ABB Installation Products 25PCJ1M1380 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786631674
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV rated power cable joint
- Style 1, single-piece molded rubber housing
- Accommodates cable insulation diameters from 1.370" to 1.630"
- Designed for 750 kcmil stranded aluminum conductors
- Fully shielded and submersible for permanent connections
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 750 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.4100 L |
Package Weight (Metric) | 1.0930 kg |

25PCJ1N2380
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Conductor. Conductor Size AWG Stranded 750.
25PCJ1M2360-ELA
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 750. Elastimold
25PCJ1N1380
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
25PCJ1M2330
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Stranded 500.
25PCJ1M2360
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 750.
35PCJ1M1300
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
35PCJ1M1280-1270
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 250. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
25PCJ1M1360
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Solid 750.Frequently Asked Questions
What is the voltage rating of this ABB cable joint?
The ABB 25kV Power Cable Joint has a voltage rating of 25 kV.
What cable insulation diameters does this joint accommodate?
This joint is designed to accommodate cable insulation diameters ranging from 1.370 inches to 1.630 inches.
What type of conductor material is this joint designed for?
This joint is specifically designed for aluminum conductors.
What is the housing style of this ABB cable joint?
This ABB cable joint features a Style 1, single-piece housing.
How to Install the 15/25/35PCJ1 Straight Joint
This guide details the permanent installation of the 15/25/35PCJ1 straight joint, a fully shielded and submersible connector for aluminum or copper conductors in wire-shielded cables. Ensure all apparatus are de-energized before starting installation to prevent serious injury.
Estimated time: 1h 30m
Tools needed:
Wire-brush, Crimping tool, Wire strippers, T&B WT3D tool (for 35kV only)
Supplies needed:
Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (user supplied), DELTECt Cable ties (for 35kV only), #14 AWG copper wire or equivalent
- Perform Initial Safety Checks and Inspections
De-energize all apparatus in the work area before beginning installation. Inspect all parts for damage, correct rating, and compatibility with mating components. Verify package contents are complete and undamaged, and ensure all components fit properly with the cable and/or mating products. Have all required tools at hand and maintain cleanliness.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables precisely at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, pushing it up to the shield wires for temporary storage.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation from both Cable 1 and Cable 2 according to the specified "X" and "Y" dimensions (refer to documentation diagrams for exact measurements). Then, carefully remove the insulation shield from both cables. Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor during this process.
- Install the Conductor Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the "Max Check Before" table provided in the documentation; redo assembly if it exceeds. Crimp the splice following its specific recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the "Max Check After" table; redo assembly if it exceeds. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are cleared from the assembly area. Clean cables where indicated and lubricate to build a ramp at the insulation shield edge.
- Complete the Joint Assembly
Slide the joint housing into its final position, ensuring proper alignment by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, 1/4” from the splice edge and 1/4” from the first, with offset locking heads. Use a T&B WT3D tool to tighten and trim. For 35kV ONLY: Remove and discard the yellow pin from the joint grounding eye. Retrain shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, repeating for Cable 2 (use #14 AWG copper wire if shield wires are smaller). Connect joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (if applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.