Authorized ABB Distributor (Installation Products)
ABB - Installation Products 655LINKCLRN0410ADRG - 600 Amp, 15kV, Deadbreak RetroFit Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

ABB Installation Products 655LINKCLRN0410ADRG 600 Amp, 15kV, Deadbreak RetroFit Cam-Op Connector Kit with Insulated Cap, Cable…

UPC: 783786291809


Documents & Media
Installation InstructionsManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

This ABB 655LINKCLRN0410ADRG is a 600 Amp, 15kV Deadbreak RetroFit Cam-Op Connector Kit designed for reliable power connections. It features an insulated cap and is engineered to accommodate cable insulation diameters ranging from 1.515 inches to 1.780 inches. The kit includes an aluminum compression lug, suitable for compressed stranded conductors up to 1000 kcmil. This connector is part of ABB's Installation Products line, known for its robust electrical infrastructure solutions. The Cam-Op mechanism provides a secure and efficient connection, crucial for maintaining system integrity in medium-voltage applications. Its design facilitates retrofitting into existing systems, offering a practical upgrade path. The specific UNSPSC code for this product is 39121421. Ensure proper installation by qualified personnel to achieve optimal performance and safety. The SKU for this item is 655LINKCLRN0410ADRG.
  • 600 Amp current rating
  • 15kV voltage rating
  • Deadbreak RetroFit Cam-Op Connector Kit
  • Accommodates cable insulation diameter: 1.515" - 1.780"
  • Aluminum compression lug for 1000 kcmil stranded conductor

Specifications

Amperage Rating
600 A
Application
External Visible Break, Testing, Grounding and Isolation
Color
Black
Conductor Range
1000 kcmil
Connection
Compression
Connection Type
Compression Lug
Current Rating
600 A
Insulation
True
Material
Aluminum
Material
EPDM-Rubber
Mounting Type
Cam-Op
Series
600 Series
Size
20.50 inches from edge of Lever to Bushing Flange
Size
1.515 inch to 1.780 inch
Special Features
Easily Installed or Removed by Hotstick Operation of the Cam Action Disconnect Lever
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Retro Cam_OP Connector Kit
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
27.5000 L
Package Weight (Metric)
12.4740 kg
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. 200ECS-G3 Jacket Seal and Grounding Kit Included.

656CETP-M0410

15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. 200ECS-G3 Jacket Seal and Grounding Kit Included.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
15/25kV, 600 Amp, no test point, Combo T Connecting Plug with Stud, Cable Adapter and Lug Kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

K655CCP-M0380

15/25kV, 600 Amp, no test point, Combo T Connecting Plug with Stud, Cable Adapter and Lug Kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
15/25kV 600 Series Deadbreak 4-Way L-Kit, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.

K655L4-H0270-S

15/25kV 600 Series Deadbreak 4-Way L-Kit, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.

K655L3-LM0360

15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
600 Amp, 15kV, Deadbreak RetroFit Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

655LINKCLRM0410ADRG

600 Amp, 15kV, Deadbreak RetroFit Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.665 inch to 0.895 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. 200ECS Jacket Seal Included.

274ELR-6689-230-S

200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.665 inch to 0.895 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. 200ECS Jacket Seal Included.
200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.740 inch to 0.950 inch.

168ELR-7495-260

200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.740 inch to 0.950 inch.

How to Install the LINK-C Deadbreak Cam Link Operable Connector System

This guide provides step-by-step instructions for the safe installation and initial setup of the LINK-C 600 amp deadbreak cam link operable connector system, including mounting, wiring, and grounding procedures.

Estimated time: 2h

Tools needed:

Torque wrench, Socket wrench (1 inch hex), Hot stick, Wire strippers, Welding equipment (if using welded studs), Multimeter

Supplies needed:

ELASTIMOLD lubricant, Hex nuts, Lockwashers, Mounting studs (3/8-16 x 2 inches), Spacers (optional), Hardware for clamps (supplied with bracket), #14 AWG or #12 AWG solid copper wire, Appropriate grounding connectors, Mating 200 amp product (if applicable)

  1. Prepare for Installation and Install 600 Amp Elbow

    DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Inspect all components for damage, proper rating, and compatibility with mating parts. Read all instructions before starting. Install the 600 amp elbow onto the cable according to its specific installation instructions, ensuring it will align with the stand-off plug.

  2. Install Mounted Stand-Off Plug (if applicable)

    If using a mounted stand-off plug, weld three 3/8-16 x 2 inch studs to the faceplate per customer standard practice. Install three hex nuts onto the studs to support the stand-off plug, or use spacers. Position the stand-off plug over the studs, resting on the nuts or spacers. Install a lockwasher and hex nut on each stud and tighten to 12 foot-lbs torque. Verify that the top surfaces of the apparatus bushing and stand-off plug are in-line; readjust nuts if necessary.

  3. Install Bushing Extender and Elbow onto Standoff Plug

    Clean and thoroughly lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender with ELASTIMOLD lubricant. Install the bushing extender onto the apparatus bushing. Insert the 600ATM into the retainer contact, engage the internal hex broach, and thread into the apparatus bushing using a suitable tool on the 1 inch hex portion of the 600ATM, torquing to 50-60 ft-lbs. Clean and lubricate the epoxy standoff plug and both interfaces of the 600 amp elbow. Install the elbow onto the epoxy standoff plug, inserting the 600AMT into the retainer contact and threading into the standoff plug, torquing to 50-60 ft-lbs.

  4. Install the Alignment Bracket

    Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until clamp tabs are flush and tight.

  5. Position and Secure the Elbow in the Alignment Bracket

    Position the elbow in the alignment bracket so that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until clamp tabs are flush and tight. Ensure the elbow clamp notch faces the cable entrance of the elbow.

  6. Install the Link Connector

    Clean and thoroughly lubricate both 600 ampere interfaces of the Link with ELASTIMOLD lubricant. Align the Link so it is perpendicular to the switch faceplate when inserted. Insert the Link into the bushing extender and elbow, ensuring both lever arms are inside the alignment bracket legs. Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, use a hot stick on the hot stick eye to move the lever arms downward, engaging the roller pin and moving the Link inward. Continue until the lever arms are perpendicular to the alignment bracket leg.

  7. Ground the System

    Ground the elbow by feeding a #14 AWG or #12 AWG solid copper wire through the grounding eye, twisting it tight, and connecting it to ground. Clean and lubricate the 200 amp interface on the Link. Ground and install the desired mating product on the 200 amp interface per its installation instructions. Ground the cable: if concentric neutral, twist wires and connect to ground using an appropriate connector; if using 20MA or 21MA devices, connect the ground lead to ground using a suitable connector. For three-phase installations, tie all grounds from all three phases to a common ground point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.