ABB Installation Products 655CETP-J5300-DRG 600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Aluminum Lug…
UPC: 075114234597
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV, 600 Amp Deadbreak / 200 Amp Loadbreak Rated
- Accommodates cable insulation diameters from 0.980" to 1.180"
- Supports compressed stranded conductors up to 350 kcmil or compacted solid conductors up to 400 kcmil
- Includes stud, cable adapter, aluminum lug, and insulated cap
- Reduces stack height by 2.67" for simplified installation
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 15kV Connector |
Color | Red |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Connection Type | Combo T Elbow Reducing Tap Plug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 655CETP |
Size | Cable Insulation Diameter 0.980-1.180 inches, Conductor Size 350 kcmil or 400 kcmil |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow |
Voltage Rating | 15 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-K0300-SG3
15-25kv 600 Amp Dead Break Elbow With Sealing Kit, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656CETP-P0410-DRGS
15/25kV, 600 Amp Base Aluminum, includes test point, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Insulated Cap and Shrink-Fit Jacket Seal Kit
167RLR-H-5260
200 Amp LoadBreak Replacement Elbow without Test point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
655CETPL0330
600 Amp, 15KV, Combo T Elbow Reducing Tap Plug with stud, cable adapter, Lug and Insulated Cap kit, No Test Point, Cable Insulation Diameter Range - 1.180 ti 1.465 inches, Connector Type - Universal Aluminum, Connector Size - AWG or Kcmil - Stranded Compressed 500, Solid/Compact 600, MMSQ Compact only 300.
K655CETP-M0380
15/25kV, 600 Amp, no test point, Combo T Elbow Reducing Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 700/750 kcmil or Solid/Compact 900 kcmil.
655CETP-J0270-DRG
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. With Insulated Cap
655CETP-L0380
15kv, 600 Amp (base aluminum) No Test Point, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, Cable Insulation Diameter Range - 1.180 to 1.465 inches (30.0 to 37.2 mm), Universal Aluminum Connector Type, Connector Sizing - 750 Stranded/Compressed, 900 Solid/Compact. No Sealing Kit.Frequently Asked Questions
What is the maximum cable insulation diameter supported?
The ABB 655CETP-J5300-DRG supports cable insulation diameters from 0.980 inches to 1.180 inches.
What conductor sizes can this tap plug accommodate?
It can accommodate compressed stranded conductors up to 350 kcmil or compacted solid conductors up to 400 kcmil.
Does this tap plug have a test point?
No, this specific model, the 655CETP-J5300-DRG, does not include a test point.
What is the current rating of this ABB elbow tap plug?
The ABB 655CETP-J5300-DRG has a current rating of 600 Amps.
What is the voltage rating for this ABB tap plug?
This ABB tap plug is rated for 15kV.
How to Install 600 Series CETP Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600 Series CETP Deadbreak Elbow Connectors, including cable preparation, lug crimping, and connection to high voltage apparatus.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools (knife, strippers), Crimping tool (for compression lug), 600AT or 600ATM assembly tool, Hotstick (for test point cap removal), Suitable sensing device (for capacitive test point), Wire brush (for aluminum conductors)
Supplies needed:
655/656/675/676CETP Elbow Connector kit (includes Elbow, Cable Adapter, Compression Lug, Lubricant), Vinyl Plastic Tape, Tape Retainer (if applicable), Tape Marker (if applicable), 10TL cable shield adapter (if using UNISHIELD® or lead sheath cable), No. 14 AWG Copper wire (or equivalent) for grounding, Suitable grounding connector, Silicone grease (for test point cap), HV insulated cap(s) or connector(s) (if replacing shipping covers), DR(G), ESA, GLR, or LR mating connector (if applicable)
- Prepare for Installation and Position Cable
DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all parts for damage, proper rating, and compatibility. Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare the Cable Shield and Insulation
Remove the outer jacket to the specified dimension. Fold back shield wires. Depending on your cable type, remove the flat metallic tape shield and secure with vinyl plastic tape, or remove fabric tape shield and install tape retainer and tape marker, or remove longitudinally corrugated shield and install tape marker, or remove semi-con shield and install tape marker. If using UNISHIELD® or lead sheath cable, refer to the 10TL cable shield adapter instructions for preparation and grounding. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove the protruding cable insulation, cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length should be 4-3/8 to 4-11/16 inches (111mm-119mm); if not, redo the assembly. For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping (should be less than 6-1/2 inches / 165mm). Crimp the compression lug according to the supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter after crimping should be 6-1/2 to 7-1/4 inches (165mm-184mm); if not, redo the assembly.
- Install Elbow and Connect to Mating Product
Lubricate the cable adapter and the inside of the elbow cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further, ensuring the cable adapter remains flush with the tape marker. Remove the tape marker. DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from the elbow and the mating part. Install the stud into the apparatus by hand until fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant.
- Secure Elbow to Mating Product
Push the elbow onto the mating part. Engage the hex broach of the contact assembly with the 600AT (for products dated September 30, 2013 or earlier) or 600ATM (for products dated October 1, 2013 or later) assembly tool. Insert the contact assembly into the elbow interface to engage the stud. For 600AT, torque the contact assembly until the torque limiter ratchets (19 to 25 foot/pounds). For 600ATM, tighten the contact assembly to 50/60 foot/pounds torque, but DO NOT EXCEED 60 FOOT POUNDS TORQUE.
- Ground the Elbow and Cable Shield
Insert one end of a piece of wire (at least No. 14 AWG Copper equivalent) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must also be grounded; follow the instructions supplied with your grounding device, or use an alternate method if no device is used. It is recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Install Tap Plug Interface (If Applicable) and Verify Seating
Clean and lubricate the entire loadbreak interface and the DR(G), ESA, GLR, or LR of the appropriate voltage class with the supplied lubricant. Install the DR(G), ESA, GLR, or LR to the tap plug interface following their respective instructions. Verify complete assembly by ensuring no portion of the colored interface sleeve is visible when viewed from the side.
- Perform Voltage Test (656CETP Only)
If using a 656CETP, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer’s directions. Contamination, moisture, or incorrect equipment can cause a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.