Authorized ABB Distributor (Installation Products)
ABB - Installation Products 655ETP-J0280-DRG - 15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300.

ABB Installation Products 655ETP-J0280-DRG 15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test…

UPC: 783786062355


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 655ETP-J0280-DRG 15kV 600 Series Deadbreak Elbow TAP PLUG Connector Kit delivers reliable, high-performance electrical connections for medium-voltage systems. This kit is engineered for 15kV class applications with a 600 Ampere continuous current rating, meeting ANSI/IEEE Standard 386 requirements. The deadbreak design allows safe connection and disconnection under load without de-energizing the system, reducing downtime and improving operational safety. Key components include an insulated cap, test and ground reducing tap plug, 600 series elbow housing, cable adapter, and a 0370 style aluminum compression lug. The lug accommodates compressed stranded conductors from 250 kcmil up to 300 compacted solid conductors, ensuring secure termination for medium-voltage cables. The kit supports cable insulation diameters ranging from 0.980 inches to 1.180 inches, providing compatibility with a wide range of cable types. Designed for medium-voltage distribution systems, this elbow tap plug is ideal for applications requiring safe, reliable branching from a main feeder. The deadbreak interface enables energized operation, making it suitable for maintenance and testing scenarios where system continuity is critical. The 600 series housing ensures compatibility with standard 600 Ampere connectors, while the included test and ground components simplify installation and enhance operational safety. The ABB 655ETP-J0280-DRG is a critical component for utilities, industrial facilities, and commercial installations requiring medium-voltage connectivity.
  • 15kV voltage rating with 600 Ampere continuous current capacity
  • Deadbreak design allows safe connection/disconnection under load
  • Includes test and ground reducing tap plug, insulated cap, and 0370 aluminum compression lug
  • Supports cable insulation diameters from 0.980" to 1.180"
  • Compatible with compressed stranded 250 kcmil to 300 compacted solid conductors

Specifications

Amperage Rating
600 A
Application
600 Amps, 15kV
Color
Black
Conductor Range
250 STR/COMPR kmcil , 300 SOL/COMPT kcmil
Connection
Compression
Connection Type
Deadbreak Elbow TAP PLUG
Current Rating
600 A
Insulation
EPDM Rubber
Material
Housing - EPDM-Rubber
Material
Aluminum
Series
600 Series
Series
600
Size
Cable Insulation Diameter 0.980 inch to 1.180 inch
Size
Cable Insulation Diameter 0.980-1.180 inches
Size
0.980" - 1.180"
Special Features
Includes Insulated Cap
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Window-Op Connector
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
25kV, 600 Amp Deadbreak, Test and Ground Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300. With Insulated Cap. Cold-Shrinkable Jacket Seal Included.

K655ETP-J0280-DRG-S

25kV, 600 Amp Deadbreak, Test and Ground Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300. With Insulated Cap. Cold-Shrinkable Jacket Seal Included.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.

756ETP-P0380-S

600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.
600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.

756ETP-N0330-S

600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.

756ETP-M0270-S

600 Amp, 35kV, Deadbreak, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.

656ETP-J0270-DRG

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. With Insulated Cap.

655ETP-F0230-DRG

15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. With Insulated Cap.
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

655ETP-K0330-DRG

15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

Frequently Asked Questions

What is the continuous current rating?

The continuous current rating for this connector is 600 Amp.

What is the maximum phase-to-phase voltage rating?

The maximum phase-to-phase voltage rating for this connector is 14.4kV.

What is the maximum operating voltage for this connector?

The maximum phase-to-ground operating voltage for the 15kV class connector is 8.3kV.

What ANSI/IEEE standard does this product meet?

This product meets ANSI/IEEE Standard 386, Latest Revision.

What is the momentary current rating?

The momentary current rating is 25kA Symmetrical for 10 Cycles.

What is the product name of this connector kit?

The product is the 15 kV WINDOW-OP Connector Kit w/o Test Point 600A, model 655ETP-W0X-DRG.

What is the BIL impulse withstand rating?

The BIL impulse withstand rating is 95kV, based on a 1.2 x 50 microsecond wave.

What is the product name of this connector kit?

The product is the 15 kV WINDOW-OP Connector Kit w/o Test Point 600A, model 655ETP-W0X-DRG.

What is the BIL impulse withstand rating?

The BIL impulse withstand rating is 95kV, based on a 1.2 x 50 microsecond wave.

What is the momentary current rating?

The momentary current rating is 25kA Symmetrical for 10 Cycles.

How to Install and Remove the 160DRG/167DRG Insulated Cap with Ground Lead

This guide provides instructions for the safe installation and removal of the ELASTIMOLD 15kV class 160DRG and 167DRG insulated caps, designed for insulating, shielding, and watersealing loadbreak bushing interfaces.

Estimated time: 15m

Tools needed:

Hotstick, Live-line tool

Supplies needed:

160DRG or 167DRG Insulated Cap with Ground Lead, Lubricant (supplied or ELASTIMOLD approved)

  1. Connect the Electrostatic Grounding Wire

    Before proceeding, ensure all apparatus is de-energized. Connect the free end of the electrostatic grounding wire to the system ground. Leave enough slack for hot-stick operation of the insulated cap. CAUTION: Train the grounding wire so it does not contact the bushing interface during operation. WARNING: If the ground lead disconnects during operation, do not attempt to reattach without first pulling the insulated cap off the bushing with the hotstick.

  2. Prepare the Insulated Cap

    Remove the protective cover from the insulated cap. Lubricate the cap's internal mating surface using only the supplied lubricant or ELASTIMOLD approved lubricants. DO NOT SUBSTITUTE, as other lubricants may be harmful. Keep the internal mating surface free from dirt and grime. Always replace the protective cover when the cap is not in use.

  3. Attach and Mate the Insulated Cap

    Firmly attach a hotstick to the insulated cap's pulling eye. Insert the male contact of the insulated cap into the loadbreak bushing. Push the cap home with a fast, firm, straight motion, ensuring it is fully mated and the locking ring is seated. Detach the hotstick from the insulated cap.

  4. Remove the Insulated Cap

    To remove the cap, attach a hotstick to the pulling eye. Before pulling, rotate the insulated cap slightly clockwise while it is in the mated position to break surface friction. Pull the receptacle off with a fast, firm, straight motion. Remove the electrostatic grounding wire of the insulated cap from the system ground. Replace the protective cover on the insulated cap to keep its internal surface clean.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.