ABB Installation Products 168FLR3-C0270 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 783786824854
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Rated for 8.3kV nominal fuse voltage
- Accommodates cable insulation diameters from 20mm to 27mm
- Supports 4/0 AWG stranded/compressed aluminum conductors
- Two capacitive test ports for safe fault detection
- Large housing design for fuse installation and thermal management
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Insulation | True |
Length | 21.12 in |
Length | 536.448 mm |
Material | Aluminum |
Material | EPDM-Rubber |
Series | 168FLR3 |
Size | Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR3B0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.
168FLR3-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded/Compressed, 1/0 AWG Solid/Compact.
274FLR1-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Capactive Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid Compact
274AFLR1-B0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 15-19mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
274AFLR3-D5240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Direct Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid/Compact. No Sealing, Size 3.
274AFLR3-C0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Direct Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
274AFLR3-C0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Direct Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid/Compact.
168FLR3-C5250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Bi-Metal, Conductor size 250 - 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.Frequently Asked Questions
What is the product's primary application?
The Elastimold 168FLR combines full-range current-limiting fusing with 15kV hot stick operable, loadbreak elbow switching to improve distribution system reliability.
Does the product have a test point for fuses?
Yes, it has built-in voltage test points for quick and convenient blown fuse indication.
What types of conductors are compatible with the lugs?
Copper compression lugs are suitable for copper conductors only. Bi-metal compression lugs are suitable for both copper or aluminum conductors.
Is the fuse in the elbow connector replaceable?
Yes, the product features a split center section for easy fuse replacement.
What is the impulse withstand rating?
The impulse withstand rating is 95kV BIL (1.2 x 50 microsecond wave).
What industry standards does the product meet?
The product meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47, Latest Revision.
Can this product be used underwater?
Yes, the 168FLR Loadbreak Fused Elbow is fully sealed and submersible.
What is the interrupting capability of the fuse?
The fuse has a full-range current-limiting fusing with a 50,000 Amp symmetrical interrupting capability.
What is the current rating range for this device?
The current rating for the 168FLR Loadbreak Fused Elbow is 3-80 Amps.
What voltage class is this product designed for?
This product is designed for the 15kV voltage class, with an 8.3kV nominal fuse voltage and 10kV maximum rated fuse voltage.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe installation and initial setup of the 168FLR and 274FLR Loadbreak Fused Elbow Connectors, including cable preparation, component assembly, and neutral wire connection.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Allen Wrench (torque limiting), Wire brush, Crimp tool, Hotstick
Supplies needed:
Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant, Optional 200ECS Cold Shrink Cable Seal, No. 14 AWG (2.5mm) copper wire, Grounding connector
- Ensure Safety and Inspect Components
Before beginning, ensure all apparatus is de-energized to prevent serious injury. Inspect all kit contents for completeness, damage, and compatibility with mating parts. Check the threads by threading the probe into the compression lug; if resistance is encountered, replace the damaged component.
- Prepare Cable Length and Remove Jacket
Using the bushing centerline as a reference, cut excess cable at least 20 inches beyond the bushing. If using an optional 200ECS Cold Shrink Cable Seal, slide it onto the cable. Remove the cable jacket for a distance of 'A' (11-1/2 inches for FLR-1, 15-3/4 inches for FLR-3) plus 7-3/8 inches from the bushing centerline. Unwrap and fold the concentric neutral wires back over the jacket and bind them, or follow instructions for the cable seal kit. Squarely cut the cable a distance of 'A' from the bushing centerline, leaving 7-3/8 inches minimum for termination.
- Prepare Cable End and Crimp Compression Lug
Cut 1-1/8 inches squarely from the cable end, taking care not to nick the conductor. Wire brush the bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread the inhibitor. Crimp the unthreaded end of the compression lug to the conductor, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the outside of the lug and cable.
- Remove Insulation Shield and Clean Cable
Remove the insulation shield 5-1/2 inches from the end of the compression lug. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue, ensuring a clean surface for the connector.
- Lubricate and Assemble Cable Half Housing
Apply the supplied lubricant to the outside of the connector, the cable insulation, the conductive shield, and the cable entrance end of the Fused Elbow cable half. Do not substitute the lubricant. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A', allowing the fuse to be tightened before bottoming on the rubber.
- Install and Hand Tighten the Fuse
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. Hand tighten the fuse; do not overtighten as the fuse stud will fracture. Pull the housing up against the bottom of the tightened fuse.
- Assemble and Secure Probe Connector
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate, then lock it in position. Tighten the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Assemble Elbow Half Housing and Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other. Insert the probe into the probe connector, pushing on the cable if necessary for alignment. Start the threads by hand to avoid cross-threading. Tighten the probe using the special torque-limiting allen wrench by inserting the short end into the hole in the probe and tightening until the wrench bends and remains bent. Position the hose clamp as shown in the diagram and tighten it, but do not overtighten.
- Connect Concentric Neutral Wires to Ground
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eyes. If a 200ECS jacket seal was used, finish installing it. Twist all neutral wires, ensuring not to damage grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Connect Elbow to Mating Bushing
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. IMPORTANT: Only lubricate if the transformer and elbow are known to be de-energized. Connect the elbow to the bushing using a hotstick, following safe operating instructions. Do not operate by hand.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.