ABB Installation Products 35PCJ1P2380 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786645343
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35 kV Voltage Rating
- Style 1 with Single Piece Housing
- Cable Insulation Diameter: 1.725" - 1.935"
- Copper Conductor Material
- 750 AWG Stranded Conductor Size
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 750 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 15-3/4 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.8500 L |
Package Weight (Metric) | 1.7460 kg |

35PCJ1N1380-S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Jacket Seal included.
25PCJ1G1230-1220
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
25PCJ1P1410
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
15PCJ1H2270
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
25PCJ1J1230
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1K1330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
15PCJ1G1210
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #3/Solid #2.
25PCJ1H1240-1230
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.Frequently Asked Questions
How is a transition joint catalog number constructed?
When constructing a catalog number for a transition joint, list the larger connector first and the smaller connector second.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What conductor types are compatible with PCJ joints?
These joints can be used with copper or aluminum conductors, accommodating a wide range of sizes up to 1250 kcmil.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What is the maximum pull force the interlock withstands?
The pin-and-socket interlock design of the PCJ power cable joints can withstand a pull force up to 500 lb.
What is the continuous current rating of the joints?
The continuous current rating for the PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What is the phase-to-ground voltage for a 35 kV class joint?
For a 35 kV class joint, the phase-to-ground voltage is 20.2 kV.
What is the BIL impulse withstand for a 25 kV class joint?
A 25 kV class joint has a BIL impulse withstand of 150 kV (1.2 x 50 μsec. wave).
What is the DC withstand during installation for a 15 kV joint?
For a 15 kV class joint, the DC withstand during installation is 56 kV.
How to Install the 15/25/35PCJ1 Series Cable Joint
This guide provides step-by-step instructions for installing the 15/25/35PCJ1 series permanent, fully shielded, and submersible cable joint for aluminum and/or copper conductors.
Estimated time: 2h
Tools needed:
Cable stripping tools, Knife or tapering tool, Wire-brush, Crimping tool, Burr removal tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), Deltect Cable ties TYD5135 (for 35kV only), #14 AWG copper wire or equivalent (if shield wires are smaller), Cleaning supplies
- Ensure Safety and Prepare Work Area
De-energize all apparatus in the work area before beginning installation. Inspect all product parts for damage, proper rating, and compatibility with mating parts. Ensure all required tools and supplies are readily available and maintain a clean work environment throughout the procedure.
- Perform Initial Cable Preparation
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables at the center line of the joint.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1's insulation shield from at least 1/2 inch to no greater than 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the housing onto Cable 1, positioning it up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables according to the specified 'X' and 'Y' dimensions in the product documentation. WARNING: Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor during this process.
- Install the Splice
If conductors are aluminum, wire-brush them and immediately insert into the splice; verify dimension against the 'Max Check Before' table. Crimp the splice per recommendations. Wipe off excess inhibitor; verify distance between cable insulations against the 'Max Check After' table. Remove any sharp protrusions/burrs and metal chips from the splice and assembly area. Clean cables where indicated and lubricate to create a ramp of lubricant at the insulation shield edge.
- Complete Joint Assembly
Slide the housing into its final position, ensuring proper placement by equalizing the deformation of the joint ends. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance (outer ties approx. 1/4” from splice edge, second ties approx. 1/4” from first with offset locking heads). Use a T&B WT3D tool to tighten and trim. Remove the yellow pin from the joint grounding eye. Retrain shield wires and secure to the joint ends. Insert one shield wire from each cable (if #14 AWG or larger) through the joint grounding eye; use #14 AWG copper wire if shield wires are smaller. Connect joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (if applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.