ABB Installation Products 25PCJ1M2290 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786432660
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV rated medium-voltage cable joint for copper conductors
- Accommodates 350 AWG solid copper conductors
- Single-piece housing for simplified installation and reduced labor
- Compatible with cable insulation diameters from 1.370" to 1.630"
- Designed for underground and aerial medium-voltage applications
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 350 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Power Cable Joint Style 1 |
Size | 14-3/8 inch long |
Size | 1.370 inch to 1.630 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.5000 L |
Package Weight (Metric) | 1.1340 kg |

25PCJ1M1300
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
15PCJ2K1330-K1310-S
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 500. Cold-Shrinkable Jacket Seal Included.
15PCJ1K1330-S
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cold-Shrinkable Jacket Seal Included.
15PCJ1K2340-2320
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 550 /Solid 650. Copper Conductor. Conductor Size AWG Stranded 450.
15PCJ1K2310-S
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Solid 500. Cold-Shrinkable Jacket Seal Included.
15PCJ2L1380-L1340
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 550 /Solid 650.
25PCJ1J1300
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
15PCJ1L2380
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 750.Frequently Asked Questions
What conductor types are compatible with PCJ joints?
The joints can be used with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What is the continuous current rating for PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating for PCJ joints?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What is the phase-to-ground voltage for the 15 kV class?
For the 15 kV class, the phase-to-ground voltage is 8.7 kV.
What is the BIL impulse withstand for the 35 kV class?
The 35 kV class has a BIL impulse withstand of 300 kV (1.2 x 50 μsec. wave).
What is the corona extinction voltage for the 25 kV class?
For the 25 kV class, the corona extinction voltage is 22 kV with 3 pC sensitivity.
What cable types are compatible with PCJ power cable joints?
They are designed for UD cable with concentric neutral and extruded insulation shielding. They also work with fabric-tape shielded or lead-jacketed cables using proper adapters.
Can copper connectors be used on aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
How to Install the 25PCJ1 Series Straight Joint
This guide provides detailed instructions for installing the 15/25/35PCJ1 Series straight joint, a permanent, fully shielded, and submersible joint for wire shielded cables. It covers cable preparation, splice installation, and final assembly for aluminum to aluminum or aluminum to copper conductors.
Estimated time: 2h
Tools needed:
Wire brush, Crimping tool (for splice and connectors), T&B WT3D tool (recommended for 35kV cable ties, if applicable), Cable stripping tools, Utility knife
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), DELTECt Cable ties (TYD5135, for 35kV only), No. 14 AWG copper wire (or equivalent, if shield wires are smaller)
- Ensure Safety and Prepare for Installation
DANGER: All apparatus must be de-energized during installation. Do not touch or move energized products. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, rating, and compatibility with mating parts. Gather all required tools and supplies, and maintain cleanliness throughout the procedure.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint to ensure sufficient length of shield wires. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables at the joint centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1's insulation shield at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, positioning it up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR during this process. Refer to the provided dimensions for 'X' and 'Y' based on your conductor size (e.g., 500-750 MCM or 1000 MCM).
- Install the Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table; if it exceeds, redo the assembly. Crimp the splice following the manufacturer's recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table; if it exceeds, redo the assembly. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are removed from the splice and joint assembly area. Clean the cables where indicated and lubricate in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly
Slide the housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, starting 1/4 inch (6mm) from the splice edge, then a second 1/4 inch (6mm) from the first with offset locking heads (T&B WT3D tool recommended). Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2 (use separate #14 AWG copper wire if shield wires are smaller). Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.