Authorized Schlegel Elektrokontakt Distributor
Schlegel Elektrokontakt DTI - Switching Function: Momentary Travel: 6 mmContact Type: Cage-Clamp 0.08-2.5 mm? Contact Equipment: 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No

Schlegel Elektrokontakt DTI Switching Function: Momentary Travel: 6 mmContact Type: Cage-Clamp 0.08-2.5 mm? Contact…


Documents & Media
Technical DrawingSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The Schlegel Elektrokontakt DTI is a momentary contact element designed for industrial control applications. It features a 6 mm actuation travel and utilizes Cage-Clamp terminal technology for conductor cross-sections ranging from 0.08 mm² to 2.5 mm² (AWG 28–14). The contact material is AgNi (Silver Nickel), offering a low contact resistance of less than 20 mOhm (new). This module is rated for a thermal continuous current of 16 A. For AC applications, it supports AC15 A600 with a rated operational voltage (Ue) of 240 V / 380 V and a rated operational current (Ie) of 3 A / 1.9 A. In DC applications, it is rated for DC13 Q300 with a rated operational voltage (Ue) of 250 V / 125 V / 60 V / 24 V and a rated operational current (Ie) of 0.27 A / 0.55 A / 1 A / 2 A. The rated insulation voltage (Ui) is 600 V for AC and 400 V for DC. The DTI switch has a mechanical service life of 1 million switching cycles and an electrical service life of 50,000 switching cycles at rated load. It meets environmental testing standards including vibration resistance (50 m/s² at 5-150Hz) and shock resistance (30 m/s² at 50ms). The DTI is classified as a Category D switch. It is suitable for use in a wide range of operating temperatures from -25°C to 55°C. Approvals include CCC, cCSAus, DNVGL, ENEC10, VDE, CE, KEMA KEUR, TÜV_Süd, and UKCA. The SKU for this product is DTI.
  • Momentary switching function with 6 mm actuation travel.
  • Cage-Clamp terminal technology for 0.08-2.5 mm² conductors.
  • AgNi (Silver Nickel) contact material for reliable performance.
  • Rated for 16 A thermal continuous current.
  • AC15 A600 and DC13 Q300 electrical ratings with multiple voltage/current options.
  • Compact design for integration into control panels and machinery enclosures

Specifications

Actuation Travel
6 mm
Certifications
CCC, cCSAus, DNVGL, ENEC10, VDE, CE, KEMA KEUR, / TÜV_Süd, UKCA
Connection Type
Cage-Clamp
Connection Type
Cage-Clamp 0.08-2.5 mm²
Contact Material
AgNi
Current Rating
16 A
Ip Rating
IP65/IP67
Ip Rating
Class II (protective insulation)
Material
AgNi
Mounting Type
Panel Mount
Poles
1 x NO
Series
DTI
Size
6 mm Travel
Size
Ø16.2 mm panel cut-out, 12 mm front bezel height
Utilization Category
AC15 A600 DC13 Q300
Voltage Rating
300 V
Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

BZI

Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No
Switching Function: Momentary Travel: 6 mmContact Type: Cage-Clamp 0.08-2.5 mm? Contact Equipment: 1 x NCContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

DTO

Switching Function: Momentary Travel: 6 mmContact Type: Cage-Clamp 0.08-2.5 mm? Contact Equipment: 1 x NCContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No
Contact Equipment: LampholderContact Type: Faston Terminal 2.8 x 0.8 mmProtection Class: II (protective insulation) Lambholder: T55KIllumination: Yes Labeling Option: No

BL5

Contact Equipment: LampholderContact Type: Faston Terminal 2.8 x 0.8 mmProtection Class: II (protective insulation) Lambholder: T55KIllumination: Yes Labeling Option: No
Switching Function: Momentary Product Group: Contact BlocksContact Type: Screw Connection 2.5 mm? Travel: 3 mm Contact Equipment: 1 x NC + 1 x NOIllumination: No Protection Class: II (protective insulation) Labeling Option: NoContact Material: AgNi IP Protection Front: IP20

BZOIK

Switching Function: Momentary Product Group: Contact BlocksContact Type: Screw Connection 2.5 mm? Travel: 3 mm Contact Equipment: 1 x NC + 1 x NOIllumination: No Protection Class: II (protective insulation) Labeling Option: NoContact Material: AgNi IP Protection Front: IP20
Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: Yes Lambholder: T55K Labeling Option: No

BZLOI5

Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: Yes Lambholder: T55K Labeling Option: No
Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

BZOI

Switching Function: Momentary Travel: 3 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No
Switching Function: Momentary Travel: 6 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 2 x NC + 2 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

AT2

Switching Function: Momentary Travel: 6 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 2 x NC + 2 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No
Switching Function: Momentary Travel: 6 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

AT

Switching Function: Momentary Travel: 6 mmContact Type: Faston Terminal 2.8 x 0.8 mm Contact Equipment: 1 x NC + 1 x NOContact Material: AgNi Protection Class: II (protective insulation)Illumination: No Labeling Option: No

Frequently Asked Questions

What are the operating temperature limits for the DTI?

The DTI has a storage temperature range of -40°C to 70°C and an operating temperature range of -25°C to 55°C, with or without illumination.

What type of connection technology does the DTI use?

The DTI features Cage-Clamp connection technology for its terminals, supporting wire sizes from 0.08 mm² to 2.5 mm².

What are the AC and DC electrical ratings for the DTI?

For AC, the DTI is rated AC15 A600 with a rated insulation voltage of 600 V and rated operational voltage of 240 V / 380 V. For DC, it's DC13 Q300 with a rated insulation voltage of 400 V and rated operational voltage of 250 V / 125 V / 60 V / 24 V.

What is the rated operational current for AC and DC use?

The rated operational current (Ie) for AC is 3 A or 1.9 A, and for DC, it is 0.27 A, 0.55 A, 1 A, or 2 A depending on the voltage.

What is the mechanical and electrical lifespan of the DTI?

The DTI has a mechanical lifespan of 1 million switching cycles and an electrical lifespan of 50,000 switching cycles under nominal load.

What are the minimum current and voltage requirements for the DTI?

The minimum current for the DTI is 1 mA under laboratory conditions, and the minimum voltage is 5 V.

What are the DTI's vibration and shock resistance ratings?

The DTI is resistant to 50 m/s² vibration at 5-150 Hz and 30 m/s² shock at 50 ms.

What is the switching capacity of the DTI?

The switching capacity is 10Ie for AC and 1.1Ie for DC.

What is the continuous thermal current rating?

The continuous thermal current rating for the DTI is 16 A.

What environmental and climate tests has the DTI passed?

The DTI is compliant with constant climate resistance tests IEC 600-68-2-3 and 2-30.