- Designed for 25/28KV outdoor power applications
- Suitable for Concentric Neutral (CN) and Jacketed Concentric Neutral (JCN) cables
- Accommodates cable insulation diameters from .84 to 1.38 inches
- Includes aluminum 2-hole spade connector
- Spade connector supports #2 AWG to 1250 kcmil conductors (2/0 AWG stranded/compressed, 3/0 AWG compact/solid)
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 2/0 STR AWG , 2/0 COMPR AWG , 3/0 SOL AWG , 3/0 COMPT AWG |
Connection Type | Spade Connector |
Connection Type | 2-Hole Spade connector |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84-1.38 inches |
Size | 2/0, 3/0, #2-1250 kcmil |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 25/28 kV |
Voltage Rating | 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2IT15J1-H0250
Ranger2 Termination. Type - Indoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 250 -Stranded or Compressed 2/0 Compact or Solid 3/0.
PCT1-0260-4-18
15kV, Single Piece Terminator (Class 1), includes Universal Aluminum Rod Contact as standard, Power Cable Termination, Conductor Size - 3/0 Stranded/Compressed or 4/0 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches. 18 inch contact
PCT21260-4
25kv, Single Piece Terminator (Class 1), includes Aluminum Rod Contact for Aluminum Conductors only, Power Cable Termination, Conductor Size - 3/0 Stranded/Compressed or 4/0 Compact/Solid, Use for Insulation Diameter Range from .830 to 1.180 inches.
PCT10250-3
15kV, Single Piece Terminator (Class 1), Two-Hole Spade Lug. Power Cable Termination, Conductor Size - 2/0 Stranded/Compressed or 3/0 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches.
PCT10270-3
15kV, Single Piece Terminator (Class 1), Two Hole Spade Lug. Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .640 to 1.070 inches.
PCT20220-4
25kv, Single Piece Terminator (Class 1), includes Universal Aluminum Rod Contact for Aluminum or Copper Conductors, Power Cable Termination, Conductor Size - #2 Stranded/Compressed or #1 Compact/Solid, Use for Insulation Diameter Range from .830 to 1.180 inches.
PCT20270-3
25kv, Single Piece Terminator (Class 1), Two Hole Spade Lug, Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .830 to 1.180 inches.
PCT11250-4 (1)
15kV, Single Piece Terminator (Class 1), includes Aluminum Rod Contact for Aluminum Conductors only, Power Cable Termination, Conductor Size - 2/0 Stranded/Compressed or 3/0 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches.Frequently Asked Questions
What cable sizes does the R2T28 termination support?
It supports cables with insulation diameters from 0.84 in (21.3 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil.
How many sheds does the R2T28 outdoor model have?
The R2T28 outdoor model has six sheds.
How can the R2T28 termination be mounted?
The R2T28 termination can be mounted free hanging or with an optional bracket.
What is the maximum altitude for R2T28 installation?
The maximum altitude for installation of the R2T28 termination is 3300 feet (1005 m).
What power system frequency does the R2T28 support?
The R2T28 termination supports a power system frequency range of 48 to 62 Hz.
What is the ambient temperature range for the R2T28?
The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the creepage distance of the R2T28 termination?
The creepage distance is 22.8 in (579 mm).
What is the lightning impulse withstand voltage?
The lightning impulse withstand voltage (BIL Dry 110 Withstand) is 150 kV Crest.
What is the maximum design voltage to ground for R2T28?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
What is the voltage rating of the R2T28 termination?
The voltage rating for the R2T28 termination is 25/28 kV.
How to Install the R2T28J2 Cable Termination
This guide provides detailed instructions for safely installing the R2T28J2 28kV Ranger 2 Cable Termination on concentric and jacketed concentric neutral cables, covering cable preparation, lug installation, and final sealing.
Estimated time: 2h
Tools needed:
Cable strippers, Crimping tool, Approved solvent applicator, Vinyl tape, Binding wire, Aluminum oxide abrasive (optional, grit 120 or finer)
Supplies needed:
R2T28J2 Termination Kit (Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves), Connector/Lug, Approved solvent, Cable (concentric or jacketed concentric neutral), Grounding materials
- De-energize and Prepare Cable for Termination
DANGER: Ensure all apparatus is de-energized before beginning installation to prevent serious injury. Verify the cable size fits the R2T28J2 kit range (0.84-1.38 inches over insulation, 1.72 inches max over jacket). Train the cable into position, cut to the required length, and allow sufficient neutral wire length for grounding. Prepare the cable according to the dimensions in Table 1, allowing 10.5 inches (270mm) for Dimension A, and additional conductor distance for lug crimping.
- Apply Mastic and Secure Neutral Wires
Carefully wrap one band of sealing mastic around the cable jacket, 1/4 inch (6mm) from the jacket end, using 50% stretch. Position it precisely as it marks the terminator's position; cut flush without overlap. Bend the neutral wires back over the mastic and press them in, then secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, cutting it flush. Finally, wrap two half-lapped layers of vinyl tape around the mastic seal, maintaining the 1/4 inch (6mm) dimension.
- Install Lug/Connector and Clean Cable Insulation
If your lug will not fit through the termination core, slide the termination body onto the cable before installing the lug (do not remove the core yet). Position and crimp the connector or lug according to its directions, ensuring the last 1/4 to 3/8 inch remains uncrimped. Remove any excess oxide inhibitor and sharp crimp flashings. Wipe the cable insulation with an approved solvent, taking care not to touch the semi-con insulation shield. If necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, avoiding the semi-con shield and not reducing the cable insulation diameter.
- Install the Termination Body
Create a track-resistant moisture seal at the base of the terminal lug using gray silicone rubber tape. Apply 1-2 layers, or build up the tape band to match the insulation diameter if the lug barrel is smaller. Liberally coat the edge of the semi-con insulation shield with silicone grease to fill the step. Pull the loose end of the removable core through the top of the termination until it is flush with the bottom. Slide the termination body onto the cable, aligning it with the leading edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise from the loose end, ensuring the termination body remains butted against the mastic seal without pushing or pulling.
- Complete Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, avoiding the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and securely connect them to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.