- 1.5 HP, 240VAC (208-240V range), 6.6A output current
- NEMA 1 / UL Type 1 (IP21) enclosure for dust and splash protection
- Advanced control panel with circuit breaker disconnect for safety
- Wall-mounted installation, compact dimensions (28.7 x 7.8 x 11.2 in), 33 lbs
Specifications
Current Rating | 6.6 A |
IP Rating | IP21 |
Mounting Type | Wall-mounted |
Nema Rating | NEMA 1 / UL Type 1 |
Poles | 3 |
Series | ACS550 |
Size | 28.7 in x 7.8 in x 11.2 in |
Voltage Rating | 240 Vac |
Package Dimensions (L x W x H) | 51 IN x 12 IN x 18 IN |
Package Dimensions (L x W x H) | 129.54 cm x 30.48 cm x 45.72 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the voltage and power ranges for ACS550 drives?
The drives support 3-phase input power with ranges of 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the operating frequency range for the motor connection?
The motor connection frequency range is from 0 to 500 Hz.
Does the drive have built-in serial communication?
Yes, the drive has built-in Modbus RTU protocol for serial communication via RS 485.
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104°F).
What protection classes are available for the ACS550 drives?
The drives are available in UL Type 1, 12, or 3R (NEMA 1, 12, or 3R) protection classes.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What product compliance and certifications does the ACS550 have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and meet Low Voltage, Machinery, and EMC Directives.
What types of analog inputs are available?
There are two analog inputs that accept voltage signals (0-10V) or current signals (0-20mA).
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.
How many digital inputs does the drive have?
The drive is equipped with six digital inputs that accept 12V to 24V DC.