Authorized ABB Distributor (Installation Products)
ABB - Installation Products K650LK-C - 25kV 600 Series Deadbreak Cam-Op Link

ABB Installation Products K650LK-C 25kV 600 Series Deadbreak Cam-Op Link

UPC: 783786022014


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

ABB 25kV 600 Series Deadbreak Cam-Op Link (SKU K650LK-C) is a deadbreak connector designed for medium-voltage applications. Manufactured by ABB Electrification, this component is rated for 25A continuous current and supports interrupt ratings from 35kA to 100kA depending on variant. The deadbreak design allows for safe connection and disconnection under load without de-energizing the system. Available with or without load lugs, it provides flexibility for panel or direct cable connections. This product is part of ABB’s 600 Series, known for reliability in industrial and utility power distribution systems. Use cases include switchgear, motor control centers, and distribution panels where medium-voltage deadbreak connections are required.
  • Rated for 25A continuous current
  • Available interrupt ratings: 35kA, 65kA, 100kA
  • Deadbreak design for safe load-side connection/disconnection
  • Options: with or without load lugs
  • Part of ABB’s 600 Series for medium-voltage applications

Specifications

Application
Designed to use pin and socket connectors to provide a visible open on a primary cable system. After testing and grounding the Cam-Op Link is removed providing a visible open. The K650LK-C Cam-Op system can be used to retrofit to existing equipment. The K650LK-C allows hotstick operations to be completed without moving the cable. The Cam connect/disconnect lever allows for easy installation or removal by hotstick. The K650LK-C provides a 200 Amp Loadbreak interface on top for testing and grounding purposes
Material
EPDM-Rubber
Size
3.50 inch (88.9 mm) Diameter, 7.50 inch (190.5 mm) wide, 12.28 inch (312.0 mm) High (not counting Cam-Op Lever). 4.00 inch (101.6 mm) Center Plug to Center Plug
Special Features
25kV, 600 Amp Deadbreak Rated Cam-Op Link. Provides 200 Amp tap for test and ground connections. 100 percent Peroxide-cured insulation. Cam-Op lever for hotstick operation and easy install/remove
Standard
ANSI/IEEE Standard 386
Type
Cam-Op Link
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
12.6600 L
Package Weight (Metric)
5.7430 kg
15/25kV, T-Splice 6-3/4 inch Long Bail Assembly, Made of Stainless Steel, Used for Assisting Cable to Transformer Connections. Non-Current Carrying. The 150TB2 bailing assembly kit consists of a modified hold down bail for securing Elastimold® tee splice K150T to a K150DP Deadbreak insulating plug. This assembly provides positive hold down force between the tee splice and the insulating plug.

150-TB-2

15/25kV, T-Splice 6-3/4 inch Long Bail Assembly, Made of Stainless Steel, Used for Assisting Cable to Transformer Connections. Non-Current Carrying. The 150TB2 bailing assembly kit consists of a modified hold down bail for securing Elastimold® tee splice K150T to a K150DP Deadbreak insulating plug. This assembly provides positive hold down force between the tee splice and the insulating plug.
HMI door mounting kit with 15M cable

181B2258

HMI door mounting kit with 15M cable
Polarizing Cover / Hermaphroditic Cover, Black, Nylon, 8 Position, AMPMODU IV/V

103350-4

Polarizing Cover / Hermaphroditic Cover, Black, Nylon, 8 Position, AMPMODU IV/V
35kV 600 Series Deadbreak Insulating Plug / Stand-Off Plug. Overall Length 5 inch, Widest Diameter 3 inch. Epoxy Housing.

750LB

35kV 600 Series Deadbreak Insulating Plug / Stand-Off Plug. Overall Length 5 inch, Widest Diameter 3 inch. Epoxy Housing.
Link-Op retaining sleeve all voltage classes. 600AT assembly tool required for operation and/or installation of Link-Op.

650RS

Link-Op retaining sleeve all voltage classes. 600AT assembly tool required for operation and/or installation of Link-Op.
Connector 2-Hole Spade Type 3/4 inch - 16 Rod for Riser Pole Units. Quantity of 1 Needed per Phase

35AL-12

Connector 2-Hole Spade Type 3/4 inch - 16 Rod for Riser Pole Units. Quantity of 1 Needed per Phase
Aluma Form bracket for riser-pole mounting for all voltage class use with PCT-1 or PCT-2 terminators

1535AFB-4

Aluma Form bracket for riser-pole mounting for all voltage class use with PCT-1 or PCT-2 terminators
Bracket for riser pole mounting fits overall cable O.D. from 1.195 in. to 1.625 in.

35-MTB4-A

Bracket for riser pole mounting fits overall cable O.D. from 1.195 in. to 1.625 in.

