ABB Installation Products 655CETPNG0230S 600 Amp, 15kV, Combo T Elbow Reducing Tap Plug without Stud, with Cable Adapter, Lug, No…
UPC: 783786084050
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 15kV rating for medium-voltage systems
- Reducing tap configuration for versatile conductor sizes
- Accommodates cable insulation diameters from 0.760" to 0.950"
- Suitable for 500-600 kcmil stranded/solid and 250-300 mm² compact conductors
- Aluminum construction with Shrink-Fit Jacket Seal Kit
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 15kV Connector |
Color | Black |
Color | Red |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection Type | Elbow Tap Plug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Size | 0.760 inch to 0.950 inch (Cable Insulation Diameter) |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, and Lug |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow |
Voltage Rating | 15 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

655ETP-G0230-S
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. 200ECS Cold-Shrinkable Jacket Seal Included.
655CETPNM0380S
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug without Stud, with Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. With Shrink-Fit Jacket Seal Kit.
655CETPNN0410S
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug without Stud, with Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Shrink-Fit Jacket Seal Kit.
655CETPN0410
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000.
655CETPM0380
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.370 inch to 1.630 inch.
655CETPN0410DRGS
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, No Test Point, Aluminum, Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Shrink-Fit Jacket Seal Kit.Frequently Asked Questions
Is it safe to install ComboT connectors on an energized system?
No, the system needs to be de-energized before initiating any installation of ComboT connectors.
What is the required torque for the 600ATM or BIP?
The 600ATM and BIP components should be torqued to 50 to 60 ft.-lbs during installation.
What is the loadmake/loadbreak switching current capacity?
The loadmake/loadbreak switching current capacity for ComboT connectors is 200 A.
What continuous current can ComboT connectors handle?
ComboT connectors can handle continuous currents of 600 A or 900 A for deadbreak interfaces, and 200 A for loadbreak interfaces.
What are the voltage ratings for CCP and CBW connectors?
CCP and CBW connectors have a voltage class of 15/25/28 kV, with a maximum phase-to-ground operating voltage of 16.2 kV.
What are the voltage ratings for CETP connectors?
CETP connectors are available in 15 kV and 25 kV classes, with max phase-to-ground operating voltages of 8.3 kV and 15.2 kV respectively.
What is the stack height reduction with ComboT connectors?
Each combination elbow/connecting plug reduces the stack height by 2.67 inches. This allows for installation in smaller cabinets and tighter spaces.
What is the loadmake/loadbreak switching current capacity?
The loadmake/loadbreak switching current capacity for ComboT connectors is 200 A.
What is the stack height reduction with ComboT connectors?
Each combination elbow/connecting plug reduces the stack height by 2.67 inches. This allows for installation in smaller cabinets and tighter spaces.
What are the voltage ratings for CETP connectors?
CETP connectors are available in 15 kV and 25 kV classes, with max phase-to-ground operating voltages of 8.3 kV and 15.2 kV respectively.
How to Install 655/656/675/676CETP Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 600/900 Series Deadbreak Elbow Connectors, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 2h
Tools needed:
Cable cutting tools, Wire strippers, Crimping tool (for compression lug), Wire brush (for aluminum conductor), 600AT or 600ATM assembly tool, Torque wrench (calibrated for 19-25 ft-lbs or 50-60 ft-lbs), Hotstick (for test point cap removal), Suitable sensing device (for capacitive test points), Measuring tape or ruler
Supplies needed:
655/656/675/676CETP Elbow Connector kit (includes elbow, cable adapter, compression lug), Lubricant (supplied with kit), Vinyl plastic tape, Tape retainer (if applicable for cable type), Tape marker (if applicable for cable type), No. 14 AWG Copper wire (or equivalent for grounding), Suitable ground connector, HV insulated cap(s) or connector(s) (to replace shipping covers), Silicone grease (for test point cap), Optional: 20MA or 21MA grounding device, 600ECS Jacket Cable Seal, 10TL cable shield adapter, DR(G)/ESA/GLR/LR loadbreak accessories
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Ensure all apparatus is installed and operated in accordance with individual user, local, and national work rules. Inspect all parts for damage, proper rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Gather all required tools and supplies, and maintain cleanliness throughout the procedure.
- Prepare the Cable for Installation
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires. Refer to instructions for any specific grounding devices (e.g., 20MA, 21MA, 600ECS) for jacket and shield removal, otherwise proceed with the following cable preparation steps specific to your cable type (outer jacket, shield wires, flat metallic tape shield, fabric tape shield, longitudinally corrugated shield, semi-con shield). If using UNISHIELD® or lead sheath cable, a 10TL cable shield adapter is required; refer to its specific instructions.
- Prepare Cable Insulation and Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation (using the supplied lubricant), always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length must be 4-3/8 to 4-11/16 inches (111mm-119mm); if not, redo the assembly.
- Install and Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-1/2 inches (165mm). Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be 6-1/2 to 7-1/4 inches (165mm-184mm); if not, redo the assembly.
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to Mating Apparatus
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Install the stud into the apparatus by hand until it is fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean. Push the elbow onto the mating part. Using the appropriate assembly tool (600AT for products dated Sep 30, 2013 or earlier, torque to 19-25 ft-lbs; 600ATM for products dated Oct 1, 2013 or later, tighten to 50-60 ft-lbs, DO NOT EXCEED 60 ft-lbs), engage the hex broach in the contact assembly, insert it into the elbow interface to engage the stud, and torque/tighten as specified.
- Ground the Cable Shield
Insert one end of a piece of wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Verify Seating and Perform Voltage Test (Optional)
Confirm complete assembly by checking that no portion of the colored interface sleeve is visible when viewed from the side. If installing a 656CETP, you may perform a voltage test using its integral capacitance test point. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
- Install Loadbreak Accessories (Optional)
If using optional loadbreak accessories (e.g., DR(G), ESA, GLR, or LR), clean and lubricate the entire loadbreak interface and the accessory of the appropriate voltage class with the supplied lubricant or ELASTIMOLD® approved lubricant. Install the accessory to the tap plug interface following the instructions provided with that specific product.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.