ABB Installation Products 35PCJ1Q1400 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 075114105118
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV Power Cable Joint, Style 1
- Single Piece Housing
- Insulation Diameter: 1.900" - 2.120"
- Aluminum Conductor: 1000 AWG Solid
- Manufacturer: ABB - Installation Products
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 15-3/4 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ1P1400-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Solid 1000. Cold-Shrinkable Jacket Seal Included.
15PCJ1L1270
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1H2260
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.
15PCJ2G1240-F1220
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
69TCJS44DP0597633
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 4, Connector type Copper/no connector required, Connector Code 00P - Not Included, Heatsink Size N - Not Required, Heatsink Bore - N - Not Required. Type Shield - N - Unknown, Metallic Screen Continuity Kit - B - 4/0 Bonding Cable 6 foot Quantity 2 with 4 Split Bolts, Armor Kit - not specified, Outer Jacket Restoration Kit - not specified
15PCJ1G2300
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded 350.
35PCJ1K1250-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0. Cold-Shrinkable Jacket Seal Included.
69TCJS45DP0597945-Q
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, Connector type Copper/no connector required, Connector Code 00P - Not Included, Heatsink Size N - Not Required, Heatsink Bore - N - Not Required. Type Shield - N - Unknown, Metallic Screen Continuity Kit - B - 4/0 Bonding Cable 6 foot Quantity 2 with 4 Split Bolts, Armor Kit - not specified, Outer Jacket Restoration Kit - not specified, For QatarFrequently Asked Questions
What is the outside diameter of a 35PCJ2QX joint?
The outside diameter (Dimension B) for a 35PCJ2QX joint is 3 3/4 inches.
What is the overall length of a 35PCJ1QX joint?
The overall length (Dimension A) for a 35PCJ1QX joint is 15 3/4 inches.
What safety standards do Elastimold PCJ power cable joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should not be used on aluminum conductors.
What is the maximum conductor size supported by PCJ joints?
PCJ power cable joints support conductor sizes up to 1250 kcmil.
What is the purpose of PCJ Style 1 power cable joints?
Style 1 PCJ power cable joints are designed for straight splicing of two similar cables.
What is the short-time current rating for PCJ power cable joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating for PCJ power cable joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
Do PCJ power cable joints require taping during installation?
No, the cable entrance engages the insulation shielding of the cable, eliminating the need for taping.
How are PCJ Style 2 power cable joints used?
Style 2 PCJ power cable joints include separate cable adapters, allowing for transition splicing between two different cable sizes.
How to Install the ABB 15/25/35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for installing the ABB 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for connecting aluminum or copper conductors in wire shielded cables.
Estimated time: 3h
Tools needed:
Cable stripping tool, Wire brush, Crimping tool, Measuring tape or ruler, Cutting tool, T&B WT3D tool (for 35kV DELTECt Cable ties)
Supplies needed:
DELTECt Cable ties (TYD5135, for 35kV ONLY), Appropriate connector (for grounding and shield wires), #14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG), Cable (to be joined)
- De-energize All Apparatus
DANGER: Ensure all apparatus in the work area are completely de-energized before beginning installation or removal of any parts. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices.
- Inspect Components and Gather Tools
Check the contents of the package to ensure they are complete and undamaged. Inspect all components for proper fit with the cable and/or mating products. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Prepare Cable Lengths and Jackets
Overlap both cables and cut them to 12 inches (305mm) from the centerline of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Finally, cut both cables at the centerline of the joint.
- Fold Back Shield Wires and Taper Cable 1
Fold back the shield wires on both cables. Taper the edge of Cable 1's insulation at least 1/2 inch to no greater than 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield of Cable 1.
- Store Joint Housing on Cable 1
Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, pushing it up to the shield wires. This procedure will not contaminate electrical interfaces.
- Remove Cable Insulation and Insulation Shield
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the dimensions provided in the document for your conductor size ('X' and 'Y' dimensions). DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.
- Install and Crimp the Conductor Splice
If conductors are aluminum, wire-brush them and immediately insert into the splice. Crimp the splice following its recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' dimension. Remove any sharp protrusions or burrs from crimping, ensuring no metal chips remain in the splice or joint assembly area.
- Clean and Lubricate Cables for Housing
Clean the cables where indicated in the diagram. Lubricate the cables in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield on both sides of the splice.
- Position the Joint Housing
Slide the joint housing into its final position over the splice. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Install 35kV Cable Ties and Prepare Grounding Eye (35kV ONLY)
For 35kV installations ONLY: Install two DELTECt Cable ties on each end of the cable entrance. Install the outer ties approximately 1/4 inch from the splice edge, then the second ties approximately 1/4 inch from the first, offsetting their locking heads. Use the T&B WT3D tool to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye.
- Connect Grounding and Shield Wires
Retrain the shield wires and secure them to the ends of the joint as shown in the diagram. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector.
- Reconstruct Cable Jacket
Reconstruct the cable jacket (where applicable) over both cables and the joint housing to complete the installation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.