ABB Installation Products 25PCJ1J1230 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786646852
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Voltage rating: 25kV for medium-voltage applications
- Insulation diameter range: 0.980 inch to 1.180 inch
- Conductor compatibility: Aluminum #1 AWG stranded or solid 1/0
- Single-piece housing for simplified installation
- Designed for outdoor, underground, or vault applications
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | #1 STR AWG , 1/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.2500 L |
Package Weight (Metric) | 1.4740 kg |

25PCJ2J1230-G1230
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1K1330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
15PCJ1G1210
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #3/Solid #2.
25PCJ1H1240-1230
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1J2270
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
35PCJ1L
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch.
15PCJ1K2320
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 450.
15PCJ1H1270
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.Frequently Asked Questions
What conductor sizes are supported by PCJ joints?
PCJ joints support conductor sizes from #2 AWG up to 1250 kcmil for both stranded/compressed and compressed/solid types.
What is the minimum cable insulation diameter for 25PCJ-1?
For 25PCJ-1, the minimum cable insulation diameter is 0.760 inches (Symbol G).
What is the short-time current rating of PCJ joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating of PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the AC withstand voltage for a 35 kV PCJ joint?
A 35 kV class PCJ joint has an AC withstand at 60 Hz for 1 minute of 69 kV.
What is the BIL impulse withstand for a 25 kV PCJ joint?
For a 25 kV class PCJ joint, the BIL impulse withstand (1.2 x 50 μsec. wave) is 150 kV.
What safety standards do PCJ joints meet?
The shield design of PCJ joints meets the IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
Can PCJ joints be used with fabric-tape or lead-jacketed cables?
Yes, PCJ joints can be used with fabric-tape shielded or lead-jacketed cables when the proper Elastimold cable shield adapter or grounding device is utilized.
What cable types are PCJ joints designed for?
PCJ power cable joints are designed for use with UD cable with concentric neutral and extruded insulation shielding.
What are the main uses of PCJ power cable joints?
PCJ power cable joints are used for straight splicing of two similar cables or transition splicing of different cable sizes up to 1250 kcmil.
How to Install the 25PCJ1 Series Straight Joint
This guide provides step-by-step instructions for the permanent, fully shielded, fully submersible installation of the 25PCJ1 series straight joint for wire shielded cables. It covers cable preparation, splice installation, and final assembly.
Estimated time: 2h
Tools needed:
Cable cutter, Measuring tape, Tapering tool or knife, Cable insulation stripper, Insulation shield removal tool, Wire brush (for aluminum conductors), Crimping tool, Deburring tool, Cleaning supplies, T&B WT3D tool (for 35kV only), Wire strippers, Crimpers
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Inhibitor (if aluminum conductor), DELTECt Cable ties TYD5135 (for 35kV only), #14 AWG copper wire or equivalent (if needed), Appropriate connector (for grounding wires)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Verify that all contents of the package are complete and undamaged. Inspect all components for proper fit with the cable and/or mating products before proceeding.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires on both cables. Finally, cut both cables precisely at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation shield from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, pushing it up to the shield wires for temporary storage.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the specified dimensions (X and Y from the diagram). Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor during this process.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Crimp the splice following the manufacturer's recommendations. Wipe off any excess inhibitor. Remove any sharp protrusions or burrs generated during crimping, ensuring all metal chips are cleared from the assembly area. Clean and lubricate the cables as indicated, building up lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper alignment by observing equal deformation of the joint ends. For 35kV installations ONLY, install two DELTECt Cable ties on each end of the cable entrance and remove the yellow pin from the joint grounding eye. Retrain and secure the shield wires to the ends of the joint. Insert one shield wire from each cable (if #14 AWG or larger, otherwise use #14 AWG copper wire) through the joint grounding eye. Connect all joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket over both cables and the joint housing where applicable.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.