ABB Installation Products 655LRTP-K0330 600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 1.090 inch to…
UPC: 783786646081
Contact for Pricing
Call (262) 252-1600 or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating
- 15kV voltage class
- Deadbreak stick-operated design for safe operation
- Aluminum compression lug
- Accommodates cable insulation diameters from 1.090" to 1.310"
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.0000 L |
Package Weight (Metric) | 3.6290 kg |

K675LR-M2330
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
655LRTP-N0410-DRG
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
655LRTPL0330DRG
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
656LRTP-J2280-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit, Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300.
656LRTP-J2280
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300.
655LRTP-M2380-DRG
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
656LRTP-J0290-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit, Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.Frequently Asked Questions
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 Cycles.
What is the impulse withstand rating?
The impulse withstand rating (BIL) is 95.0kV (1.2 x 50 microsecond wave).
What is the voltage rating of this connector kit?
The connector kit has a 15kV voltage class, with an 8.3 kV maximum phase-to-ground operating voltage and 15.0 kV maximum phase-to-phase.
What is included in the 655LRTP-W0X kit?
The kit includes a 600 Series Elbow Housing, a STICK-OP LB Reducing Tap Plug, a Cable Size Adapter, a Compression Lug, Silicone Lubricant, an Instruction Sheet, and a Crimp Chart.
What standards does this connector meet?
The connector kit meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating?
The continuous current rating for the connector kit is 600 Amp. It also provides a 200 Amp load break tap.
What is the impulse withstand rating?
The impulse withstand rating (BIL) is 95.0kV (1.2 x 50 microsecond wave).
What is included in the 655LRTP-W0X kit?
The kit includes a 600 Series Elbow Housing, a STICK-OP LB Reducing Tap Plug, a Cable Size Adapter, a Compression Lug, Silicone Lubricant, an Instruction Sheet, and a Crimp Chart.
What standards does this connector meet?
The connector kit meets ANSI/IEEE Standard 386, Latest Revision.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 Cycles.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems, ensuring fully shielded and submersible cable connections.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Capacitive sensing device, Torque wrench
Supplies needed:
655/675LR or K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (optional), Silicone lubricant, Threaded Stud, No. 14 AWG Copper wire (or equivalent), Suitable ground connector, Grounding device (optional), HV insulated cap(s) or connector(s), Tape marker
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety. Inspect all package contents and components for completeness, damage, correct rating, and compatibility with mating parts.
- Position and Cut Cable
Assemble the cable in its final position, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean and Prepare Cable
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the specified lengths and dimensions according to the cable type diagrams provided in the full instructions.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the lug. Measure the 'Check Dimension' before crimping (it must be less than 6-3/8 inches). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface. After crimping, the distance from the end of the lug to the cable adapter must be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition it if necessary. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand-tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part surfaces with the supplied lubricant.
- Connect Elbow to First Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Second Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand-tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place. Proceed to the voltage test directions.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent ampacity) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for any grounding device used, or use an alternate grounding method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points, following its manufacturer's directions, to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can provide a false reading. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.