Authorized ABB Distributor (Installation Products)
ABB - Installation Products K650-J4-5 - 15/25kV 600 Series Deadbreak 4-Point Junction, Rubber Junction, Stainless Steel U-Straps and Back Plate.

ABB Installation Products K650-J4-5 15/25kV 600 Series Deadbreak 4-Point Junction, Rubber Junction, Stainless Steel U-Straps…

UPC: 783786657971


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB K650-J4-5 is a 15/25kV 600A Deadbreak 4-Way Junction designed for medium-voltage cable splicing and termination in industrial, utility, and renewable energy applications. This deadbreak junction enables safe, energized connections without system de-energization, reducing downtime during installation or maintenance. The fully shielded, fully submersible molded rubber housing is constructed from 100% peroxide-cured EPDM materials, providing high dielectric strength, environmental resistance, and long-term performance in harsh conditions including subsurface, vault, or padmount installations. Key features include a 4-way design for multiple cable terminations, stainless steel U-straps and back plate for robust mechanical support and corrosion resistance, and compatibility with Elastimold® 600A Series Elbow connectors, Bushing Extenders, and Adapters. The junction meets ANSI/IEEE Standard 386 and delivers 600A continuous current with 25kA symmetrical momentary rating (10 cycles). For 15kV class, it supports 8.3kV phase-to-ground and 14.4kV phase-to-phase operating voltages, with 95kV BIL impulse withstand and 34kV AC one-minute withstand. For 25kV class, it supports 16.2kV phase-to-ground and 28kV phase-to-phase, with 140kV BIL impulse withstand and 45kV AC one-minute withstand. Each kit includes the molded junction, mounting hardware, lubricant tubes, installation instructions, and protective caps. Ideal for sectionalizing, looping, tapping, and equipment bypass in power distribution networks, the K650-J4-5 ensures reliable performance in outdoor and underground environments where moisture, UV exposure, and mechanical stress are concerns.
  • 15/25kV voltage class with 600A continuous current rating
  • 4-way design for multiple cable terminations
  • Fully shielded, fully submersible molded rubber housing (100% peroxide-cured EPDM)
  • Stainless steel U-straps and back plate for corrosion-resistant mechanical support
  • Compatible with Elastimold® 600A Series Elbow connectors, Bushing Extenders, and Adapters

Specifications

Application
Designed for subsurface, vault or padmount applications and can be used for sectionalizing, looping, tapping, and equipment bypass
Connection
Push-In
Connection Type
Deadbreak
Current Rating
600 A
Material
EPDM
Material
EPDM-Rubber and Stainless Steel Bracket
Material
Rubber, Stainless Steel
Poles
4
Poles
4-Point
Series
600 Series
Size
600 Series
Special Features
Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provides mating for Elastimold 600 Amp Series Elbow connectors. U-Style Mounting Straps Only
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
4-Point Rubber Junction
Voltage Rating
15/25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
11.5300 L
Package Weight (Metric)
5.2300 kg
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.

J4-6226-15

4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.
15/25kV 600 Series Deadbreak 2-Point Junction, Rubber Junction, Stainless Steel U-Straps and Back Plate.

K650-J2-5

15/25kV 600 Series Deadbreak 2-Point Junction, Rubber Junction, Stainless Steel U-Straps and Back Plate.
15/25kV 600 Series Deadbreak 2-Point Junction, Hardware package consists of brackets and straps only.

K650-J2-6

15/25kV 600 Series Deadbreak 2-Point Junction, Hardware package consists of brackets and straps only.
5 Point Junction, with one 200 Amp Bushing Well Interfaces, two Blank Positions, and two 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.

J5-2BB66-25-N

5 Point Junction, with one 200 Amp Bushing Well Interfaces, two Blank Positions, and two 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.
5 Point Junction, with one 200 Amp Bushing Well Interface, one Blank Position, one 600 Amp Bushing Interface, one Blank Position, one 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.

J5-2B6B6-25-SV-N

5 Point Junction, with one 200 Amp Bushing Well Interface, one Blank Position, one 600 Amp Bushing Interface, one Blank Position, one 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.
5 Point Junction, with one 200 Amp Bushing Well Interfaces, one 600 Amp Bushing Interface, two Blank Positions, and one 600 Amp Bushnig Interface, 25kV, Standard Spacing - 4 inch Centers, No Parking Stand.

J5-26BB6-25-N

5 Point Junction, with one 200 Amp Bushing Well Interfaces, one 600 Amp Bushing Interface, two Blank Positions, and one 600 Amp Bushnig Interface, 25kV, Standard Spacing - 4 inch Centers, No Parking Stand.
5 Point Junction, with one 200 Amp Bushing Well Interface, one Blank Position, one 600 Amp Bushing Interface, one Blank Position, one 600 Amp Bushnig Interface, 25kV, Standard Spacing - 4 inch Centers, No Parking Stand.

J5-2B6B6-25-N

5 Point Junction, with one 200 Amp Bushing Well Interface, one Blank Position, one 600 Amp Bushing Interface, one Blank Position, one 600 Amp Bushnig Interface, 25kV, Standard Spacing - 4 inch Centers, No Parking Stand.
5 Point Junction, with one 200 Amp Bushing Well Interfaces, one 600 Amp Bushing Interface, two Blank Positions, and one 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.

J5-26BB6-25-SV-N

5 Point Junction, with one 200 Amp Bushing Well Interfaces, one 600 Amp Bushing Interface, two Blank Positions, and one 600 Amp Bushnig Interface, 25kV, Spacing - 6-1/2 inch Centers, No Parking Stand.

