ABB Installation Products K656LR-G0240-S 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 783786427147
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage class with 600 Amp continuous rating
- Integrated test point for safe diagnostic testing without service interruption
- Aluminum compression lug for 1/0 to 2/0 AWG conductors
- Cable insulation diameter compatibility: 0.760" to 0.950"
- Cold-shrinkable jacket seal for environmental protection
- Fully shielded, dead-front submersible design
- Meets ANSI/IEEE Standard 386 requirements
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection Type | Deadbreak Elbow |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K656LR |
Size | Cable Insulation Diameter 0.760 inch to 0.950 inch |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point. Cold-Shrinkable Jacket Seal Included |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.4000 L |
Package Weight (Metric) | 2.9030 kg |

274AFLR3-B0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Direct Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid/Compact.
K656LR-M0380-SG3
Elbow Connector with Test Point, 600 Amp, Dead Break, 15/25 KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 700/750, Solid 900. 200ECS-G3 Jacket Seal and Grounding Kit Included.
K656LR-M0360-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400. Cold-Shrinkable Jacket Seal Included.
K655LR-P0380-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900. Cold-Shrinkable Jacket Seal Included.
K656LR-M0290
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.
K656LR-N0360-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400. Cold-Shrinkable Jacket Seal Included.
K656LR-H0240
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K656LR handle?
The K656LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for this elbow connector?
The K656LR is designed for insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the continuous current rating for the K656LR?
The K656LR has a continuous current rating of 600 Amps.
What is the momentary current rating for the K656LR?
The K656LR has a momentary current rating of 25kA Sym for 10 Cycles.
What are the BIL ratings for the K656LR?
For 15kV class, the BIL is 95kV. For 28kV class, the BIL is 140kV.
What is the corona extinction rating for the K656LR?
For 15kV class, the corona extinction is 11kV AC @ 3pC sensitivity. For 28kV class, it is 21.5kV AC @ 3pC sensitivity.
What standards does the K656LR meet?
The K656LR meets ANSI/IEEE Standard 386, Latest Revision.
Is a grounding device recommended for certain cable types?
Yes, when used on metallic tape shield or drain wire cable, an ECS cable seal grounding device is highly recommended for safety.
What is the purpose of the test point on the K656LR?
The K656LR features a non-corrosive, capacitive test point for testing purposes.
How to Install K656LR-G0240-S Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K656LR-G0240-S Deadbreak Elbow Connectors, including cable preparation, lug crimping, and connection to high-voltage apparatus.
Estimated time: 2h
Tools needed:
Hotstick, Suitable sensing device, Wire brush, Crimping tool, Utility knife, Torque wrench, Wire strippers
Supplies needed:
K655/675LR or K655/K675LR Deadbreak Elbow Connector kit, No. 14 AWG Copper wire or equivalent, Suitable grounding connector, Lubricant, Silicone lubricant, Tape marker, Waterproofing material, 10TL cable shield adapter (if applicable), 20MA or 21MA grounding device or 600ECS Jacket Cable Seal (if applicable)
- Prepare for Installation and Ensure Safety
Before beginning, ensure all apparatus are de-energized. Inspect all components for damage, proper rating, and compatibility with mating parts. Gather all required tools and supplies, and maintain a clean work area. Read the entire installation instructions thoroughly. DANGER: All apparatus must be de-energized during installation or removal. Failure to follow these instructions will result in serious or fatal injury. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Prepare the Cable
Assemble the cable in its final position, ensuring sufficient slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the specified dimensions (9-3/4, 10-3/4, 12-3/4 inches from the cut end, as shown in the diagrams).
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove any protruding cable insulation by cutting it even with the end of the cable adapter, taking care not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm); if not, redo the assembly. For aluminum conductors, wire brush the conductor immediately before insertion. Fully insert the conductor into the compression lug. Measure the 'Check Dimension' before crimping to ensure it is less than 6-3/8 inches. Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8 inches to 7-1/8 inches (162mm-181mm) after crimping; if not, redo the assembly.
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter, pushing until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect to Mating Apparatus
Remove any protective caps from both the elbow and the mating apparatus. If the mating apparatus is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean. Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected.
- Connect Opposite Mating Part (if applicable)
If connecting an opposite mating part, clean and lubricate its mating surface. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the specific instructions provided with that component.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent ampacity) through the grounding eye and twist to form a small loop, being careful not to damage the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is properly grounded, either through a dedicated grounding device (following its instructions) or an alternate approved method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Secure Cap
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it firmly on the elbow until it snaps into place. To test for voltage, remove the test point cap with a hotstick, peeling it off at an angle. Use a suitable sensing device, designed for capacitive test points, to determine if the cable is energized, following the meter manufacturer's directions. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it securely on the test point. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.