ABB Low Voltage Drives ACS550-PC-017A-2 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…
Alternate Item Number: 3AUA0000010229
UPC: 662348041338
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 5 HP motor control capability
- 240 VAC input voltage (208-240V range)
- 16.7 A output current
- NEMA 1 / UL Type 1 (IP21) enclosure for dust and light moisture protection
- Includes circuit breaker disconnect for integrated safety and installation ease
Specifications
Package Dimensions (L x W x H) | 51 IN x 12 IN x 18 IN |
Package Dimensions (L x W x H) | 129.54 cm x 30.48 cm x 45.72 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the voltage and power range for ABB ACS550 standard drives?
The drives support 3-phase input power with ranges of 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the frequency range for the input power?
The input power frequency range for these drives is 48 to 63 Hz.
What is the power factor of the ABB ACS550 drives?
The power factor for these drives is 0.98.
What is the motor connection frequency range?
The motor connection frequency range is from 0 to 500 Hz.
What are the acceleration and deceleration time ranges?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What types of analog inputs are available?
There are two analog inputs that accept voltage signals (0-10V) or current signals (0-20mA).
What is the auxiliary voltage output?
An auxiliary voltage of 24 V DC ±10% is available, with a maximum current of 250 mA.
How many digital inputs are provided?
There are six digital inputs that accept 12V to 24V DC, supporting both PNP and NPN configurations.
What are the specifications for the relay outputs?
There are three relay outputs with a maximum switching voltage of 250V AC/30V DC and a maximum switching current of 6A.
What serial communication protocol is built-in?
The drives have a built-in RS 485 serial communication port supporting the Modbus RTU protocol.