ABB Installation Products 756LR-P0400 600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786424764
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 35kV DeadBreak Elbow with Test Point
- Cable insulation diameter compatibility: 1.725" to 1.935"
- Aluminum compression lug for 900 kcmil/1000 kcmil/500 mm² conductors
- Integrated test point for diagnostic measurements without disconnection
- Compliant with ANSI C119.4 and IEEE 386 standards
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 900 kcmil , 1000 kcmil |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.9000 L |
Package Weight (Metric) | 4.0370 kg |

755LR-P0400-SG3
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. 200ECS-G3 Jacket Seal and Grounding Kit Included.
776LR-K2250
900 Amp, 35KV, DeadBreak, Elbow with Test Point, with insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
756LR-Q0410-S
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.
756LR-N0330-S
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
756LR-M0290-SG3
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-J0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. Cold-Shrinkable Jacket Seal Included.
775LR-N2440
900 Amp, 35KV, DeadBreak, Direct Test Elbow with insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
756LR-N0380
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.Frequently Asked Questions
What is the AC one-minute withstand rating?
The AC one-minute withstand rating for the 756LR is 50kV AC.
What is the impulse withstand rating of the 756LR?
The 756LR has a 150kV BIL Impulse Withstand rating (1.2 x 50 microsecond wave).
What is included in a 756LR kit?
Each kit contains an elbow connector housing, a copper compression lug, a stud, an insulated plug with cap, lubricant tubes, a cable adapter, and installation instructions.
What materials are used in the 756LR's construction?
The 756LR features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
Is the 756LR elbow suitable for submersible applications?
Yes, the 756LR features a fully shielded, fully submersible molded rubber housing.
What standard does the 756LR elbow meet?
The 756LR elbow meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating of the 756LR?
The 756LR has a continuous current rating of 600 Amps.
What cable insulation diameters does the 756LR support?
The 756LR supports cable insulation diameters from .760 inches to 2.120 inches.
What conductor sizes are compatible with the 756LR?
The 756LR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
What is the maximum operating voltage for this elbow?
The maximum phase-to-ground operating voltage for the 35kV voltage class is 21.1kV. The maximum phase-to-phase voltage is 36.6kV.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 756/776LR Deadbreak Elbow Connectors, designed for fully shielded, submersible deadfront cable connections on 35kV class systems.
Estimated time: 2h
Tools needed:
Crimping tool, Wire brush, Hotstick, Voltage sensing device, Wire strippers, Utility knife, Torque wrench, Cleaning supplies
Supplies needed:
756/776LR Deadbreak Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Crimp connector, Lubricant, Stud Prepack), HV insulated cap(s) or connector(s), No. 14 AWG Copper wire (or equivalent), Grounding connector, Silicone lubricant, Tape marker
- De-energize Apparatus and Inspect Components
DANGER: Ensure all apparatus is de-energized before beginning installation. Do not touch or move energized products. Inspect all package contents for completeness and damage, and verify component compatibility with the cable and mating products. Read all instructions thoroughly before proceeding.
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable End
Prepare the cable end by removing the outer jacket, semi-con shield, and cable insulation to the specified dimensions for your cable type. Refer to the provided diagrams for precise measurements (e.g., 10-3/8in, 11-3/8in, 13-5/8in from the cut end to tape markers) and techniques.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Conductor Insulation
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Measure the 'Check Dimension' (must be less than 7 inches/178mm) before crimping. Crimp the compression lug following its supplied instructions. Wipe off all excess inhibitor. The distance from the end of the lug to the cable adapter after crimping should be 6-7/8 inches to 7-5/8 inches (175mm-194mm). Redo if dimensions are incorrect.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
WARNING: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (if supplied with the elbow) into the mating part if it's not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to First Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Second Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug and Voltage Detection Cap
If an insulating plug is used, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place. This plug provides a means for detecting system voltage.
- Ground Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent ampacity) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded, either via a grounding device or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Replace Cap
CAUTION: For 600amp L-Kits, ensure all components are tightened to specified torque. If using the integral capacitance test point, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: Use a suitable sensing device designed for capacitive test points; do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.