ABB Installation Products 756LR-K0230 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 075114333627
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating for medium-voltage applications.
- 600 Series Deadbreak Elbow design for disconnectable connections.
- Integrated test point for safe circuit testing.
- Accommodates cable insulation diameters from 1.090" to 1.310".
- Includes aluminum compression lug, insulated plug, cap, stud, and cable adapter.
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.3100 L |
Package Weight (Metric) | 3.7690 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
755LRTP-P0380-DRG
600 Amp, 35KV, Stick Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
755LRTP-N0380-DRG
600 Amp, 35kV, Stick-Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
755LRTP-J0240-DRG
600 Amp, 35kV, Stick-Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
755LR-P0400-SG3
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. 200ECS-G3 Jacket Seal and Grounding Kit Included.
273RLR-K-5270
200 Amp, 25kV, Loadbreak Replacement Elbow Connector without Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
755LR-P0360-SG3
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. 200ECS-G3 Jacket Seal and Grounding Kit Included.
755LRL0270TL200
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. With Shield Adapter, With 200kV BIL.Frequently Asked Questions
What is the voltage rating for the 756LR elbow?
The 756LR elbow can be used through 35kV.
What are the withstand voltage ratings of the 756LR?
The 756LR has a 150kV BIL impulse, 50kV AC one-minute, and 103kV DC 15-minute withstand rating.
What are the maximum operating voltages for the 756LR?
For the 35kV class, the maximum phase-to-ground operating voltage is 21.1kV and phase-to-phase is 36.6kV.
What are the withstand voltage ratings of the 756LR?
The 756LR has a 150kV BIL impulse, 50kV AC one-minute, and 103kV DC 15-minute withstand rating.
What is the continuous current rating?
The continuous current rating for the 756LR elbow is 600 Amps.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What is the corona extinction voltage?
The corona extinction voltage is 26kV AC at 3pC sensitivity.
What is the continuous current rating?
The continuous current rating for the 756LR elbow is 600 Amps.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What is the corona extinction voltage?
The corona extinction voltage is 26kV AC at 3pC sensitivity.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 756LR and 776LR deadbreak elbow connectors on 35kV class systems, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device (for capacitive test points), Cable stripping tools, Measuring tape or ruler
Supplies needed:
756LR or 776LR Deadbreak Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Cable (appropriate for 35kV class systems), Grounding device (if not using alternate method), Wire (at least No. 14 AWG Copper for grounding), Suitable connector (for grounding wire), Waterproofing material (for cable jacket), Silicone lubricant
- Position and Cut Cable
DANGER: Ensure all apparatus is de-energized before starting. Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable for Connection
Remove the outer jacket (if applicable) and prepare the cable according to its specific type (e.g., non-jacketed concentric neutral, jacketed shield wires) as detailed in the product instructions. Ensure cable insulation, semi-con shield, and outer jacket are cut to the specified lengths (e.g., 10-3/8”, 11-3/8”, 13-5/8” from the end). Refer to specific instructions for UNISHIELD, Lead Sheath, or grounding devices if used.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Carefully remove any protruding cable insulation, cutting it even with the end of the cable adapter without nicking the adapter or conductor. Verify the exposed conductor length is between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If the length is incorrect, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping; it must be less than 7 inches (178mm). Crimp the lug according to its instructions. Wipe off excess inhibitor. Verify the distance from the lug end to the cable adapter is 6-7/8 inches to 7-5/8 inches (175mm-194mm) after crimping.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Apparatus
DANGER: Ensure all apparatus is de-energized. Do not connect or disconnect mating products while energized. Remove protective caps from both the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End of Elbow (if applicable)
If connecting to another mating part on the opposite end of the elbow, clean and lubricate that mating part. Insert it into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug (if used)
If using an insulating plug as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place. CAUTION: This plug provides a means for detecting system voltage; follow voltage test directions.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper) through the grounding eye and twist to form a small loop, avoiding damage to the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded either via a grounding device (following its instructions) or an alternate method. It is also recommended to waterproof the cable jacket to prevent moisture ingress.
- Perform Voltage Test (Safety Check)
CAUTION: Ensure all 600amp L-Kit components are torqued to specifications. To test for voltage, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points, following its manufacturer's directions. Do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the cap with silicone lubricant and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.