Contact for Pricing
Overview
- Filterless, refrigerant-less design
- NEMA power cord connection standard
- Copper pipe and aluminum fins heat exchanger core
- Air movers with thermal protection
- Regulating mechanical thermostat set at 35 C (95 F), differential of 4 C (7 F)
- Solenoid water valve
- UL Listed to save customers time and money with agency approvals
- Capacities ranging from 870 watts to 6700 watts
Specifications
Application | Controls and Drives;Power Distribution |
Capacity Btu/h @ Δt 25degr.C | 2,968 Btu/h |
Capacity Watts @ Δt 25degr.C | 870 W |
Color | Light Gray |
Color | Gray |
Color Code | RAL 7035 |
Depth | 114 mm |
Depth | 4.49 in |
Finish | Powder Coated |
Height | 15.9 in |
Height | 404 mm |
Material | Mild Steel |
Max Current | 0.5 A |
Mechanical Advantage | Mild steel sheet metal standard |
NEMA Rating | 12 Indoor, dust-resistant |
Nominal Voltage | 115 V |
Operating Temperature | 10-50 °C |
Operating Temperature | 50-122 |
Operating Temperature | 10-50 |
Product Family | ClimaGuard |
Protection Rating | NEMA Type 12 |
Thickness | 1.21 mm |
Thickness | 18 ga |
Thickness | 51.40mm (2.024") |
Type | Heat Exchangers |
Voltage AC | 100-120 V |
Voltage Rating | 100 - 120 VAC |
Weight | 9 kg |
Weight | 19 lb |
Width | 12.12 in |
Width | 308 mm |
Package Dimensions (L x W x H) | 15.5 IN x 9 IN x 19.5 IN |
Package Dimensions (L x W x H) | 39.37 cm x 22.86 cm x 49.53 cm |
Package Weight (Imperial) | 19.000 L |
Package Weight (Metric) | 8.618 kg |
How to Install the WCHE01916002 Heat Exchanger
This guide provides step-by-step instructions for installing the WCHE01916002 heat exchanger, including mounting, plumbing connections, and initial setup.
Estimated time: 45m
Tools needed:
Screwdriver, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Adhesive gasket, Thread tape, NPT adapting valves
- Prepare the installation site
Ensure the cabinet is Type 12 or IP55 rated, clean, and has enough space for installation. Verify that there are no heat sources nearby and that air circulation is adequate.
- Cut the cabinet for mounting
Using the provided template for the WCHE01916002 model, cut the necessary openings in the cabinet. Remove any sharp edges or burrs from the cut area.
- Attach the adhesive gasket
Apply the adhesive gasket to the mounting surface of the heat exchanger to ensure a tight seal when mounted.
- Mount the heat exchanger
Position the heat exchanger against the cabinet and secure it using the included mounting screws. Confirm that the gasket forms a tight seal.
- Make plumbing connections
Connect the water supply using the included on/off valves and NPT adapting valves. Use thread tape on the valve threads to prevent leaks.
- Check for leaks
Introduce water into the circuit and inspect all connections for leaks. Ensure the pressure does not exceed the unit's specifications.
- Install pressure gauges
Install an inlet and outlet pressure gauge on the plumbing circuit along with a gate valve to control water flow and monitor pressure.
- Power up the unit
Connect the power supply to the heat exchanger and ensure all electrical connections are secure. Follow the manufacturer's guidelines for initial power-up.
- Perform initial checks
After powering up, verify that the unit operates correctly and check for any unusual noises or leaks.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.