ABB Installation Products 755LR-M0320 600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 075114311212
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 35kV rating for medium-voltage applications
- Accommodates cable insulation diameters from 1.370" to 1.630"
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for 450/500 AWG stranded and 550 AWG solid conductors
- ABB 600 Series Deadbreak Elbow for reliable cable termination
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Blue |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

755LR-N0320
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
162LR-A-2220
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575 inch to 0.740 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.
755LR-M0330
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
755LR-M0300
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
161LRJS-D2240
200 Amp, 15kV, Loadbreak Elbow with Jacket Seal, Cable Insulation Diameter 0.890 inch to 1.220 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
161LRJS-D-5270
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector, .890 inch - 1.220 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-A-5200
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .575 inch - .740 Inch Cable Insulation Diameter, #4 Stranded Wire Size, Bi-Metal Compression LugFrequently Asked Questions
What is the 755LR elbow connector used for?
It provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the impulse withstand rating (BIL) for the 755LR?
The impulse withstand (BIL) rating is 150kV.
How is the 755LR connected or disconnected?
It can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
What materials are used in the 755LR construction?
It features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
Is the 755LR elbow submersible?
Yes, it features a fully shielded, fully submersible molded rubber housing.
What is the DC 15-minute withstand voltage?
The DC 15-minute withstand voltage is 103kV.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the continuous current rating of the 755LR?
The continuous current rating for the 755LR is 600 Amps.
What is the maximum operating voltage for the 755LR?
The maximum phase-to-ground operating voltage is 21.1kV.
What cable insulation diameters does the 755LR support?
It supports insulation diameters from .760 inches to 2.120 inches.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755LR and 775LR Deadbreak Elbow Connectors, designed for high voltage apparatus connections and splicing on 35kV class systems.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Crimping tool, Wire brush, Measuring tape, Hotstick, Capacitive voltage sensing device, Torque wrench, Cleaning cloths
Supplies needed:
755/775LR Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), High voltage cable, Tape marker, Grounding wire (No. 14 AWG Copper or equivalent), Suitable grounding connector, Cable jacket waterproofing material, HV insulated cap(s) or connector(s), Silicone lubricant, Mating apparatus bushing or connector
- Position Cable and Prepare for Cutting
DANGER: Ensure all apparatus is de-energized before beginning installation. Position the cable in its final assembled location with enough slack to allow for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable for Connection
Remove the outer jacket (if applicable) and prepare the cable according to its specific type (e.g., concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield). Refer to the detailed diagrams and instructions in the product documentation for precise measurements and procedures, especially if using a 20MA or 21MA grounding device, 600ECS Jacket Cable Seal, or 10TL cable shield adapter.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the exposed conductor length is between 4-3/8 inches to 4-3/4 inches (111mm-121mm); if not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping (should be less than 7 inches/178mm). Crimp the compression lug following the supplied instructions. Wipe off any excess inhibitor. Verify the distance from the end of the compression lug to the cable adapter is between 6-7/8 inches to 7-5/8 inches (175mm-194mm) after crimping; if not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter is still flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down firmly until the cap snaps into place.
- Ground the Cable Shield
Insert one end of a grounding wire (at least No. 14 AWG Copper) through the grounding eye and twist to form a small loop, being careful not to damage the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded according to the instructions supplied with any grounding device, or via an alternate method if no device is used. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Use the integral capacitance test point to determine if the circuit is energized. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points; do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.