Hammond Power FCL1000-5-4 Current Transformer for Active Harmonic Filter 4" I.D split-core AC line current sensor…
UPC: 803423162245
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Split-core AC current sensor for active harmonic filters
- 4-inch inner diameter window size
- Rated for up to 1000A AC line current
- 333mV output signal compatible with various power meters
- High accuracy with exceptional linearity and low phase angle error
- Hinged design for easy installation without power disconnection
- Built-in burden resistor for 0.333 Vac output
- cULus 2808 listed materials for robust construction
- Conforms to IEEE/ANSI C57.13 and IEC 61869-1 standards
- Manufactured in the US
Specifications
Application | Chemical Processing, Data Centers, HVAC, Material Handling, Mining, Oil & Gas, Pulp & Paper, Hospitals, Wastewater |
Frequency Rating | 50-400 Hz |
Height | 6.5 in |
Length | 1.5 IN |
Special Features | I.D split-core AC line current sensor |
Standard | cRUL,CE |
Type | Accessories > Active Harmonic Filter Accessories > AC line current sensor |
Width | 6.5 IN |

FCL1500-5-4
Current Transformer for Active Harmonic Filter 4" I.D split-core AC line current sensor up to 1500A
FCL2000-5-4
Current Transformer for Active Harmonic Filter 4" I.D split-core AC line current sensor up to 2000AFrequently Asked Questions
What is the purpose of the HPS TruWave Active Harmonic Filter?
The AHF is designed to reduce total demand distortion (TDD) and total harmonic distortion (THD(V)) to levels less than 5%, and can correct for linear displacement and balance three-phase current.
What are the performance requirements for harmonic current and voltage distortion?
The AHF limits harmonic current to less than 5% TDD and voltage distortion THD(V) to less than or equal to 5% at the installation point.
What is the operating temperature range for the AHF?
The AHF operates in an ambient temperature range of 0°C to 40°C.
What input voltages can the AHF operate with?
The AHF can operate from input voltages of 480, 240, or 208 VAC, with a tolerance of +12%, -15%.
What is the frequency range for AHF operation?
The AHF is designed to operate with a voltage frequency of 50 or 60 Hz, with a tolerance of ±5 Hz.
Can multiple AHF units be installed in parallel?
Yes, up to six systems can be installed in parallel if the harmonic correction needs exceed the largest single AHF's current rating.
What information is available on the AHF's LCD touch screen display?
The display shows power quality information (voltage, current, THD, harmonics, power factor), operating status, and historical data.
What is the warranty period for the AHF?
The standard factory warranty is at least 18 months from shipment or one year from startup, whichever comes first.
What are the humidity and altitude limitations for AHF operation?
The AHF can operate in humidity up to 95% non-condensing and at altitudes up to 1000 M, with de-rating at higher altitudes.
What is the efficiency of the AHF?
The AHF efficiency is no less than 98% at full load, with heat losses not exceeding 2% of the unit KVAR rating.
Frequently Asked Questions about Hammond Power
What certifications and standards do Hammond Power products comply with?
Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.
What is Hammond Power's warranty policy?
Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.
What industries and applications are Hammond Power products used for?
Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.
What are the main product lines offered by Hammond Power?
Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.
What are the key features of Hammond Power products?
Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.
What environmental ratings do Hammond Power products have?
Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.
What technical support does Hammond Power offer?
Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.
What communication protocols do Hammond Power products support?
Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.
What accessories are available for Hammond Power products?
Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.
How are Hammond Power products typically installed?
Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.