Authorized ABB Distributor (Installation Products)
ABB - Installation Products K656CYL0300L0360L036 - 600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.

ABB Installation Products K656CYL0300L0360L036 600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, Cable Insulation…

UPC: 783786656707


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

This ABB Installation Products Separable Wye Joint Package, SKU K656CYL0300L0360L036, is designed for 600 Amp, 15/25KV applications. It features a 3-way configuration with an integrated test point for enhanced diagnostics and maintenance. The package accommodates cable insulation diameters ranging from 1.180 inches to 1.465 inches. It includes aluminum compression lugs for secure conductor connections. The system supports various conductor sizes, including compressed stranded AWG/kcmil of 350 (compacted solid 400 / mm² compact 185) and also 650 (compacted solid 750 / mm² compact 400). This product is suitable for medium voltage power distribution systems where reliable and safe connections are paramount. The separable design facilitates ease of installation and disconnection. The test point allows for voltage testing without de-energizing the entire circuit, improving operational efficiency and safety. ABB's commitment to quality ensures dependable performance in electrical infrastructure projects.
  • 600 Amp, 15/25KV rated for medium voltage applications
  • 3-Way Separable Wye Joint configuration
  • Integrated test point for safe voltage testing
  • Accommodates cable insulation diameters from 1.180" to 1.465"
  • Includes aluminum compression lugs for secure connections

Specifications

Amperage Rating
600 A
Application
Compact Design is suitable for small vaults and manholes
Color
Black
Conductor Range
350 kcmil , 400 kcmil , 650 kcmil , 750 to 800 kcmil
Connection
Compression
Connection Type
Separable Wye Joint
Current Rating
600 A
Environmental Conditions
All Weather Conditions
Insulation
True
Length
37.27 in
Length
946.658 mm
Material
Aluminum
Material
Housing - EPDM-Rubber
Poles
3-Way
Series
K656CYL
Size
Cable Insulation Diameter 1.180-1.465 inches
Special Features
Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Separable Wye Joint
Voltage Rating
15 to 25 kV
Voltage Rating
15/25kV
Width
8.12 in
Width
206.248 mm
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
25.5000 L
Package Weight (Metric)
11.5670 kg
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.

K655LR-J0330

600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 300 or Solid 350 or mmSquared 150

K655YSR-H0290

600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 300 or Solid 350 or mmSquared 150
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 450 kcmil or Compacted Solid 500/550 kcmil

K655YSR-L0320

600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 450 kcmil or Compacted Solid 500/550 kcmil
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 or Compacted Solid 800/900.

K656CH-M0380

600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 or Compacted Solid 800/900.
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Solid 500/550. 200ECS-G2 Jacket Seal and Grounding Kit Included.

K655YSR-K0320-SG2

600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Solid 500/550. 200ECS-G2 Jacket Seal and Grounding Kit Included.
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed/Stranded 700/750 kcmil or Compacted/Solid 900 kcmil.

K656CH-L0380

600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed/Stranded 700/750 kcmil or Compacted/Solid 900 kcmil.
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 250 or Solid 300.

K655YSR-G0280

600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 250 or Solid 300.

Frequently Asked Questions

What is the primary application of the K656CY-HP joint?

The K656CY-HP cable joint is used to join cables in a disconnectable 3-way joint. It is suitable for small vaults and manholes due to its compact size.

What is the impulse withstand rating for the 25kV class?

For the 25kV voltage class, the impulse withstand (BIL) is 140kV (1.2 x 50 microsecond wave).

How do I order the basic wye joint housing?

To order the basic wye joint housing only, specify K656CY-HP.

What components are included in the K656CY-HP kit?

Each K656CY-HP kit includes a 3-Way Bus Bar, Lubricant 82-08, Installation Instruction IS-0388, and three Straight receptacles K655YSR.

What material is the K656CY-HP made from?

The K656CY-HP is made from 100% peroxide cured EPDM molded rubber.

Does the K656CY-HP include a test point?

Yes, the K656CY-HP separable wye joint includes an integral capacitive test point.

Is the K656CY-HP joint submersible?

Yes, the K656CY-HP separable wye joint is fully shielded and fully submersible, made from 100% peroxide cured EPDM molded rubber.

What is the momentary and fault close rating?

The momentary and fault close rating for the K656CY-HP is 25kA Symmetrical for 10 Cycles.

What is the impulse withstand rating for the 15kV class?

For the 15kV voltage class, the impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).

What is the continuous current rating for the K656CY-HP?

The K656CY-HP separable wye joint has a continuous current rating of 600 Amps for both 15kV and 25kV voltage classes.

How to Install K656/K676 Series Deadbreak Receptacles

This guide provides step-by-step instructions for the safe and proper installation of K656/K676 series deadbreak receptacles, including cable preparation, crimping, and final assembly for high voltage electrical systems.

