ABB Installation Products 15PCJ2N1410 15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable…
UPC: 783786430246
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage rating for medium-voltage power systems.
- Style 2 joint design with universal housing.
- Includes separate cable adapters for precise termination.
- Accommodates cable insulation diameters from 1.515" to 1.780".
- Suitable for 1000 AWG stranded aluminum conductors.
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 21 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.2500 L |
Package Weight (Metric) | 1.4740 kg |

15PCJ2M1410
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
25PCJ1L1310
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Solid 500.
15PCJ1M1330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
25PCJ2N1380
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
15PCJ1M2330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Stranded 500.
15PCJ2L2380-K2320
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Solid 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 450.
25PCJ1M2290
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 350.
15PCJ2K1330-K1310-S
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 500. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
Can copper connectors be used on aluminum conductors?
No, copper compression connectors should not be used on aluminum conductors. They are suitable for splicing copper conductors to copper conductors only.
What type of connector is needed for copper-to-copper splices?
An all-copper compression connector is required for copper-to-copper connections. The standard kit includes an aluminum connector.
What are the continuous and short-time current ratings?
The continuous current rating is equal to that of the cable rating. The short-time current rating is equal to the cable rating up to 35 kA.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard. The connectors meet ANSI 119.4 Class A and Class 3 ratings.
What pull force can the pin-and-socket interlock withstand?
The pin-and-socket interlock in PCJ power cable joints can withstand a pull force of up to 500 lb.
What conductor types and sizes are compatible?
PCJ power cable joints are compatible with copper or aluminum conductors. They can be used with a wide range of sizes up to 1250 kcmil.
What voltage classes are PCJ power cable joints available in?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
Where can Elastimold PCJ power cable joints be installed?
PCJ power cable joints can be installed in direct-burial, underground vault, and even overhead applications. They provide a permanent, fully shielded, fully submersible splice.
What types of cable splicing do PCJ joints support?
PCJ power cable joints support straight splicing of two similar cables or transition splicing of different cable sizes. They can handle conductors up to 1250 kcmil.
Can copper connectors be used on aluminum conductors?
No, copper compression connectors should not be used on aluminum conductors. They are suitable for splicing copper conductors to copper conductors only.
How to Install the Elastimold 15/25/35PCJ2WXXXX-RC Straight Joint
This guide provides step-by-step instructions for installing the Elastimold 15/25/35PCJ2WXXXX-RC straight joint, a permanent, fully shielded, and submersible joint for aluminum or copper conductor, wire shielded cables.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Wire strippers, Wire brush, Crimp tool, Hex wrench, Hose clamp
Supplies needed:
Elastimold Joint Housing, Splice (Conductor Contact), Cable Adapters, Lubricant, Retaining Collars, Electrical tape, Connector (user supplied for grounding), No. 14 AWG copper wire (if needed for grounding), Cable jacket reconstruction material (e.g., heat/cold shrink, user supplied), Bonding cable(s) (user supplied), Insulating and sealing tapes (user supplied), Solder (user supplied), CNW connectors (user supplied)
- Perform Safety Checks and Initial Inspection
DANGER: Ensure all apparatus is de-energized before beginning installation or removal of parts. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Inspect all components for damage, proper rating, and compatibility with mating parts and cables. Read the entire installation instructions before starting. Have all required tools at hand and maintain cleanliness throughout the procedure. Examine mating cable ends to ensure they are free from moisture and contaminants. If strand-filled or water-blocking material is present, contact the cable manufacturer for welding/crimping procedures.
- Prepare Cable 1 Jacket and Shield Wires
Using the stripping guide, carefully remove 11-1/4 inches (285.7mm) of the cable jacket from Cable 1. Fold back the shield wires and tape their ends to the jacket, allowing enough extra length to rejoin them later over the joint. Clean the surface of the insulation shield, shield wires, and jacket for a distance of 30 inches (760mm). Slide the joint housing onto Cable 1 to a distance of 30 inches (760mm).
- Prepare Cable Insulation and Mark
Using the stripping guide, carefully remove the insulation shield and cable insulation from both cables. DO NOT CUT OR NICK THE INSULATION, as this could lead to assembly failure. Wrap two turns of electrical tape 1 inch (25mm) from the edge of the insulation shield on both cables to serve as a marker. Clean the cable insulation, then lubricate it to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Install Cable Adapters
Take one cable adapter and lubricate the inside of both ends. Install the cable adapter onto Cable 1 until it meets the tape marker. Repeat this process for the other cable adapter on Cable 2.
- Install Retaining Collars
Select a retaining collar and partially thread the appropriate size setscrews (refer to instructions packaged with the collars). Position the retaining collar over the insulation, flush against the cable adapter. Using the supplied hex wrench, tighten each set screw only one or two turns at a time to keep the collar centered over the insulation. Continue tightening the set screws until they are below the surface of the collar. Repeat this process for Cable 2.
- Install Splice and Crimp Conductors
Thoroughly clean the ends of the cable adapters and the exposed cable conductors. Install a hose clamp around the adapter on the opposite side of the splice from where the housing is stored to hold the adapter in place during final assembly. Tape over the hose clamp to form a smooth surface. Wirebrush the exposed conductors of both cables and immediately insert them into the splice. Ensure the 'Check' dimension does not exceed 8-1/2 inches (215mm); if it does, redo the assembly. Crimp the splice following the recommendations provided with it. Wipe off all excess inhibitor. Check the distance between cable adapters; if it exceeds 8-3/4 inches (222mm), redo the assembly. Clean and lubricate the outside surface of the cable adapters before sliding the housing into its final position.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, centering it over the cable adapters. Remove all tape. Ensure that cable and adapter insulation are not exposed after positioning the joint. Reshape the shield wires and secure them to the ends of the joint. Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye; repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate user-supplied connector. Reconstruct the cable jacket (where applicable) over both cables and also over the joint housing using heat/cold shrink or other suitable material (not included in this kit).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.