Frequently Asked Questions

What is the K650LK-C Cam-Op system designed for?

The K650LK-C Cam-Op system uses pin and socket connectors to provide a visible open on a primary cable system. It is removed after testing and grounding to provide this visible open.

What is the momentary fault close rating for the 200A loadbreak interface?

The 200A loadbreak interface has a 10kA Sym – 10 Cycles Momentary & Fault Close rating.

What type of insulation does the K650LK-C use?

The K650LK-C features 100% Peroxide-cured insulation.

What items are included in the K650LK-C kit?

Each kit contains one K650LK-C cam-op link, one protective shipping cap 2701-41, installation instructions IS-0409, and three tubes of lubricant 82-08.

What is the momentary rating for the 600A deadbreak connection?

The 600A deadbreak connection has a 25kA Sym – 10 Cycle Momentary rating.

What is the AC one-minute withstand voltage rating?

The AC one-minute withstand voltage rating for the K650LK-C is 40kV AC.

What is the purpose of the 200 Amp Loadbreak interface?

The 200 Amp Loadbreak interface on top of the K650LK-C is provided for testing and grounding purposes.

What Elastimold products are compatible with the K650LK-C?

The K650LK-C mates with Elastimold products including the 370TR test rod, 370GLR grounding elbow, and 275DR/DRG insulated cap.

Can the K650LK-C be operated with a hotstick?

Yes, the K650LK-C allows hotstick operations for easy installation or removal. This feature enables operations without moving the cable.

What is the impulse withstand (BIL) rating of the K650LK-C?

The K650LK-C has a 125kV BIL impulse withstand rating, based on a 1.2 x 50 microsecond wave.

How to Install the LINK-C Deadbreak Cam Link Operable Connector System

This guide provides step-by-step instructions for the installation and initial setup of the LINK-C 600 amp deadbreak cam link operable connector system, including mounting, wiring, and grounding procedures.

Estimated time: 1h 30m

Tools needed:

Torque wrench with 1-inch hex socket, Hot stick, Wire strippers, Suitable tool for 1-inch hex portion

Supplies needed:

ELASTIMOLD supplied lubricant, 600 amp elbow, #14 AWG or #12 AWG solid copper wire, Appropriate connector for grounding wire, Desired mating 200 amp product, Hardware for alignment bracket clamps

  1. Prepare and Install 600 Amp Elbow

    Ensure all apparatus is de-energized before beginning installation. Inspect all components for damage and compatibility. Install the 600 amp elbow onto the cable according to the separate installation instructions provided with the elbow. Ensure it will align with the standoff plug.

  2. Install Bushing Extender

    Clean and thoroughly lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender using ELASTIMOLD supplied lubricant. Install the bushing extender onto the apparatus bushing. Insert the 600ATM into the retainer contact, engage the internal hex broach, and thread into the apparatus bushing using a suitable tool applied to the 1-inch hex portion. Torque to 50-60 ft-lbs.

  3. Install Elbow onto Epoxy Standoff Plug

    Clean and thoroughly lubricate the epoxy standoff plug and both interfaces of the 600 amp elbow with ELASTIMOLD supplied lubricant. Install the elbow onto the epoxy standoff plug. Insert the 600AMT into the retainer contact, engage the internal hex broach, and thread into the epoxy standoff plug through the compression lug hole using a suitable tool applied to the 1-inch hex portion. Torque to 50-60 ft-lbs.

  4. Install Alignment Bracket

    Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware, alternating sides until clamp tabs are flush and tight.

  5. Secure Elbow in Alignment Bracket

    Position the elbow in the alignment bracket so that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket with the supplied hardware, alternating sides until clamp tabs are flush and tight. Ensure the elbow clamp notch faces the cable entrance of the elbow.

  6. Install the LINK-C Connector

    Clean and thoroughly lubricate both 600 ampere interfaces of the LINK-C with ELASTIMOLD supplied lubricant. Align the LINK-C so it is perpendicular to the switch faceplate when inserted. Insert the LINK-C into the bushing extender and elbow, ensuring both lever arms are inside the alignment bracket legs. Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, move the lever arms downward using a hot stick eye to engage the roller pin and move the LINK-C inward until the lever arms are perpendicular to the alignment bracket leg.

  7. Grounding and Mating Product Installation

    Ground the elbow by feeding a #14 AWG or #12 AWG solid copper wire through the grounding eye, twisting it tight, and connecting it to ground. Clean and lubricate the 200 amp interface on the LINK-C. Ground the cable (twist concentric neutral wires or connect ground lead from 20/21MA device to ground). For three-phase installations, tie all grounds from all three phases to a common ground point. Install the desired mating 200 amp product on the 200 amp interface according to its specific installation instructions.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.