Contact for Pricing
Overview
- All exterior components are 316 stainless steel or corrosion-resistant composite
- Space-saving flush or exterior mounted models available
- Local visual indicators provide system status
- Leak compensation models are equipped with rapid purge valve and visual purge status indicator
- All models utilize dry, clean inert gas supply of 60 PSI (4 bar) to 115 PSI (8 bar)
- Ambient operating temperature -4°F (-20°C) to 131°F (55°C)
- Type X models provide automatic purge cycle and 4PNO/20A/440VAC power contactor with 115 VAC or 230 VAC coil
Specifications
Application | Hazardous Environments |
Certification Type | Y and Z |
Color | Unpainted |
Consist Of | P P Leak Comp Brkt 60 YZ IS |
Finish | Brushed |
Material | Stainless Steel 316L |
Material | SS Type 316;Stainless Steel 316L |
Modification Services | No |
Mounting | Exterior |
Mounting Type | Exterior Mount |
Operation Type | Leak Compensation |
Size | 4-8 bar, <60 cu ft in |
Thickness | 3.18 mm |
Thickness | 11 ga |
Thickness | 51.40mm (2.024") |
Type | Other Accessories |
Weight | 8.3 lb |
Works With | NEMA / IEC |
Package Dimensions (L x W x H) | 9.25 IN x 6.75 IN x 13.25 IN |
Package Dimensions (L x W x H) | 23.495 cm x 17.145 cm x 33.655 cm |
Package Weight (Imperial) | 8.300 L |
Package Weight (Metric) | 3.765 kg |

LB48SST
1-1/4 Inch 316 Stainless Steel Form 8 (LB) Conduit Body, Cover and Gasket with Polished Finish
CBS18HIC50516
Electrical box hardware assembly that provides conduit support on both sides of an electrical box. It is made of pre-galvanized steel and has a silver finish. The assembly will mount 4" square boxes and fits 1/2" EMT conduit. It fits flanges from 5/16" to 1/2".How to Install the nVent Hoffman Purge/Pressurization Unit (PCFB1YZ/PCFF1YZ)
This guide provides step-by-step instructions for installing and configuring the nVent Hoffman Purge/Pressurization Unit to ensure safe operation in hazardous environments.
Estimated time: 45m
Tools needed:
Screwdriver, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Terminal connectors, Orifice plates
- Prepare the installation site
Use the supplied mounting template to cut mounting holes into the enclosure. Ensure that the Control Unit and Relief Valve are diagonally opposed for optimal installation.
- Mount the Control Unit and Relief Valve
Securely fix the Control Unit and Relief Valve to the enclosure using the mounting screws. Ensure both components are properly aligned and securely attached.
- Install the Spark Arrestor
Select the appropriate orifice for the required purge flow rate and fit it into the Spark Arrestor using the circle-clip. Attach the Spark Arrestor to the enclosure, ensuring it is diagonally opposed to the Control Unit.
- Connect the air supply
Connect the isolated air supply to the Control Unit. Ensure that the supply pressure is set to 60 PSIG (4 bar) and does not exceed 115 PSIG (8 bar).
- Check enclosure integrity
Ensure that the enclosure door is closed, fully latched, and free of leaks before proceeding.
- Adjust the Flow Control Valve
Slowly increase the Flow Control Valve until the Alarm Indicator changes from RED to GREEN, indicating that the enclosure is pressurized.
- Power up the enclosure
After the purge time has been completed, power can be applied to the enclosure. Ensure that all safety checks have been performed before powering on.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.