ABB Installation Products 25PCJ1H2230 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 075114327916
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV Power Cable Joint, Style 1
- Single-piece housing for efficient installation
- Accommodates cable insulation diameter: 0.850" - 1.050"
- Designed for Copper Conductor: AWG Stranded #1 / Solid 1/0
- Manufacturer: ABB - Installation Products
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | #1 STR AWG , 1/0 SOL AWG |
Connection | Compression |
Connection Type | Cable Joint |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Style 1 |
Size | 0.850-1.050 inch insulation diameter |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.7200 L |
Package Weight (Metric) | 0.7800 kg |

25PCJ2J1230-G1230
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
35PCJ2-J1230-H1210-S
35kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1 or Solid 1/0. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #3 or Solid #2. Includes Cold-Shrinkable Jacket Seal.
K676CH-BUS
15/25kV 900 Amp Series Deadbreak 4-Way Insulated Bus Bar Splice with Test Point. Plated Copper Components.
15PCJ1J2320
15kV, Power Cable Joint, Single Piece Housing. Cable Insulation Diameter .980 to 1.050 inches. Copper Conductor. Conductor Size 320 - 450 - 550kcmil. No Sealing Kit.
25PCJ2K2330
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 500 kcmil.
25PCJ1-G1270
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 or Solid 250 kcmil.
25PCJ1K2330
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size kcmil Stranded-Compressed 500, Solid-Compact 600.
15PCJ2-G1220-F1210
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Side 1 - Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded/Compressed #2 or Solid/Compact #1. Side 2 - Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded/Compressed #3 or Solid/Compact #2. Length 16.38 inch x 2.78 inch Diameter.Frequently Asked Questions
How are transition joints ordered for different cable sizes?
When ordering a transition joint for two different-size cables, list the larger connector first and the smaller connector second.
What are the available voltage classes?
The PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What is the maximum conductor size supported?
The PCJ power cable joints support a wide range of conductor sizes up to 1250 kcmil.
What types of splicing can these joints perform?
They can perform straight splicing of two similar cables or transition splicing of different cable sizes.
What are the installation environments for PCJ joints?
PCJ power cable joints can be installed in direct-burial, underground vault, and even overhead applications. They are fully submersible.
What standards do the PCJ joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the continuous current rating?
The continuous current rating of the PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What is the 25 kV class DC withstand during installation?
For the 25 kV class, the DC withstand during installation is 80 kV.
Can copper connectors be used with aluminum cables?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
How to Install the ABB 15/25/35PCJ1 Series Straight Cable Joint
This guide provides detailed instructions for installing the ABB 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for aluminum or copper conductors. Ensure all apparatus is de-energized and follow safety practices for high voltage electrical equipment.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Cable jacket removal tool, Cable insulation removal tool, Wire brush (for aluminum conductors), Crimping tool, Measuring tape, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), Deltec Cable ties TYD5135 (for 35kV only), #14 AWG copper wire (if needed)
- De-energize and Prepare Cables for Initial Cuts
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Overlap both cables and cut them to 12 inches (305mm) from the joint centerline. Remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires and then cut both cables at the joint centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1 at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the housing onto Cable 1, positioning it up to the shield wires.
- Remove Cable Insulation and Insulation Shield
Carefully remove the cable insulation and then the insulation shield from both cables according to the 'X' and 'Y' dimensions provided in the document's table for your conductor size. WARNING: DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR during this process.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them and immediately insert into the splice. Check the 'Max Check Before' dimension from the document's table. Crimp the splice following its specific recommendations. Wipe off any excess inhibitor. Check the 'Max Check After' dimension. Remove any sharp protrusions or burrs generated during crimping, ensuring all metal chips are cleared from the splice and joint assembly area. Clean the cables where indicated and lubricate them to create a build-up or ramp at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two Deltec Cable ties (TYD5135) on each end of the cable entrance, approximately 1/4 inch (6mm) from the splice edge, with the second tie 1/4 inch from the first and offset locking heads. Use the T&B WT3D tool to tighten and trim. Remove and discard the yellow pin from the joint grounding eye. Retrain and secure the shield wires to the ends of the joint. Insert one shield wire from each cable (if #14 AWG or larger, otherwise use separate #14 AWG copper wire) through the joint grounding eye. Connect all joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (if applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.