ABB Installation Products 756LR-L0270 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786353330
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Fully shielded, dead-front submersible design for 35kV applications
- 600 Amp continuous current rating with 25kA momentary withstand
- Test point for safe electrical testing without cable disconnection
- Includes insulated plug, cap, stud, aluminum compression lug, and cable adapter
- Supports cable insulation diameters from 1.180" to 1.465" and conductor sizes from 4/0 AWG to 250 kcmil
- Accommodates cable insulation diameters from 1.180" to 1.465"
- Supports 4/0 AWG compressed stranded, 250 kcmil compacted solid, and 125 mm² compact conductors
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Connection Type | Deadbreak Elbow |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | 1.180 inch to 1.465 inch (Cable Insulation Diameter) |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.3100 L |
Package Weight (Metric) | 3.7690 kg |

756LR-K0270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-L2300-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-K0270
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
756LR-L2320
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
756LR-L2260
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
756LR-L0300-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
756LR-L2240-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-J0240
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.Frequently Asked Questions
What is the 756LR's primary use?
It provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What standards does the 756LR meet?
The 756LR meets ANSI/IEEE Standard 386, Latest Revision.
How is the 756LR connected or disconnected?
It can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
What materials are used in 756LR construction?
It features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
What is the DC 15-minute withstand voltage?
The DC 15-minute withstand voltage is 103kV.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the impulse withstand rating?
The impulse withstand (BIL) rating is 150kV.
Is the 756LR submersible?
Yes, it features a fully shielded, fully submersible molded rubber housing.
What insulation diameters does the 756LR support?
It supports insulation diameters from 0.760 in to 2.120 in.
What conductor sizes are compatible with 756LR?
It is compatible with #2 AWG to 1250 kcmil for aluminum and copper conductors.
How to Install 756LR/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 756LR and 776LR Deadbreak Elbow Connectors on 35kV class systems. Ensure all apparatus are de-energized and only competent personnel perform the installation.
Estimated time: 2h
Tools needed:
Wire strippers, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
756LR/776LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if applicable), Crimp connector, Lubricant (silicone type), Stud Prepack, Wire (No. 14 AWG Copper or equivalent for grounding), Suitable ground connector
- Prepare the Cable for Installation
Position the cable in its final assembled location with enough slack to allow for elbow removal. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24” (610mm). Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield according to the specific cable type and dimensions provided in the documentation (e.g., 10-3/8” to 13-5/8” for various shield types).
- Install Cable Adapter and Crimp Compression Lug
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter; do not cut or nick the cable adapter or conductor. Ensure the exposed conductor length is between 4-3/8” to 4-3/4” (111mm-121mm). For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” before crimping (should be less than 7” or 178mm). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-7/8” to 7-5/8” (175mm-194mm).
- Install Elbow and Connect to Mating Apparatus
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; reposition if necessary. Remove the tape marker. WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped with one. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Complete Connections and Ground the Cable Shield
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down hard until it snaps into place. Insert one end of a piece of wire (ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop; do not damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; follow instructions supplied with the grounding device or use an alternate method. It is recommended to waterproof the cable jacket at this point to prevent moisture entry.
- Perform Voltage Test (Safety Procedure)
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per instructions provided with plug connectors. To perform a voltage test, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line. WARNING: The voltage test point is a capacitance device and is NOT directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or using the wrong equipment can provide a false “no voltage” indication. To prevent serious or fatal injury, treat the elbow as energized until the “no voltage” test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.