ABB - Installation Products K655YSR-M2400 - 600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.

ABB Installation Products K655YSR-M2400 600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter…

UPC: 783786507672


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 600 Series Deadbreak Straight Receptacle, SKU K655YSR-M2400, is engineered for reliable power distribution in medium voltage applications. This receptacle is rated for 600 Amps and operates within a voltage range of 15-25 kV, making it suitable for robust electrical infrastructure. It features a deadbreak straight connection type, ensuring a secure and safe termination point for underground distribution systems. The design accommodates cable insulation diameters ranging from 1.370 inches to 1.630 inches. For conductor connections, it utilizes a copper compression lug, providing a durable and low-resistance electrical interface. The receptacle supports a variety of conductor sizes, including AWG or kcmil, with specific capacities for compressed stranded (900 kcmil), compacted solid (1000 kcmil), and mm² compact (500 mm²) conductors. This versatility allows for integration with different cable types and sizes commonly found in utility and industrial power networks. Manufactured by ABB - Installation Products, this 600 Series receptacle is designed for straightforward installation and dependable service life. Its construction prioritizes electrical integrity and safety in demanding power environments. The UNSPSC code for this product is 39121421, categorizing it within electrical connectors and accessories.
  • 600 Amp current rating
  • 15-25 kV voltage rating
  • Deadbreak straight receptacle connection
  • Copper compression lug for conductor connection
  • Accommodates cable insulation diameter from 1.370" to 1.630"

Specifications

Amperage Rating
600 A
Application
These Connectors allow a straight cable connection on Switchgear or Electrical Apparatus equipped with 600 Amp Bushings
Color
Black
Conductor Range
900 kcmil , 1000 kcmil
Connection
Compression
Environmental Conditions
All Weather Conditions
Insulation
True
Length
16.98 in
Length
431.292 mm
Material
Housing - EPDM-Rubber
Special Features
Fully Shielded, Fully Submersible, Can be easily Connected or Disconnected in a De-Energized State
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Straight Receptacle
Voltage Rating
15 to 25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.

755LR-N0400

600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.
600 Amp, 15/25kV, Separable H Joint Kit, 4-Way with Test Point. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.

K656CH-K0320

600 Amp, 15/25kV, Separable H Joint Kit, 4-Way with Test Point. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle with Test Point, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.

K152SR-B2240

200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle with Test Point, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
25kv Compact H Joint Kit with two Cable Insulation Diameters size M - 1.370 to 1.630 with Aluminum Lugs for 750 kcmil, and two Cable Insulation Diameters size L - 1.180 to 1.465 with Aluminum Lugs for 500 kcmil, includes Cold-Shrinkable Seal with Copper Rod and Crimp Connector.

K656CH-DP0593493

25kv Compact H Joint Kit with two Cable Insulation Diameters size M - 1.370 to 1.630 with Aluminum Lugs for 750 kcmil, and two Cable Insulation Diameters size L - 1.180 to 1.465 with Aluminum Lugs for 500 kcmil, includes Cold-Shrinkable Seal with Copper Rod and Crimp Connector.
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.

K656CY-M0360-SG1

15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
900 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Seal with Copper Rod and Constant Force Spring Included.

K675SR-K2360-SG2

900 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Seal with Copper Rod and Constant Force Spring Included.
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.

K655YSR-G0230

600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.

K656CY-K0270

15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.

Frequently Asked Questions

What is the K655YSR's overall voltage and current rating?

The K655YSR is a fully rated 15/25kV, 600 Amp Deadbreak Receptacle.

What is the momentary current rating?

The momentary current rating is 25kA symmetrical for 10 cycles.

What is the continuous current rating for 25kV?

The continuous current rating for the 25kV voltage class is 600 Amps.

What are the 25kV operating voltage limits?

For the 25kV class, the maximum operating voltage is 16.2kV phase-to-ground and 28kV phase-to-phase.

What is the continuous current rating for 15kV?

The continuous current rating for the 15kV voltage class is 600 Amps.

What are the 15kV operating voltage limits?

For the 15kV class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase.

What conductor sizes and insulation diameters are compatible?

The K655YSR supports #2 AWG to 1250 kcmil aluminum and copper conductors. It is compatible with insulation diameters from 0.640 in to 1.935 in.

What type of cable connection does the K655YSR provide?

