Overview
- 600 Amp, 35kV rating for medium-voltage applications
- Accommodates cable insulation diameters from 1.370" to 1.630"
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for secure conductor connection
- Supports various conductor sizes: 300/350 AWG, 150 mm²
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 300 kcmil , 350 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-K2290-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
755LR-L2290
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.
755LR-M0260
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-L0330
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
755LR-L0300
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
755LR-L0270
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
755LR-K0330-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. 200ECS Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the primary application of the 755LR?
The 755LR is designed for fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the continuous current rating of the 755LR?
The 755LR has a continuous current rating of 600 Amps.
What is the corona extinction voltage?
The corona extinction voltage is 26kV AC at 3pC sensitivity.
What is the DC 15-minute withstand voltage?
The DC 15-minute withstand voltage is 103kV.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the impulse withstand rating?
The impulse withstand (BIL) rating is 150kV (1.2 x 50 microsecond wave).
What is the maximum operating voltage for the 755LR?
The maximum phase-to-ground operating voltage is 21.1kV, and maximum phase-to-phase is 36.6kV.
What standard does the 755LR meet?
The 755LR meets ANSI/IEEE Standard 386, Latest Revision.
What insulation diameters does the 755LR support?
The 755LR supports insulation diameters from 0.760 in to 2.120 in.
What conductor sizes are compatible with the 755LR?
It is compatible with #2 AWG to 1250 kcmil for aluminum and copper conductors.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 755/775LR Deadbreak Elbow Connectors, ensuring fully shielded, submersible deadfront cable connections for 35kV class systems. All apparatus must be de-energized during installation, and this product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Cable preparation tools, Knife or utility blade, Measuring tape or ruler, Wire brush (for aluminum conductors), Crimping tool, Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
755/775LR Deadbreak Elbow Connector kit (includes elbow, cable adapter, compression lug, insulating plug, lubricant, stud prepack), Grounding wire (at least No. 14 AWG Copper equivalent), Suitable grounding connector, Waterproofing material (for cable jacket, if recommended), HV insulated cap(s) or connector(s) (if replacing shipping covers), Tape marker
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. If using concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable Insulation and Shield
Prepare the cable by removing the outer jacket (if applicable), semi-con shield, and cable insulation according to the specific cable type (e.g., jacketed, non-jacketed, unishield, lead sheath). Refer to the provided diagrams for precise dimensions, typically involving measurements like 10-3/8 inches, 11-3/8 inches, and 13-5/8 inches from the cable end for insulation, semi-con shield, and tape marker respectively. If using a grounding device or shield adapter, follow their specific instructions.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Carefully remove any cable insulation protruding beyond the end of the cable adapter, cutting it flush. Ensure you do not cut or nick the cable adapter or the conductor. Verify that the exposed conductor length is between 4-3/8 inches (111mm) and 4-3/4 inches (121mm); if not, re-do the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Before crimping, measure the 'Check Dimension' (distance from lug end to cable adapter); it must be less than 7 inches (178mm). Crimp the lug according to its specific instructions. After crimping, wipe off any excess inhibitor. Verify the distance from the end of the compression lug to the cable adapter is between 6-7/8 inches (175mm) and 7-5/8 inches (194mm); if not, re-do the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Push the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Finally, remove the tape marker.
- Prepare Elbow and Mating Part
Remove protective caps from both the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud (supplied with the elbow) into it. Thoroughly clean and lubricate both the elbow and the mating part with the provided lubricant, ensuring all surfaces remain clean. DANGER: DO NOT connect or disconnect mating products while energized, and DO NOT energize while disconnected.
- Connect Elbow to Mating Part
Carefully push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Secure Opposite Mating Part (if applicable)
If connecting another mating part to the opposite end of the elbow, clean and lubricate its surface. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part to the specifications provided with its instructions.
- Install Insulating Plug and Cap (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground Cable Shield
Insert one end of a grounding wire (at least No. 14 AWG Copper equivalent) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is properly grounded, either via a grounding device (following its instructions) or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Re-cap
Use the integral capacitance test point to determine if the circuit is energized. First, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor; use only a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can cause false readings. After testing, clean and lubricate the inside of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.