Hammond Power CP1P6G0006FC Passive Harmonic Filters, 5 HorsePower, 600 Volts, 6 Amperes, 60 Hertz, Open Style…
UPC: 803423190415
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- The HPS passive harmonic filter is specifically engineered to mitigate harmonic currents created by non-linear loads.
- It is currently available from 5 to 500 horsepower and it improves power quality by simultaneously reducing harmonics and improving true power factor.
- HPS passive harmonic filters consists of reactors and capacitors in an LCL arrangement designed to reduce a broad range of harmonics associated with variable frequency drives and other three phase rectifiers.
- Typical Power Factor: >95%
- Open style with integrated contactor
Specifications
Ambient Operating Temperature | 0 to 40 Deg C |
Application | For applications requiring IEEE-519 compliant power systems such as chemical processing, data centers, HVAC systems, material handling, hospitals, and wastewater treatment plants |
Cooling | Natural Convection |
Depth | 20.1 IN |
Enclosure | Open Frame |
Enclosure Type | Open Style |
Frequency | 60Hz |
Frequency Rating | 60 HZ |
Height | 22 IN |
Impedance | 6A |
Input Current | 5 A |
Length | 20.1 in |
Mounting | Wall/Ceiling/Floor Mount |
Mounting Style | Floor |
Output Current | 6 A |
Special Features | Delivers superior performance compared to traditional harmonic filters by reducing harmonic current distortion to less than 5% and correcting true power factor to over 95%, enabling users to meet IEEE 519 harmonic requirements. |
Standard | cUL Listed (E61431) |
Voltage | 600 V |
Voltage Rating | 600V |
Warranty | 3 Years |
Weight | 120 L |
Width | 21.5 IN |
Package Dimensions (L x W x H) | 20.1 IN x 21.5 IN x 22 IN |
Package Dimensions (L x W x H) | 510 mm x 546 mm x 559 mm |
Package Weight (Imperial) | 120.000 L |
Package Weight (Metric) | 54.000 kg |

CP1P6G0008FC
Passive Harmonic Filters, 7.5 HorsePower, 600 Volts, 8 Amperes, 60 Hertz, Open Style, Contactor
CP1P6G0049FC
Passive Harmonic Filters, 50 HorsePower, 600 Volts, 49 Amperes, 60 Hertz, Open Style, Contactor
CP1P6G0399CC
Passive Harmonic Filters, 400 HorsePower, 600 Volts, 399 Amperes, 60 Hertz, Enclosure Type 3R, Contactor
CP1K6G0061CC
Passive Harmonic Filters, 50 HorsePower, 480 Volts, 61 Amperes, 60 Hertz, Enclosure Type 3R, Contactor
CP1P6G0287CC
Passive Harmonic Filters, 300 HorsePower, 600 Volts, 287 Amperes, 60 Hertz, Enclosure Type 3R, Contactor
CP1K6G0019FC
Passive Harmonic Filters, 15 HorsePower, 480 Volts, 19 Amperes, 60 Hertz, Open Style, Contactor
CP1K6G0037CC
Passive Harmonic Filters, 30 HorsePower, 480 Volts, 37 Amperes, 60 Hertz, Enclosure Type 3R, ContactorFrequently Asked Questions
What is the primary function of the HPS passive harmonic filter?
The HPS passive harmonic filter improves power quality by reducing harmonics and improving true power factor.
How much harmonic current distortion does the filter typically reduce?
It reduces harmonic current distortion by 80%, typically to 5% or less at full load.
What standard does the HPS passive harmonic filter meet?
It meets IEEE 519 harmonic requirements when operated within designed parameters.
What is the typical power factor achieved with this filter?
The filter corrects true power factor to over 95%.
What are the available voltage ratings for the filter?
The voltage ratings are 480VAC or 600VAC +/-10%.
What is the warranty period for the HPS passive harmonic filter?
The product comes with a 3-year warranty.
What is the efficiency of the filter at full load?
The efficiency is no less than 99% at full load.
What is the overload capability of the filter?
It can handle 150% of its rated current for 1 minute.
What are the available enclosure types for the filter?
The enclosure types are Open or Type 3R.
What types of loads are associated with harmonic distortion?
Harmonic distortion is caused by non-linear loads such as variable frequency drives (VFDs), DC drives, chargers, and rectifiers.
How to Install the HPS Centurion P Passive Harmonic Filter
This guide provides step-by-step instructions for the installation and initial setup of the HPS Centurion P Passive Harmonic Filter, ensuring safe and proper operation.
Estimated time: 1h
Tools needed:
Screwdriver, Wire strippers, Multimeter, Forklift
Supplies needed:
Mounting screws, Terminal connectors, Grounding wire
- Inspect the unit
Immediately after receiving the Passive Harmonic Filter, inspect it for any transit damage and verify correctness against the shipping documents. Report any damage to the carrier and HPS.
- Mount the filter
Using a forklift, carefully lift and position the Passive Harmonic Filter in the designated installation location. Ensure it is level and has at least 6 inches of clearance from walls or obstructions.
- Ground the filter
Connect the designated main grounding location of the Passive Harmonic Filter to a proper ground to ensure safe operation before energizing the unit.
- Make electrical connections
Connect the input terminals A1, B1, and C1 to the phases A, B, and C of the power supply. Connect the output terminals A2, B2, and C2 to the corresponding phases of the load, following local codes.
- Verify connections
Use a multimeter to verify that all electrical connections are secure and that there is no voltage present before proceeding with the next steps.
- Commission the filter
Turn on the power supply and monitor the filter's operation. Use a power quality analyzer to measure total harmonic distortion and power factor before and after connecting the filter to ensure proper functionality.
- Perform initial calibration
Check the output voltage and current to ensure they are within specified limits. Adjust the voltage taps if necessary to maintain proper operation.
Frequently Asked Questions about Hammond Power
What certifications and standards do Hammond Power products comply with?
Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.
What is Hammond Power's warranty policy?
Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.
What industries and applications are Hammond Power products used for?
Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.
What are the main product lines offered by Hammond Power?
Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.
What are the key features of Hammond Power products?
Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.
What environmental ratings do Hammond Power products have?
Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.
What technical support does Hammond Power offer?
Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.
What communication protocols do Hammond Power products support?
Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.
What accessories are available for Hammond Power products?
Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.
How are Hammond Power products typically installed?
Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.