ABB Installation Products K656DRGN 600 Amp, 15/25kV, 600 Series Deadbreak Insulated Cap with Test Point (without Stud)…
UPC: 783786515363
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 15/25kV deadbreak insulated cap for medium-voltage systems
- Integrated test point for safe voltage diagnostics without insulation compromise
- Molded EPDM rubber construction for insulation, shielding, and water sealing
- Pre-attached grounding wire for safety and fault current management
- Hotstick operation provision for safe installation and maintenance
Specifications
Application | 15/25 kV |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Insulated Cap |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

150-TB-2
15/25kV, T-Splice 6-3/4 inch Long Bail Assembly, Made of Stainless Steel, Used for Assisting Cable to Transformer Connections. Non-Current Carrying. The 150TB2 bailing assembly kit consists of a modified hold down bail for securing Elastimold® tee splice K150T to a K150DP Deadbreak insulating plug. This assembly provides positive hold down force between the tee splice and the insulating plug.
K650BIP-720LOT
15/25kV 600 Series Deadbreak Insulated Plug (with Cap). Material Epoxy, Length 4.5 inch, Widest Diameter 3 inch. - Lot of 720
K656-CBW
15/25kV, 600 Amp Base Aluminum, includes test point, Combo T Bushing Well with Stud, Cable Adapter and Lug Kit.Frequently Asked Questions
What is the K656DRG designed for?
The Elastimold® insulated cap is designed to insulate, shield, and water seal 15/25kV, 600 Amp IEEE Std. 386 bushing interfaces.
What items are included in the K656DRG kit?
Each kit contains one K656DRG insulated cap with test point, one 650SA stud, one 82-08 lubricant, and one IS-1325 installation instruction.
What is the maximum operating voltage for the 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV and phase-to-phase is 28kV.
What is the continuous current rating for the 15kV class?
The continuous current rating for the 15kV voltage class is 200 Amp.
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
How can I order the K656DRG with a factory-assembled stud?
To order the K656DRG with the stud factory-assembled, add "SP" to the part number.
How can I order the K656DRG without a stud?
To order the K656DRG without the stud, add "N" to the part number.
Can the K656DRG be operated with a hotstick?
Yes, the K656DRG includes a provision for hotstick operation.
Does the K656DRG include a grounding wire?
Yes, the K656DRG insulated cap comes with an attached grounding wire.
What material is the K656DRG made from?
The K656DRG insulated cap is made from molded EPDM Rubber.
How to Install the K656DR/K676DR Deadbreak Insulated Cap with Test Point
This guide provides step-by-step instructions for safely installing the K656DR/K676DR Deadbreak Insulated Cap, designed for insulating, shielding, and watersealing 15kV and 28kV class deadbreak bushing interfaces.
Estimated time: 30m
Tools needed:
Hotstick, High impedance testing device
Supplies needed:
K656DR/K676DR Insulated Cap, Lubricant, Stud (if applicable), No. 8 Copper Grounding Wire, Grounding wire connector
- Prepare for Installation and Ensure Safety
DANGER: All apparatus must be de-energized during installation or removal. Failure to follow these instructions will result in damage to the product and serious or fatal injury. Before beginning, ensure all apparatus is de-energized. Inspect all parts for damage, correct rating, and compatibility with mating components. Verify the package contents are complete and undamaged. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Have all required tools ready and maintain cleanliness throughout the procedure.
- Prepare Grounding Wire and Stud
Connect the free end of a No. 8 copper grounding wire to the system ground using a utility-specified connector. Ensure the grounding wire length is sufficient to reach the grounding eye of the insulated cap when installed. If the bushing lacks a stud, hand assemble the supplied stud into the insulated cap. If the bushing already has a stud, discard the supplied stud.
- Clean and Lubricate Interfaces
For new installations where the bushing is confirmed de-energized, thoroughly wipe both the bushing interface and the insulated cap interface to remove all contaminants. Lubricate these surfaces with the supplied lubricant or an Elastimold approved lubricant. For circuits previously energized, clean and lubricate only the interface of the insulated cap.
- Install the Insulated Cap
During this step, the grounding wire will be wrapped loosely around the center of the insulated cap body; a second hotstick will be needed to manage its tension and position. Attach the first hotstick tool to the insulated cap's pulling ring. Push the receptacle onto the bushing interface as far as it will go. Using the second hotstick, engage the grounding wire and apply slight tension. With the first hotstick, while pushing against the bushing interface, twist clockwise until the threads between the bushing and insulated cap engage. Continue turning without pushing until resistance is felt. DO NOT OVERTIGHTEN.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.