ABB Installation Products K656CY-K0320 15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable…
UPC: 783786396931
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV rated 3-way deadbreak separable wye joint package
- Test point for safe voltage verification without de-energizing
- Accommodates cable insulation diameter: 1.090" to 1.310"
- Aluminum compression lug for conductors up to 450 kcmil (stranded) or 550 kcmil (solid)
- Part of ABB’s 600 Series for medium-voltage cable systems
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Wye Joint |
Voltage Rating | 15 to 25 kV |
Width | 8.12 in |
Width | 206.248 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 25.5000 L |
Package Weight (Metric) | 11.5670 kg |

K656LR-H0320-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 450 or Compact/Solid 500. Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656CY-K0320-SG1
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K656CH-HO240
600 Amp, 15/25kV, Separable H Joint Kit, 4-Way with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
K656CH-H0270
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
K656CY-DP0592440
600 Amp, 15/25KV, Separable Wye Joint package, 3-Way with Test Point, 2 X ( Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. ) and 1 X ( Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. ) Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K656CH-DP0592441
600 Amp, 15/25KV, Separable H Joint package, 4-Way with Test Point, 2 X ( Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. ) and 2 X ( Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. ) Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K655YSR-G0240
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
K655YSR-K0320-S
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the primary application of the K656CY joint?
The K656CY cable joint is used to join cables in a disconnectable 3-way joint. It is suitable for small vaults, manholes, and direct-buried applications.
What standard does the K656CY joint meet?
The K656CY joint meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating for 25kV?
For the 25kV voltage class, the impulse withstand (BIL) is 140kV.
What is the impulse withstand rating for 15kV?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV.
Are the components of the K656CY reusable?
Yes, the K656CY features reusable components, which can help reduce inventory and other costs.
What type of material is the K656CY molded from?
The K656CY is molded from 100% peroxide cured EPDM rubber.
Can the K656CY be used in direct-buried applications?
Yes, the K656CY can be used in direct-buried applications.
Does the K656CY joint include a test point?
Yes, the K656CY joint includes an integral capacitive test point.
Is the K656CY joint suitable for submersible applications?
Yes, the K656CY joint is fully shielded and fully submersible.
What is the maximum phase-to-ground operating voltage for 25kV?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.
How to Install K656/K676 Series Deadbreak Receptacles
This guide provides detailed instructions for the safe and proper installation of K656/K676 series deadbreak receptacles, including cable preparation, crimping, and final assembly for high-voltage cable splices and taps. Repeat these steps for each cable leg.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush (for aluminum cable), Rag, 650ATY assembly tool OR 600RRT assembly tool, Cable stripping tools, Crimp tool
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Approved safety solvent, Tape (for markers), Conductive copper strip (for flat metallic tape shielded cable), No. 14 AWG copper wire (or equivalent), ECS grounding device (optional)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation. Do not touch or move energized products. Inspect all package contents for completeness and damage. Verify all components fit properly with the cable and mating products.
- Prepare Cable End
Wipe the outer jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth.
- Install Optional Grounding Device and Receptacle Housing
If using an ECS grounding device, slide the tube onto the cable for a distance of 38 inches (96.5 cm). Slide the receptacle housing onto the cable for a distance of 30 inches (76.2 cm).
- Prepare Cable for Termination (Type-Specific)
Follow the appropriate procedure for your cable type. For Jacketed Concentric Neutral Cable: Remove 13-3/4 inches (34.9 cm) of jacket, bend neutral wires back. Remove 10-1/4 inches (26 cm) of semi-con. Apply two turns of tape 1 inch (2.54 cm) from semi-con end. Bevel insulation 1/4 inch (0.64 cm) at 45 degrees. Thoroughly clean insulation with approved safety solvent. Lubricate cable and inside adapter, then slide adapter over cable until flush with tape marker. For Flat Metallic Tape Shielded Cable: Remove 13-3/4 inches (34.9 cm) of outer jacket. Remove 11-1/4 inches (28.6 cm) of tape shield, wrap conductive copper strip, and apply two turns of tape at 11-1/4 inches (28.6 cm). Remove 10-1/4 inches (26 cm) of semi-con. Bevel insulation 1/4 inch (0.64 cm) at 45 degrees. Thoroughly clean insulation with approved safety solvent. Lubricate cable and inside adapter, then slide adapter over cable until flush with tape marker.
- Expose Conductor and Assemble Retaining Ring
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the adapter or conductor. The exposed conductor should measure 4 3/4 to 5 inches (12.1 to 12.7 cm). Assemble the aluminum retaining ring over the conductor, snugging it firmly against the cable adapter. Using the provided hex wrench, hand tighten the socket head screw. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches (11.1 to 12.1 cm).
- Prepare and Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it fully into the crimp connector (which contains inhibitor). Measure the distance from the end of the connector to the holding collar; it must not exceed 7 inches (17.78 cm). Crimp the connectors following the instructions packaged with them, rotating each crimp 90 or 180 degrees. After crimping, re-measure the distance from the end of the connector to the holding collar; it must not exceed 7 inches (17.78 cm).
- Assemble Washers and Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the bolt. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Torque Bolts
Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. (67.8 to 81.3 Nm).
- Lubricate and Position Receptacle Housing
Apply the supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod.
- Complete Housing Assembly with Tool
Attach either the 650ATY or 600RRT assembly tool. Use the tool to slowly slide the receptacle housing over the splice section until fully seated. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place. Remove the venting rod.
- Final Checks and Grounding
Check all cable adapters to ensure they are properly located. Remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings and to ground, making a small loop and twisting tightly without damaging the eye.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.