ABB Installation Products K656I-J0250 15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point.…
UPC: 783786391028
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage class with 600A continuous current rating
- Integral capacitive test point for safe voltage verification
- Fully shielded, fully submersible, and direct-buried capable
- Tool-free separable design for quick connection/disconnection
- Modular components support future system expansions
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection Type | Deadbreak Separable Straight Joint |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Poles | 2-Way |
Series | 600 Series |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | Fully Shielded, Fully Submersible, 100 percent Peroxide cured Molded EODM Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Straight Joint |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15-25kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-J0250
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70.
K656CY-K0320
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 550.
K656CY-K0320-SG1
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K656CH-HO240
600 Amp, 15/25kV, Separable H Joint Kit, 4-Way with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
K656CH-H0270
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
K656CY-DP0592440
600 Amp, 15/25KV, Separable Wye Joint package, 3-Way with Test Point, 2 X ( Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. ) and 1 X ( Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. ) Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K656CH-DP0592441
600 Amp, 15/25KV, Separable H Joint package, 4-Way with Test Point, 2 X ( Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. ) and 2 X ( Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. ) Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.Frequently Asked Questions
What is the K656I joint used for?
The K656I separable "I" joint is used to join cables in a disconnectable 2-way joint. It is suitable for small vaults, manholes, and direct-buried applications.
What components are included in a complete joint package?
A complete joint package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
What is the corona extinction voltage for the 25kV class?
For the 25kV voltage class, the corona extinction is 21kV AC at 3pC sensitivity.
What is the momentary current rating for the joint?
The momentary current rating for the K656I joint is 25kA Symmetrical for 10 Cycles for both 15kV and 25kV classes.
Does the K656I joint meet industry standards?
Yes, the K656I joint meets ANSI/IEEE Standard 386, Latest Revision.
What are the key features of the K656I joint?
Key features include a compact, fully shielded, and fully submersible design made of 100% peroxide cured EPDM molded rubber. It also has an integral capacitive test point.
What is the continuous current rating of the joint?
The K656I joint has a continuous current rating of 600 Amps for both 15kV and 25kV voltage classes.
What are the voltage ratings for the 25kV class?
For the 25kV class, the operating voltage is 16.2kV Max Phase-to-Ground and 28kV Max Phase-to-Phase. It has a 140kV BIL impulse withstand.
What are the voltage ratings for the 15kV class?
For the 15kV class, the operating voltage is 8.3kV Max Phase-to-Ground and 14.4kV Max Phase-to-Phase. It has a 95kV BIL impulse withstand.
What is the AC one-minute withstand voltage for the 15kV class?
For the 15kV voltage class, the AC one-minute withstand voltage is 34kV AC.
How to Install K656 Deadbreak Receptacles
This guide provides step-by-step instructions for the safe and proper installation of one leg of K656CY, K656CH, or K656I Deadbreak Receptacles, designed for splicing and tapping solid dielectric cables rated for 600A at 15kV and 25kV.
Estimated time: 1h 30m
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush (for aluminum cable), Assembly tool (650ATY or 600RRT), Rag, Approved safety solvent
Supplies needed:
Receptacle housings, Cable adapters, Center section (I, Wye, or H), Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, No. 14 AWG copper wire (for grounding), Tape (for markers and support)
- Prepare for Installation and Inspect Components
DANGER: Ensure all apparatus is de-energized before starting. Inspect all receptacle components for damage, correct rating, and compatibility with mating parts. Confirm all package contents are complete and undamaged, and check threads for proper fit.
- Clean Cable Jacket and Position Housing
Wipe the outer cable jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely. If using an ECS grounding device, slide its tube onto the cable 38 inches. Then, slide the receptacle housing onto the cable 30 inches (76.2 cm).
- Prepare Cable End (Type-Specific)
Refer to the special cable preparation supplement (Part A for Jacketed Concentric Neutral or Part B for Flat Metallic Tape Shielded) for specific instructions. This involves removing the outer jacket and semi-con shield to specified lengths, creating a tape marker, beveling the insulation, and thoroughly cleaning the insulation. Lubricate the cable and the inside of the cable adapter, then slide the adapter onto the cable until flush with the tape marker.
- Trim Insulation and Assemble Retaining Ring
Remove any protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor measures 4 3/4 to 5 inches (12.1-12.7 cm). Assemble the aluminum retaining ring over the conductor, snug it firmly against the cable adapter, and hand-tighten the socket head screw. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches (11.1-12.1 cm).
- Install and Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor immediately before fully inserting it into the crimp connector. Confirm bolt holes align with the mating part. Crimp the connector following the provided instructions, rotating each crimp 90 or 180 degrees. Verify the distance from the end of the connector to the holding collar is 6 3/4 to 7 inches (17.1-17.8 cm).
- Assemble and Torque Splice Bolts
Assemble the washers and bolt: flat washer against the spade contact, then the Belleville washer (concave side down), followed by the hex-head bolt. Hand tighten. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. Do not move or reposition any part after tightening.
- Lubricate and Position Receptacle Housing
Apply the supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod.
- Engage Receptacle Housing with Assembly Tool
Attach either the 650ATY or 600RRT assembly tool. Use the tool to slowly slide the receptacle housing completely over the splice section. Once fully engaged, remove the nylon venting rod. WARNING: Do not place hands on the threaded rod or guide shaft if using the 600RRT tool.
- Complete Grounding
If an ECS grounding device is used, complete its installation according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.