ABB Installation Products K655SR-K0270 600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and…
UPC: 075114382007
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetrical momentary withstand
- Fully shielded, submersible molded rubber housing for environmental protection
- Accommodates cable insulation diameters from 1.090" to 1.310"
- Compatible with compressed stranded 4/0 AWG, compacted solid 250 kcmil, or 125 mm² compact conductors
- Meets ANSI/IEEE Standard 386 for 15/25kV applications with 95kV/140kV BIL ratings
Specifications
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 16.98 in |
Length | 431.292 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | 1.090"-1.310" |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Receptacle |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-G-0270-SG3
15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
252LRJS-C5250
25 kV, 200 Amp, Deadbreak, Elbow Connector with Test Point, with Jacket Seal, Cable Insulation Diameter - .805-1.060 inch. Bi-Metal Lug, Conductor Size 250 - 2/0 Stranded/Compressed or 3/0 Compact/Solid. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide.
K655SR-L-0330-SG3
600 Amp, Straight Receptacle with Cable Adapter, Lug and Retaining Ring, DeadBreak, 15/25 KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-J0260-S
35kV, 600 Amps, Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG, Compressed/Stranded 3/0 or Compacted/Solid 4/0 or 95 mm2. Cold-Shrinkable Jacket Seal Included.
756LR-L0310-S
35kV, 600 Amps, Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 400 kcmil or Compacted/Solid 450 kcmil or Compact 240 mm2. Cold-Shrinkable Jacket Seal Included.
656LRTP-M0380-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit with Insulated Cap. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed/Stranded 700/750 kcmil or Compact/Solid 900. Includes Elbow Housing, Reducing Tap Plug, Cable Size Adapter, Compression Lug, Lubricant, Instruction Sheet and Crimp Chart.
K465LR-J0390
15/25kV, 630 Amps, Deadbreak Elbow without Test Point. Cable Insulation Diameter 0.980 inch to 1.180 inch (24.892-29.972mm). Aluminum Compression Lug, Conductor Size 800 Stranded/Compressed or 500 mm2. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Tube Lubricant, Cable Adapter, Installation Instructions and Crimp Chart. Exceeds ANSI/IEEE Standard 386 Latest Revision.Frequently Asked Questions
Can the K655SR be connected or disconnected energized?
No, the K655SR can only be easily connected or disconnected when it is in a de-energized state.
What is the maximum operating voltage for 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and phase-to-phase is 28kV.
What is the momentary current rating?
The momentary current rating for both 15kV and 28kV voltage classes is 25kA Symmetrical for 10 cycles.
What is the continuous current rating?
The continuous current rating for both 15kV and 28kV voltage classes is 600 Amps.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and phase-to-phase is 14.4kV.
What cable insulation diameters does K655SR support?
The K655SR supports cable insulation diameters ranging from .640 in to 1.935 in.
What conductor types and sizes are compatible?
It is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
What is the K655SR designed for?
The K655SR provides a fully shielded, submersible cable connection on 15/25kV high-voltage apparatus bushings, allowing straight cable connections on switchgear.
What is the maximum operating voltage for 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and phase-to-phase is 28kV.
What conductor types and sizes are compatible?
It is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
How to Install the K655SR/M655SR Deadbreak Straight Receptacle
This guide provides step-by-step instructions for installing the K655SR or M655SR Deadbreak Straight Receptacle, covering apparatus bushing preparation, cable management, and component connection for a secure high-voltage interface. DANGER: All apparatus must be de-energized during installation by competent personnel trained in high voltage safety.
Estimated time: 2h
Tools needed:
5/8-11 tap, Hex wrench, Wire brush, Torque wrench, 15/16 socket, Crimping tool, Wire strippers
Supplies needed:
Receptacle housing, Bushing adapter, Cable adapter, Aluminum holding collar, Hex head bolt, Crimp connector, Belleville washer, Flat washer, Nylon venting rod, Lubricants, Brass bolt, Bushing converter contact, Loctite, Tape marker, No. 14 AWG copper wire, Suitable connector, Hose clamp (for 35kV only)
- Prepare Apparatus Bushing
If a stud is present in the apparatus bushing, remove it and re-tap the hole using a 5/8-11 tap. Clean and lubricate the apparatus bushing and bushing converter interface. Assemble the bushing converter onto the apparatus bushing. Apply 3-4 drops of Loctite to the threads of the brass bolt. Assemble the contact adapter to the apparatus bushing, with the bolt hole facing out, using a 5/8” brass bolt. Torque to 60 ft.-lbs.
- Prepare Cable End
Train the cable end and straighten it into its final position. Cut the cable squarely to ensure maximum available length for crimp growth.
- Manage Concentric Neutral Wires (If Applicable)
Unwrap the concentric neutral wires (if applicable) a distance of 30” (76cm). Do not cut them. Bend and fold them back out of the way.
- Clean Outer Cable Jacket
Wipe the outer jacket clean for a distance of 38” (96.5cm) or up to the concentric neutral wires.
- Slide Receptacle Housing
Slide the receptacle housing onto the cable a distance of 30” (76cm).
- Prepare Semi-Con Shield
Remove the semi-con shield and install a tape marker to the dimensions shown in the diagram (10-1/4” (26.04cm) from the end of the cable insulation, and 11-1/4” (28.58cm) from the end of the semi-con shield). Do not cut or nick the cable insulation.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45˚ angle, approximately 1/4” (6mm) back. Thoroughly clean, then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4 3/4” – 5” (12.06cm – 12.7cm). If the length is incorrect, redo the assembly.
- Position Holding Collar
Position the holding collar over the conductor and flush against the cable adapter. Using the supplied hex wrench, tighten the setscrew. The exposed conductor length should be 4 3/8” – 4 3/4” (11.11cm – 12.06cm).
- Insert Conductor into Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Make sure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If the distance is over 7” (17.8cm), do not proceed and redo all previous work.
- Confirm Component Orientation and Alignment
Confirm that components are oriented in the order: Receptacle Housing, Cable Adapter, Crimp Connector, Contact Adapter. Crucially, confirm that the bolt hole in the crimp connector is aligned with the bolt hole in the contact adapter.
- Crimp Connectors
Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90˚. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7” (17.8cm), do not proceed and redo all previous work.
- Assemble and Torque Bolt
Assemble the washers and bolt in the following order: Flat washer against the spade contact, Belleville washer (concave side down), hex-head bolt. Hand tighten. The splice and cables are now in their final positions. Using a torque wrench with a 15/16 socket, tighten to 50-60 ft.-lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate Cable and Bushing Adapters
Apply supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter and the area of the bushing adapter as shown in the diagram. Do not substitute other lubricants, as they may be harmful to this product or its mating product.
- Seat Receptacle Housing and Ground
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the supplied nylon venting rod. Slide the receptacle housing onto the bushing converter until fully seated. Remove the venting rod. Connect a short piece of No. 14 AWG copper wire (or equivalent) to the grounding eye of the receptacle housing, making a small loop and twisting tightly without damaging the eye. Gather the concentric neutral wires. Using a suitable connector, connect the neutral wires and the grounding wire.
- Secure with Hose Clamp (35kV Only)
For 35kV installations only, position the hose clamp between the locator bumps on the receptacle housing. Tighten the clamp until an audible click is heard.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.