Estimated time: 1h 30m

Tools needed:

Hex wrench, Torque wrench with 15/16” socket, 650ATY assembly tool OR 600RRT assembly tool, Wire brush (for aluminum cable), Rag, Approved safety solvent, Wire strippers/Cable knife

Supplies needed:

K656/K676 Series Deadbreak Receptacle kit (includes housings, adapters, center sections, collars, bolts, crimp connectors, washers, venting rod, lubricant), Solid dielectric type cable (concentric neutral or flat metallic tape shielded), ECS grounding device (optional), No. 14 AWG copper wire (or equivalent), Electrical tape, Inhibitor (pre-filled in crimp connector for aluminum cable)

  1. Perform Initial Safety Checks and Component Inspection

    Before beginning, ensure all apparatus is de-energized. Inspect all components from the K656/K676 series deadbreak receptacle kit for completeness, damage, and compatibility with your cable and mating parts. Read the entire installation instructions and have all required tools ready. Maintain cleanliness throughout the procedure. This product must be installed by competent personnel trained in high voltage electrical equipment safety practices.

  2. Prepare the Cable End and Slide Housing

    Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth. If using an ECS grounding device, slide its tube onto the cable for a distance of 38 inches (96.5 cm). Then, slide the receptacle housing onto the cable for a distance of 30 inches (76.2 cm).

  3. Perform Cable Specific Preparation

    Refer to the special cable preparation supplement for your specific cable type. For Jacketed Concentric Neutral Cable (Part A): From the cable end, remove 13-3/4 inches (34.9 cm) of the jacket, bending neutral wires back. Remove 10-1/4 inches (26 cm) of semi-con shield. Wrap two turns of tape 1 inch (2.5 cm) from the semi-con shield end. Bevel the insulation end at a 45-degree angle for approximately 1/4 inch (0.6 cm). Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end towards the outer jacket. For Flat Metallic Tape Shielded Cable with Semi-con Shield (Part B): From the cable end, remove 13-3/4 inches (34.9 cm) of the outer jacket. Remove 11-1/4 inches (28.6 cm) of the tape shield, wrapping a conductive copper strip around the edge and securing it with two turns of tape. Remove 10-1/4 inches (26 cm) of the semi-con shield. Bevel the insulation end at a 45-degree angle for approximately 1/4 inch (0.6 cm). Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end towards the outer jacket.

  4. Install Cable Adapter and Retaining Ring

    Apply the supplied lubricant sparingly along the prepared cable and generously to the inside of the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until its end is flush with the tape marker (or the appropriate position as per your cable preparation). Remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring the exposed conductor measures 4-3/4 to 5 inches (12.1 to 12.7 cm). Assemble the aluminum retaining ring over the conductor, snugging it firmly against the cable adapter. Hand-tighten the socket head screw using the provided hex wrench. Confirm the exposed conductor now measures 4-3/8 to 4-3/4 inches (11.1 to 12.1 cm); if not, redo the assembly.

  5. Install and Crimp the Connector

    Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it fully into the crimp connector (which contains inhibitor). Confirm the distance from the end of the connector to the holding collar is not over 7 inches (17.78 cm). Ensure bolt holes in the crimp connectors are positioned to align with the mating part. Crimp the connector following its specific instructions, rotating each crimp 90 or 180 degrees. After crimping, re-measure the distance from the end of the connector to the holding collar; it must not exceed 7 inches (17.78 cm).

  6. Assemble Washers and Torque Bolt

    Assemble the washers and hex-head bolt in the following order: flat washer against the spade contact, then the Belleville washer with its concave side down, followed by the hex-head bolt. Hand tighten the bolt. Using a torque wrench with a 15/16” socket, tighten all bolts to 50 to 60 ft. lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.

  7. Lubricate and Position Receptacle Housing

    Generously apply the supplied or ELASTIMOLD approved lubricant to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).

  8. Complete Receptacle Housing Assembly

    Use an appropriate assembly tool (650ATY or 600RRT) to slide the receptacle housing completely over the splice section. If using 650ATY, attach the tool with the 'U' shaped yoke over the splice section and the 'C' shaped yoke over the receptacle housing, then slowly raise the handle. If using 600RRT, attach the tool and turn the hex nut on either side to slide the housing. WARNING: Do not place hands on the threaded rod or guide shaft with the tool in place. Once the housing is in place, remove the venting rod. Repeat steps 7 and 8 for any remaining cables.

  9. Perform Final Checks and Grounding

    Check all cable adapters to ensure they are properly located and remove any vinyl tape markers. Complete the installation of any ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damaging the eye. Connect this wire to the main ground.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.