ABB Installation Products 15PCJ1M1330 15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786432424
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV voltage class power cable joint for reliable medium-voltage connections.
- Accommodates cable insulation diameters from 1.370" to 1.630".
- Designed for 500 AWG stranded aluminum conductors.
- Fully shielded, fully submersible molded rubber housing with deadfront construction.
- Meets IEEE Standard 404 with high BIL and AC/DC withstand ratings.
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 500 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.5000 L |
Package Weight (Metric) | 1.1340 kg |

15PCJ2J1330
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size Stranded 500.
25PCJ2N1380
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
15PCJ1M2330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Stranded 500.
15PCJ2L2380-K2320
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Solid 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 450.
25PCJ1M2290
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 350.
15PCJ2K1330-K1310-S
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 500. Cold-Shrinkable Jacket Seal Included.
15PCJ1K1330-S
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cold-Shrinkable Jacket Seal Included.
15PCJ1K2340-2320
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 550 /Solid 650. Copper Conductor. Conductor Size AWG Stranded 450.Frequently Asked Questions
What are Elastimold PCJ power cable joints made of?
Elastimold PCJ power cable joints feature permanently crimped connectors inside ethylene propylene diene monomer (EPDM) rubber housings.
Where can PCJ power cable joints be installed?
They can be installed in direct-burial, underground vault, and overhead applications, providing a permanent, fully submersible splice.
What connectors are needed for copper-to-copper splices?
An all-copper compression connector is required for copper-to-copper connections.
What is the short-time current rating?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and connectors meet ANSI 119.4 Class A and Class 3 ratings.
What cable types are PCJ joints designed for?
PCJ power cable joints are designed for use with UD cable with concentric neutral and extruded insulation shielding.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables, while Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What conductor types and sizes are compatible?
PCJ joints are compatible with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What voltage classes are available for PCJ joints?
PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
How to Install a Single Core Joint (15PCJ1M1330)
This guide provides step-by-step instructions for the safe and proper installation of the 15PCJ1M1330 Single Core Joint, a permanent, fully screened, submersible joint for extruded solid dielectric cables.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Measuring tape or ruler, Wire brush, Crimping tool, Cleaning solvent, Clean cloth, Sandpaper, Heat gun, Soldering iron (optional, or tool for constant force spring)
Supplies needed:
Joint Housing (15PCJ1M1330), PVC tape, Conductor splice, Lubricant, Flat copper braid, Constant force spring (optional), Mastic tape, Heat shrink
- Prepare for Installation and Initial Cable Setup
Ensure all apparatus are de-energized before starting. Verify package contents, component compatibility, and have all required tools ready. Train the cables into their final position, square cut them leaving approximately 5mm between, and store the heat shrink on one of the cables.
- Remove Cable Jacket and Metallic Shield
Remove the jackets of both cables to the dimensions specified in the provided table. Carefully remove the cable metallic tape screen for the indicated distance and secure the ends with PVC tape. Ensure the PVC tape is on the copper tape and does not overlap onto the non-metallic screen.
- Prepare Non-Metallic Screen and Insulation
Carefully remove the cable non-metallic screen from both cables to the specified point, taking care not to nick or damage the insulation surface or conductor strands. Bevel the edge of Cable 1. Cut the insulation to the conductor on both cables to dimension 'E' (do not remove the insulation). Install a PVC tape marker on Cable 2 to dimension 'B' to locate the splice later.
- Temporarily Store Joint Housing on Cable 1
Apply one layer (half-lapped) of PVC tape over the metallic screen on Cable 1, starting at the jacket and extending 10mm beyond the metallic screen end. Install a different color PVC tape marker on Cable 1 to dimension 'B'. Lubricate both cable entrances of the splice housing. Clean and lubricate the insulation, non-metallic screen, and PVC taped portion of the metallic screen on Cable 1. Store the housing onto Cable 1 up to the jacket, ensuring sharp edges of the metallic screen are covered to prevent damage to the joint housing.
- Remove Cable Insulation
Carefully remove the cable insulation from both cables to dimension 'E' as specified in the table. Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor during this process.
- Install Conductor Splice
Wire brush the exposed conductors of both cables. Immediately insert the conductors fully into the conductor splice; do not crimp yet. Check the distance between insulations against the 'Before' crimping dimension in the table; if it exceeds, do not proceed and review instructions. Crimp the conductor splice according to the provided crimp chart. Remove any sharp protrusions or burrs and clean metal chips. Wipe off excess inhibitor. Recheck the distance between cable insulations against the 'After' crimping dimension; if it exceeds, do not proceed.
- Clean and Lubricate Core Surfaces
Remove all contaminants from the insulation surface. Clean the conductor, connector, and Cable 2 insulation surfaces with cleaning solvent and a clean cloth, always wiping towards the screen end. Lubricate cable insulation surfaces using the supplied lubricant, wiping towards the screen end to create a build-up or ramp of lubricant at the edge of the non-metallic screen.
- Position Joint Housing
Slide the joint housing over the crimp connector into its final position. Measure the distance between the joint housing and the PVC tape marker on each side; ensure distance 'X' is equal on both sides. Remove the PVC tape applied in Step C to expose 25mm of copper tape.
- Restore Screen
Wrap flat copper braid around each joint housing, continuing the ends over the metallic tape screen for 20mm on each side. Attach each end of the copper braid to the metallic tape screen by either soldering or using a constant force spring.
- Restore Outer Jacket
Lightly sand the outer surface of the jacket of both cables for a distance of 130mm. Heat both sanded areas for approximately 15 seconds, being careful not to burn the cables. Wrap two layers of mastic tape at the edge of the jacket on both cables. Position the heat shrink from Cable 1 over the center of the assembly and shrink it, starting at the center and working towards the ends.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.