Overview
- Supports up to three hot-swappable 1600W Power Supply Units for scalable capacity.
- Hosts up to nine transmitter modules for long-distance Class 4 power delivery.
- 1 RU design minimizes rack footprint in headend, MDF, or IDF spaces.
- Integrated management module provides web-based monitoring and control.
- UL 1400-1 compliant for safe, fault-managed high-voltage power distribution.
Specifications
Mounting | Rack Mount Bracket |
Mounting Type | Rack Mount |
Series | FMPS Class 4 Transmitter Chassis |
Size | 1 RU |
Standard | UL-1400-1 (Class 4), IEC 62368-1 and IEC 61508, EN 55032, CFR47 (FCC) Part 15 Class A, EN55035, CE, CAN ICES-3(A)/NMB-3(A), REACH, RoHS Compliant |
Standard | UL-1400-1 (Class 4), IEC 62368-1 and IEC 61508, EN 55032, CFR47 (FCC) Part 15 Class A, EN55035, CE, CAN ICES-3(A)/NMB-3(A), ICES-003, REACH, RoHS Compliant |
Type | Transmitter Chassis |
Width | 17.5 In. |
Package Dimensions (L x W x H) | 22 IN x 17.54 IN x 1.74 IN |
Package Weight (Imperial) | 12.75 lbs |

FRE1UBL
The Panduit Opticom Rack Mount Enclosure ensures network reliability by housing, organizing, managing and protecting up to 96 fiber optic cable terminations, splices, connectors and patch cords. The FRE1U is black, made of steel and features 4 FAP/cassette slots. It can accommodate 4 FAP adapter panels, 4 Opticom cassettes, 8 HD Flex cassettes or FOSM splice modules in a 1 RU footprint. Fibers are easily accessible through front and rear pullout drawers. 1.72"H x 17.60"W x 15.59"D (43.6mm x 447.0mm x 396.0mm)
UINSTL1SH
UPS Installation Service per unit 1-5 kVA and EBP Per Install (Nonbusiness Hours) - OT Labor included, Trip Charge Included
UPM-SEMIANNUAL
Semi-Annual Preventative Maintenance On-Site UPS and Battery Inspection (2 hour standard)
UONSITESH
Standard On-Site service, (48 hour SLA) (2 hour standard) Outside Normal Business Hours plus Sunday and Holiday
FRE2UBL
The Panduit Opticom Rack Mount Enclosure ensures network reliability by housing, organizing, managing and protecting up to 192 fiber optic cable terminations, splices, connectors and patch cords. The FRE2U is black, made of steel and features 8 FAP/cassette slots. It can accommodate 8 FAP adapter panels, 8 Opticom cassettes, 16 HD Flex cassettes or FOSM splice modules in a 2 RU footprint. Fibers are easily accessible through front and rear pullout drawers. 3.46"H x 18.98"W x 15.63"D (88.0mm x 482.0mm x 397.0mm)
UINSTL2SHX
UPS Installation Service per unit single phase 6-10 kVA and EBP, 3 phase 10,15,20kVA and EBP and MBP per install (Nonbusiness Hours) - OT Labor included, Additional hours for units are at the same location, same visit.Frequently Asked Questions
What is the input voltage range for the PXTC1ARA?
The PXTC1ARA accepts input voltage from 115 to 230 VAC, single phase, 50-60 Hz.
What is the operating temperature range for the PXTC1ARA?
The operating temperature range for the PXTC1ARA is 14°F to 122°F (-10°C to 50°C).
Is the PXTC1ARA compliant with safety standards?
Yes, the PXTC1ARA complies with the UL 1400-1 Standard and other safety regulations.
What is the maximum output power of the PXTC1ARA?
The PXTC1ARA can deliver up to 4800 W based on a fully loaded Transmitter Chassis.
What is the maximum distance for power delivery?
The PXTC1ARA can deliver power to remote receivers up to 2 km away.
What type of components are hot-swappable?
The PXTC1ARA supports hot-swappable power supplies and transmitter modules.
What is the efficiency rating of the PXTC1ARA?
The PXTC1ARA has an efficiency rating of over 92% at full load.
What is the isolation rating for the PXTC1ARA?
The isolation rating for the PXTC1ARA is 3kV input to output.
Can the PXTC1ARA be monitored remotely?
Yes, the PXTC1ARA supports remote monitoring and control via a web-based interface.
How much weight can the PXTC1ARA support?
The PXTC1ARA has a base configuration weight of 12.75 lbs. (5.78 kg).
How to Install the PXTC1ARA Panduit Fault Managed Power System (FMPS)
Installation guide for mounting and wiring the PXTC1ARA Panduit Fault Managed Power System (FMPS) Transmitter Chassis and Receivers.
Estimated time: 2h
Tools needed:
Screwdrivers (#2 Phillips, #3 Phillips, Slotted), Wire stripper, Wrenches and/or pliers, Wire cutters, Compression crimp tools, Multimeter
Supplies needed:
Field wiring, Copper patch wire, Receiver grounding wire (6 AWG), Mounting screws, Grounding screw, Panduit Ferrules (16AWG and 18AWG recommended)
- Prepare for Installation
Ensure the site-specific Project Package is available, verifying all part numbers and quantities. Confirm adequate rack space and proper rack grounding. Verify that the correct Class 4 Cable type and size have been pulled between the head end and receiver locations. Ensure the Transmitter Chassis or rack Power Distribution Unit (PDU) is within 50 feet of a properly sized AC mains connection or breaker panel. For Receivers, ensure proper bonded access to Earth-ground is available and the mounting location is within 10 ft. of powered devices.
