Contact for Pricing
Overview
- 600 Amp current rating
- 15/25kV voltage class
- 600 Series Deadbreak Direct Test Elbow
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for 3/0 AWG to 4/0 AWG conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 600 Series |
Size | Cable Insulation Diameter 0.640 inch to 0.820 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators. Direct conductor test point equipped elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Direct Test Elbow with Test Point |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.7100 L |
Package Weight (Metric) | 3.0440 kg |

K656LR-N0410-CS871
25kV, 600 Amp, Deadbreak, Elbow with Test Point, (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter), No Sealing Kit, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Any Customer Specific Modifications CS871 - CSA Die Compatibility.
M655YSR-K0240
600 Amp, 35kV, Separable Cable Joint, Straight Receptacle. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
K675SR-M2420
900 Amp, 15/25kV, 600 Series Straight Receptacle with Cable Adapter, Lug and Retaining Ring, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size kcmil Compacted Solid 1250.
2674-35
Submersible Control Cabinet, 15kv, 4 Ways, Way1- MVS3 with Motor and VS, Way2- MVI3, Way3- MVI3, Way4- MVS3 with Motor and VS, Spanish Labels and Instructions, Submersible Control with Two Source Ways Supported with SEL751A Control A) 4-Way Submersible Control (Setup for V.S. and Motors on 2 Ways Only). B) 40AH Submersible Battery. C) Submersible Handheld. D) 19-pin Handheld Cable 30 Foot. Includes Submersible Control Assembly with Spanish label. Flat Washers, Elastic Stop Nut, NamePlates and Labels, Fittings, Connector Ring DHPE, Cable Clamps, #10-32 Screw with Ext. Tooth Lockwasher, #10-32 SS Elastic Stop Nut, Cap and Chain Assemblies, Phillips Pan Head Machine Screws, Elastic Stop Nuts, 30 Inch Submersible Wire Harness, Settings Format, 18 AWG Wires - Blue, Red, Black, White, Green and Brown. Female Terminal 16-14 AWG, Insulated Ring Terminal 1/4. Ferrules 18 AWG Single and Twin, 7 Foot Ethernet Cable.
M650SL
15-25 kV, 600 Amps, Sacrificial Limb, Spiking Aid Appendage. Replaceable Cap that Provides a Convenient Place to Spike the Bus to Assure that it is De-Energized. This also Assures that all Cables Connected to the Bus are De-Energized. Meets ANSI/IEEE Standard 386. 5.06 inches Long X 1.96 inch Diameter. Includes IS-1296 Instruction Sheet.
J4-2226-15-L
4 Point Junction, with three 200 Amp Bushing Well Interfaces and one 600 Amp Bushing interface, 15kV, Left Parking Stand.Frequently Asked Questions
What is the maximum voltage rating for this deadbreak elbow?
The ABB K656DLR-F0260 deadbreak elbow has a voltage rating of 15/25kV.
What conductor sizes are compatible with this elbow?
This elbow is compatible with compressed stranded 3/0 AWG, compacted solid 4/0 AWG, and compact 95 mm² conductors.
What is the range of cable insulation diameters supported?
The cable insulation diameter range for this elbow is 0.640 inch to 0.820 inch.
What type of lug is included with this deadbreak elbow?
An aluminum compression lug is included with the K656DLR-F0260 deadbreak elbow.
Does this elbow come with a test point?
Yes, the K656DLR-F0260 is a deadbreak direct test elbow and includes a test point.
How to Install K656/K676DLR Direct Test Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K656/K676DLR and 656/676DLR Direct Test Elbow Connectors, including cable preparation, component assembly, and grounding procedures for 15kV and 25kV class systems.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), High voltage insulated hot stick, Appropriate HV meters with T&B Elastimold series 200TC-1, 200TC-2, 200TC-4 or approved adapters, Vinyl plastic tape (if using flat metallic tape shield), Suitable connector for grounding wire, Torque wrench
Supplies needed:
Elbow connector (K656DLR or K676DLR), Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant (supplied with kit), Stud Prepack (supplied with kit), No. 14 AWG copper wire (or equivalent) for grounding, Tape marker, Tape retainer (if using fabric tape shield), Waterproofing material (for cable jacket, recommended)
- De-energize and Position Cable
Before starting, ensure all apparatus is de-energized. Position the cable in its final assembled location, allowing enough slack to remove elbows. If applicable, unwind concentric neutral wires. Cut the cable 1 3/4 inches (45mm) from the centerline of the mating product. DANGER: All apparatus must be de-energized during installation or removal. Failure to follow this instruction will result in serious or fatal injury.
- Prepare the Cable for Connection
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires. Refer to specific instructions for your cable type (e.g., outer jacket, shield wires, metallic tape, fabric tape, corrugated shield, Unishield, lead sheath, or semi-con shield) to remove the outer jacket and shield to the specified dimensions. Do not cut or nick the cable insulation.
- Install Cable Adapter and Compression Lug
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove protruding cable insulation, cutting it even with the end of the cable adapter, ensuring the exposed conductor is between 4 3/8 and 4 11/16 inches (111mm to 119mm). Fully insert the conductor into the compression lug (wire brush aluminum conductors immediately before insertion). Crimp the compression lug according to its supplied instructions, then wipe off any excess inhibitor. Verify the final lug-to-adapter distance is between 6 1/2 to 7 1/4 inches (165mm to 184mm).
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. Remove the tape marker.
- Connect Elbow to Mating Products
Remove protective caps from both the elbow and the mating part. If the mating part lacks a stud, hand tighten the supplied threaded stud into it. Clean and lubricate both the elbow and the mating part. Push the elbow onto the mating part, aligning the compression lug hole with the stud. For the opposite end, clean and lubricate the mating part, insert it into the elbow, engage threads, hand tighten, and then torque according to the mating part's instructions. If an insulating plug is used, clean and lubricate the voltage detection cap's inner surface, then place it on the elbow and push until it snaps into place. DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED.
- Ground the Cable Shield
Insert one end of a minimum No. 14 AWG copper wire through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with any grounding device, or via an alternate method if no device is used. It is recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Direct Voltage Test (Optional)
If performing a direct voltage test, use only the appropriate direct voltage test port adapter and meter (e.g., 200TC-1, 200TC-2, 200TC-4 adapters with compatible meters). Read and understand the separate operating instructions for the specific test adapter and meter before proceeding. The cap on the direct access port should be installed at all other times. DANGER: Insertion of any object, other than the appropriate direct voltage test port adapter and meter, into the direct test port or in close proximity to it can result in electric shock which will cause serious or fatal injury.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.