Frequently Asked Questions

How do I order only the mounting bracket and back plate?

To order only the mounting bracket and back plate, add "-6" at the end of the catalog number.

What is the K650J4 product?

The K650J4 is a 15/25kV, 600 Amp Deadbreak 4-Way Junction. It features a fully shielded, fully submersible molded rubber housing.

What are the primary applications for this junction?

ELASTIMOLD® junctions are designed for subsurface, vault, or padmount applications. They can be used for sectionalizing, looping, tapping, and equipment bypass.

What other products are compatible with the K650J4?

The K650J4 provides mating for Elastimold® 600 A Series Elbow connectors. It also mates with K655 Elbow Connector, K655BE Bushing Extender, and 655BEA3 Bushing Adapter.

What standards does the K650J4 meet?

The K650J4 meets ANSI/IEEE Standard 386, Latest Revision.

What is the maximum operating voltage for 15kV class?

For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.

What is the continuous current rating for the junction?

The continuous current rating for the K650J4 junction is 600 Amp for both 15kV and 28kV voltage classes.

What is the maximum operating voltage for 28kV class?

For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.

What items are included in the K650J4 kit?

Each kit contains one basic molded junction K650J4, mounting hardware 600J4-6, two tubes of lubricant 82-08, installation instructions IS-0207, and four protective caps 650PPC-01.

How do I order the K650J4 with "U" style mounting straps?

To order the K650J4 with "U" style mounting straps only, add "-5" at the end of the catalog number.

How to Install the LINK-C Deadbreak Cam Link Operable Connector System

This guide provides step-by-step instructions for installing the LINK-C 600 amp deadbreak cam link operable connector system. It covers mounting, wiring, and connecting the system to provide a fully shielded, submersible connection between cable and apparatus, including a 200 ampere tap.

Estimated time: 2h

Tools needed:

Hot stick, 600ATM (Operating Tool), Suitable tool (for 1 inch hex), Torque wrench, Wire strippers, Welding equipment

Supplies needed:

ELASTIMOLD supplied lubricant, 3/8-16 x 2 inch studs, Hex nuts, Lockwashers, Spacers (optional), #14 AWG or #12 AWG solid copper wire, Appropriate connectors, Hardware (for clamps)

  1. De-energize Apparatus and Prepare for Installation

    DANGER: All apparatus must be de-energized during installation or removal of part(s). Do not touch or move energized products. Inspect all parts for damage, rating, and compatibility with mating parts. Ensure all required tools are at hand and maintain cleanliness throughout the procedure.

  2. Install the 600 Amp Elbow

    Install the 600 amp elbow onto the cable according to the installation instructions supplied with the elbow, ensuring it will align with the stand-off plug.

  3. Mount Stand-Off Plug (Conditional)

    If using a bolted stand-off plug, weld 3/8-16 x 2” studs to the faceplate according to dimensions. Install three hex nuts onto the studs to support the stand-off plug, ensuring it is in-line with the bushing. Install the stand-off plug over the studs. Secure with lockwashers and hex nuts, tightening to 12 ft-lbs torque. Adjust nuts as required to ensure the top surfaces of the bushing and stand-off plug are in-line.

  4. Install Bushing Extender and Elbow onto Standoff/Bushing

    Clean and lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender with ELASTIMOLD supplied lubricant. Install the bushing extender onto the apparatus bushing. Insert the 600ATM into the retainer contact and engage its internal hex broach. Insert the retainer contact into the bushing extender and thread into the apparatus bushing using a suitable tool applied to the 1” hex portion of the 600ATM, torquing to 50-60 ft-lbs. Clean and lubricate the epoxy standoff plug (if used) and both interfaces of the 600 amp elbow. Install the elbow onto the epoxy standoff plug. Insert the 600AMT into the retainer contact and engage its internal hex broach. Insert the retainer contact into the 600 amp elbow through the compression lug hole and thread into the epoxy standoff plug using a suitable tool applied to the 1” hex portion of the 600AMT, torquing to 50-60 ft-lbs.

  5. Install Alignment Bracket

    Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware and torque by alternating sides until clamp tabs are flush with each other and tight on both sides.

  6. Secure Elbow to Alignment Bracket

    Position the elbow in the alignment bracket such that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket with the supplied hardware and torque by alternating sides until clamp tabs are flush with each other and tight on both sides. Ensure the elbow clamp notch faces the cable entrance of the elbow.

  7. Install the LINK-C Connector

    Clean and lubricate both 600 ampere interfaces of the Link with ELASTIMOLD supplied lubricant. Align the Link such that when inserted into the bushing extender and elbow, it is perpendicular to the switch faceplate. Insert the Link into the bushing extender and elbow, ensuring both lever arms are on the inside of the alignment bracket legs. Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, move the lever arms downward using a hot stick eye, thus engaging the roller pin and moving the Link inward. Continue moving lever arms until perpendicular to the alignment bracket leg.

  8. Ground System and Install Mating Products

    Ground the elbow by feeding a #14 AWG or #12 AWG solid copper wire through the grounding eye on the elbow, twist tight, and connect to ground. Clean and lubricate the 200 amp interface on the Link. Ground, then install the desired mating product on the 200 amp interface per its installation instructions. Ground the cable: if concentric neutral cable is used, twist the concentric neutral wires together and connect to ground using an appropriate connector. If 20MA or 21MA grounding devices are used, connect the ground lead from the device to ground using a suitable connector. For three-phase installations, all grounds from all three phases must be tied to a common ground point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.