It allows a straight cable connection on switchgear or electrical apparatus equipped with 600 Amp bushings.

What is the K655YSR's primary application?

The K655YSR provides a fully shielded, submersible cable connection on 15/25kV high-voltage "I", "Y", or "H" Bus.

What is the K655YSR's overall voltage and current rating?

The K655YSR is a fully rated 15/25kV, 600 Amp Deadbreak Receptacle.

How to Install K656/K676 Series Deadbreak Receptacles

This guide provides detailed instructions for installing K656 and K676 series deadbreak receptacles, including cable preparation, crimping, and final assembly for splicing and tapping solid dielectric cables. These instructions cover the installation of one leg; repeat for additional cables as needed.

Estimated time: 1h 30m

Tools needed:

Hex wrench (supplied), Torque wrench with 15/16" socket, Wire brush (for aluminum cable), Rags, Approved safety solvent, Cable stripping tools, Crimp tool (refer to connector instructions), 650ATY assembly tool OR 600RRT assembly tool

Supplies needed:

K656/K676 Deadbreak Receptacle Kit (housings, adapters, center sections, collars, bolts, crimp connectors, washers, venting rod), ELASTIMOLD approved lubricant (or supplied lubricant), No. 14 AWG copper wire (or equivalent) for grounding, Tape (for markers), Conductive copper strip (for flat metallic tape shielded cable, if applicable), ECS grounding device (if used)

  1. De-energize Apparatus and Inspect Components

    DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Failure to follow instructions will result in serious injury. Inspect all parts for damage, proper rating, and compatibility with mating parts. Ensure all required tools and supplies are at hand and maintain cleanliness.

  2. Clean and Square Cable End

    Wipe the outer jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth.

  3. Slide ECS Grounding Device Tube (Optional)

    If an ECS grounding device is being used, slide the tube onto the cable a distance of 38 inches (96.5 cm) from the end.

  4. Slide Receptacle Housing

    Slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm) from the end.

  5. Prepare Jacketed Concentric Neutral Cable (Part A)

    Measure 13-3/4 inches (34.9 cm) from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage neutral wires. Bend neutral wires back. Measure 10-1/4 inches (26 cm) from the cable end and remove the semi-con shield with a straight, smooth, squared cut, avoiding nicks to the insulation. At 1 inch (2.54 cm) from the end of the semi-con shield, wrap two turns of tape as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.64 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.

  6. Remove Protruding Cable Insulation

    Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor should be 4 3/4 inches to 5 inches (12.07 cm to 12.7 cm). If not, redo the assembly.

  7. Assemble Aluminum Retaining Ring

    Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4 3/8 inches to 4 3/4 inches (11.11 cm to 12.07 cm). If not, redo the assembly.

  8. Prepare Crimp Connector

    Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar; if it is over 7 inches (17.78 cm), do not proceed and recheck all previous work.

  9. Repeat for Additional Cables

    Repeat Steps 5 through 8 for all remaining cables to be joined in the splice.

  10. Confirm Component Alignment Before Crimping

    Prior to crimping, confirm that all components are positioned correctly and that the bolt holes in the crimp connectors are properly aligned with the bolt holes of the mating part.

  11. Crimp Connectors

    Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if it is over 7 inches (17.78 cm), do not proceed and redo all previous work.

  12. Assemble Washers and Bolt

    Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. Clean and lubricate the bolt and washer assembly area.

  13. Torque Tighten Bolts

    Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.

  14. Apply Lubricant for Assembly

    Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section as shown in the diagram, and the inside mating surface of the receptacle housing.

  15. Slide Receptacle Housing and Insert Venting Rod

    Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).

  16. Use Assembly Tool to Complete Housing Slide

    Attach the appropriate assembly tool (650ATY or 600RRT). If using the 650ATY, ensure the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing, then slowly raise the handle to slide the housing over the splice section. If using the 600RRT, slide the housing over the interface by turning the hex nut on either side of the tool. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place. Remove the venting rod once the housing is fully seated.

  17. Repeat Housing Assembly for Remaining Cables

    Repeat Steps 15 and 16 for all remaining cables to complete the housing assembly for the entire splice.

  18. Verify Cable Adapters and Remove Markers

    Check all cable adapters to ensure they are located properly and remove all vinyl tape markers.

  19. Complete Grounding

    If an ECS grounding device is used, complete its installation according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect to ground.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.