, Installation Instructions and Crimp Chart. Exceeds ANSI/IEEE Standard 386 Latest Revision.
168RLR-H-270
15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
756LR-M2380-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K465LR-G-0230
15/25kV, 630 Amps, Deadbreak Elbow without Test Point. Cable Insulation Diameter 0.760-0.950 inches (19.304-24.130mm). Aluminum Compression Lug, Conductor Size #1 Stranded/Compressed or 1/0 Solid/Compact or 50 mm2. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Tube Lubricant, Cable Adapter, Installation Instructions and Crimp Chart. Exceeds ANSI/IEEE Standard 386 Latest Revision.
776LR-M5330-S
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.370 inch to 1.630 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
756LR-M2340-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 550. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.Frequently Asked Questions
What standards does the 776LR meet?
The 776LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the DC 15-minute withstand voltage?
The DC 15-minute withstand voltage is 103kV.
Is the 776LR elbow submersible?
Yes, the 776LR features a fully shielded, fully submersible molded rubber housing.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What is the continuous current rating?
The continuous current rating for the elbow connector is 900 Amps.
What is the corona extinction voltage?
The corona extinction voltage is 26kV AC at 3pC sensitivity.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the impulse withstand rating?
The impulse withstand rating is 150kV BIL (1.2 x 50 microsecond wave).
What is the maximum phase-to-phase voltage?
The maximum phase-to-phase voltage for the 35kV class is 36.6kV.
What is the maximum operating voltage?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
How to Install Elastimold 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 755LR (600-ampere) or 775LR (900-ampere) deadbreak elbow connectors on 35kV class systems. It covers cable preparation, connector assembly, and final connection procedures.
Estimated time: 2h
Tools needed:
Cable cutter, Cable stripping tools, Measuring tape, Beveling tool, Utility knife, Wire brush (for aluminum conductors), Crimping tool, Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
755/775LR Elbow connector, Cable adapter, Compression lug, Insulating plug (if applicable), Lubricant (silicone), Threaded stud (from prepack), Grounding wire (No. 14 AWG Copper or equivalent), Suitable ground connector, Waterproofing material, Cleaning solution/wipes
- De-energize Apparatus and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all package contents for completeness and damage. Verify all components are rated and compatible with the cable and mating products. Read all instructions before proceeding.
- Prepare the Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm). Prepare the cable by removing the outer jacket and semi-con shield to the dimensions specified in the documentation for your cable type (e.g., 10-3/8, 11-3/8, 13-5/8 inch tape markers).
- Install Cable Adapter and Trim Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure the exposed conductor length is between 4-3/8 inches to 4-3/4 inches (111mm-121mm).
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the lug. Measure the 'Check Dimension' before crimping (should be less than 7 inches / 178mm). Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface. Verify the distance from the end of the lug to the cable adapter is between 6-7/8 inches to 7-5/8 inches (175mm-194mm) after crimping.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect to Mating Apparatus
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped with one. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End (if applicable)
If connecting to another mating part on the opposite end of the elbow, clean and lubricate its surface. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper (or equivalent ampacity) wire through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded according to the instructions supplied with any grounding device, or by an alternate method if no device is used. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
CAUTION: When constructing 600-amp L-Kits, tighten each component to specified torque. The elbow connector has an integral capacitance test point. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.