Authorized Hammond Power Distributor
Hammond Power SK3A0150PB3K - 600V Class Three Phase DOE2016 and NRCan 2019 Compliant Energy Efficient K-Factor Transformer, K-Factor 13, 600D PV, 208Y/120 SV, 150 kVA, Three Phase, Copper Wound, Shielded
More images

Hammond Power SK3A0150PB3K 600V Class Three Phase DOE2016 and NRCan 2019 Compliant Energy Efficient K-Factor…

UPC: 803423126759


Documents & Media
BrochureTechnical BulletinInstallation InstructionsSpecification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The Hammond Power Solutions (HPS) SK3A0150PB3K is a 150 kVA, three-phase, energy-efficient transformer designed for applications with non-linear loads. This unit features a K-Factor 13 rating, crucial for effectively managing harmonic distortion generated by equipment such as variable frequency drives (VFDs) and uninterruptible power supplies (UPS). The transformer is constructed with copper windings for enhanced thermal performance and durability, ensuring a long service life. Its shielded design helps minimize electromagnetic interference (EMI), contributing to cleaner power delivery. This transformer meets stringent energy efficiency standards, complying with DOE2016 and NRCan 2019 regulations, which translates to reduced operational costs and a lower environmental impact. The primary voltage is 208Y Volts and the secondary voltage is 120 Volts. General construction includes a ventilated type, convection air-cooled design for transformers 15 kVA and larger, with three coils and a single 3-leg core. Taps are provided on the primary side to meet or exceed NEMA standards. The transformer is designed, constructed, and rated in accordance with UL, CSA, and NEMA standards. For non-linear load applications, de-rating is performed as per ANSI/IEEE C57.110. Scott-T designs are not acceptable for this product series. Key Specifications: - SKU: SK3A0150PB3K - Manufacturer: Hammond Power Solutions - kVA Rating: 150 kVA - Phase: Three Phase - Primary Voltage: 208Y Volts - Secondary Voltage: 120 Volts - K-Factor: 13 - Winding Material: Copper - Construction: Shielded, Ventilated Type, Convection Air Cooled - Standards: UL, CSA, NEMA - Warranty: 10 Year Limited Warranty (refer to manufacturer's published warranty for details)
  • Specifically designed to handle the harmonics generated by non-linear loads such as computer and telecommunication equipment, drives and other power electronics
  • Meets North American Efficiency Standards: U.S. - DOE 10 CFR Part 431 (DOE 2016); Canada - SOR/2018-201, (NRCan 2019) & ON Reg. 404/12;  Mexico - NMX-J-351-ANCE-2021
  • Standard three phase voltage groups available at k-factor ratings of K4, K9, K13
  • Copper windings for enhanced durability and thermal performance
  • Shielded construction to minimize electromagnetic interference

Specifications

Application
Addresses the overheating problems due to harmonics associated with non-linear loads where drives, personal computers, telecommunications equipment, broadcasting equipment and other similar power electronics are found in high concentrations.
Cable Entry
Side knock-outs standard on all units
Connection Type
SV (Secondary Voltage: 208Y/120V)
Connection Type
208Y/120V
Connection Type
Y/Delta
Connection Type
208Y/120 SV
Cooling
Convection cooled
Depth
29.5 IN
Enclosure
DH4-N3R - Indoor or Outdoor
Enclosure Color
ANSI 61 Grey
Enclosure Type
3R
Frequency
60 Hz
Frequency Rating
60 HZ
Height
44.5 in
Height
1130.3 mm
KVA Rating
150 KVA
Length
29.5 in
Material
Copper
Mounting
Floor Mount
Mounting Method
Wall/Floor
Number Of Phases
3
Number Of Taps
ST-20 compliant
Phase
3PH
Phase
A - 3PH Delta-Wye-N
Poles
3PH
Poles
3
Primary Voltage
600D V
Secondary Voltage
208Y/120V
Series
SK3A
Series
DOE2016 and NRCan 2019 Compliant Energy Efficient K-Factor Transformer
Size
150 kVA
Sound Level dBA
Meets NEMA ST-20 standards
Special Features
Meets current DOE 10 CFR part 431 (2016) and C802.2 efficiencies in an outdoor type enclosure. Smaller kVA sizes have standard input and/or output lugs, knockouts, and wall mounting brackets to save installation costs.
Standard
CSA, UL
Temperature Rating
Typical 30 Average/ 40 Maximum Deg C
Temperature Rise
150
Transformer Rating
150kVA
Type
Transformer > Distribution > DOE 2016 Energy Efficient > K Factor > Three Phase
Voltage Rating
208Y/120 V
Voltage Rating
600V Class
Voltage Rating
600 VAC
Voltage Rating
600D PV / 208Y/120 V
Wall Mounting
No
Warranty
10 year warranty
Weight
1100 lbs
Width
31.5 in
Width
800.1 mm
Winding
CU
Winding
K - CU + Shield
Package Dimensions (L x W x H)
29.5 IN x 31.5 IN x 44.5 IN
Package Dimensions (L x W x H)
74.93 cm x 80.01 cm x 113.03 cm
Package Weight (Imperial)
1100.000 L
Package Weight (Metric)
498.960 kg
A - 15.0 kV bushing

015J0400AN

A - 15.0 kV bushing
O Plus C - 34.5 kV bushing

034Z3000AW

O Plus C - 34.5 kV bushing

Frequently Asked Questions

What is the insulation system temperature rise for HPS Sentinel transformers?

All units utilize a uniform 220°C insulation system with 80°C, 115°C, or 150°C temperature rise options.

What is the standard enclosure type for HPS transformers?

The standard enclosure type for all low voltage HPS transformers is a Type 3R.

What is the BIL rating for HPS Sentinel transformers?

The standard 10kV BIL rating provides increased reliability and protection against critical equipment failure.

What are the available winding materials for HPS Sentinel transformers?

The winding material can be either copper or aluminum conductors.

Are HPS Sentinel transformers compliant with energy efficiency regulations?

Yes, the HPS Sentinel G, K, and H product lines meet the latest energy efficiency standards outlined by DOE and NRCan.

What types of loads are K-Factor transformers designed for?

K-Factor transformers are specifically designed to handle harmonics generated by non-linear loads like computer equipment and power electronics.

What is the warranty period for HPS Sentinel transformers?

The HPS Sentinel transformers come with a 10-year warranty.

Are HPS transformers tested before shipment?

Yes, all HPS transformers are tested at HPS prior to shipment to meet stringent quality criteria.

What is the typical impedance range for HPS Sentinel transformers?

The typical impedance range for these transformers is 1.8% to 7.5%.

What are the mounting options for HPS Sentinel transformers?

Mounting options include floor or wall/ceiling mounting. Built-in wall mounting brackets are standard up to 50kVA.

Frequently Asked Questions about Hammond Power

What certifications and standards do Hammond Power products comply with?

Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.

What is Hammond Power's warranty policy?

Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.

What industries and applications are Hammond Power products used for?

Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.

What are the main product lines offered by Hammond Power?

Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.

What are the key features of Hammond Power products?

Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.

What environmental ratings do Hammond Power products have?

Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.

What technical support does Hammond Power offer?

Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.

What communication protocols do Hammond Power products support?

Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.

What accessories are available for Hammond Power products?

Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.

How are Hammond Power products typically installed?

Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.