- Mount the Panduit FMPS Transmitter Chassis
Verify the rack is properly grounded. Mount the Transmitter Chassis using the provided side brackets and rack mounting screws. For 2-post racks, install brackets at position B or C. For 4-post racks or cabinets, use position A with a strain relief bar or shelf for support if needed. Ensure the chassis is securely fastened with the grounding screw.
- Install Power Supply Modules
Insert the Power Supply Module into an empty slot in the back of the Transmitter Chassis until it clicks. Verify engagement by gently pulling the handle. Remove blanking panels before installing additional modules. Ensure fans are not blocked for proper airflow.
- Connect Input Power
Connect the Power Supply Module to the power source using the provided C-19 to C-20 power cord. Ensure PDU outlets or circuit breakers are correctly sized according to the Project Package and local codes. Do not supply power until the complete system is ready.
- Install Transmitter Modules
Slide the Transmitter Module into its designated slot in the Transmitter Chassis until it clicks. Ensure the module is securely seated.
- Wire Transmitter Modules
Connect the field wiring to the Euro-style connectors on the Transmitter Module. Use appropriate Panduit ferrules on both ends of each Class 4 cable pair. Refer to the Project Package for specific cable requirements.
- Mount the Receiver
Secure the Receiver to its mounting location using the provided screws. Ensure proper Earth-ground connection is made. Avoid mounting above heat sources or in direct sunlight. If mounting multiple receivers, ensure at least 4 inches of separation for cooling.
- Wire the Receiver
Connect the Receiver input wiring from the Class 4 cable to the input Euro-style connectors. Connect the Receiver output wiring to the powered devices using the output Euro-style connectors. Ensure the total power demand does not exceed the Receiver's capacity.
- Apply Power and Initial Setup
Once all hardware is installed and wired, apply power to the system. Access the Network Management Card (NMC) web interface via Ethernet to perform initial setup and configuration. Follow the instructions for logging into the NMC for the first time.
Frequently Asked Questions about Panduit
What environmental ratings do Panduit products have?
Panduit products feature comprehensive environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13; CSA Type 1, 2, 3, 4, 4X, 12, and 13; and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. They meet IEC 60529 IP66 rating, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments, with operating temperatures ranging from -40°C to 130°C.
What certifications and standards do Panduit products comply with?
Panduit products are certified to multiple critical industry standards, including UL (Underwriters Laboratories) in the USA and Canada, CSA (Canadian Standard Association), EN IEC 61386, LVD 2006/G5/EC, and ARRA standards. Our products meet rigorous certifications for electrical safety, environmental compliance (WEEE and RoHS), and are designed to perform in extreme temperatures ranging from -55°C to 105°C, making them suitable for demanding industrial environments.
What industries and applications are Panduit products used for?
Panduit products are engineered for critical applications across multiple industries, including commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety-critical environments. Their solutions span electrical infrastructure, wire management, cable ties, power connectors, and safety systems designed to withstand extreme conditions like high vibration, temperature variations, UV exposure, and corrosive agents. Key industries include solar and wind energy, aerospace, heavy trucking, military, commercial transportation, and industrial manufacturing.
What are the main product lines offered by Panduit?
Panduit offers a comprehensive range of electrical infrastructure products including power connectors, cable ties, grounding connectors, identification products, safety solutions, terminals, cable cleats, wiring duct, and cable tie accessories. These products are engineered for industrial environments across multiple sectors like commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety applications.
What are the key features of Panduit products?
Panduit products are engineered for robust performance in heavy-duty industrial environments, featuring a comprehensive range of solutions including cable ties, power connectors, terminals, and identification products. Key features include proven quality performance, subject matter expertise, and customer-driven innovation across multiple industrial sectors such as commercial construction, food and beverage, oil and gas, renewable energy, transportation, and safety applications. The product line is designed to maximize productivity, reliability, and safety while meeting stringent industry standards.
What is Panduit's warranty policy?
Panduit provides a comprehensive Limited Product Warranty that can be fully reviewed on their official website at www.panduit.com/warranty. All Panduit products are subject to the terms, conditions, and limitations of this current warranty. Customers are advised to review the specific warranty details for their particular product, as Panduit requires buyers to determine product suitability for their intended use and assumes all associated risks.
What technical support does Panduit offer?
Panduit offers comprehensive technical support through their dedicated customer service team, accessible via phone at 1-800-777-3300. They provide expert assistance for their full range of industrial infrastructure products, including cable ties, power connectors, terminals, and identification solutions. Customers can also access additional technical resources and product information through their website at www.panduit.com.
What accessories are available for Panduit products?
Panduit offers a wide range of accessories across multiple product lines, including cable ties, cable tie accessories, cable tie tools, identification products, cable cleats, grounding connectors, and VeriSafe accessories like the VeriSafe Network Module and Insulation Piercing Connectors. For a comprehensive view of all available accessories, customers are recommended to visit www.panduit.com for the full product catalog.
How are Panduit products typically installed?
Panduit products are engineered for comprehensive installation across industrial environments, utilizing specialized tools and techniques for precise mounting. Installation methods vary by product line - from cable ties and power connectors to terminals and identification solutions - but all are designed for robust performance in heavy-duty settings. Technicians typically use Panduit's dedicated installation tools and follow manufacturer guidelines available at www.panduit.com to ensure proper fitting and maximum infrastructure reliability.